Plan Review Notes
Plan Review Notes For Permit 08120369
Permit Number 08120369
Review Stop P
Sequence Number 1
Notes
Date Text
2009-01-12 11:23:23DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT IR-1 THE CERTIFICATE OF AUTHORIZATION NUMBER IS
 REQUIRED IN THE TITLE BLOCK FOR THE LANDSCAPE ARCHITECT
 BUSINESS AND THE ARCHITECTS LA NUMBER IS INCORRECT IN
 THE TITLE BLOCK. (ON PLANS LA000907, BUT ON THE FLORIDA
 STATE DBPR WEBSITE IT IS LISTED AS LA0000907). FAC
 61G1-16.004 & FS 481.306. PLEASE SHOW CORRECT NUMBERS
 ON TITLE BLOCK. (SEE ATTACHED SHEETS FROM FLA DBPR
 WEBSITE).
  
 2. SHT IR-1 SHOWS NO PIPING. THE CONTROLLER, BACKFLOW,
 & RAIN SENSOR ARE NOT SHOWN AS WELL. PLEASE INDICATE
 THE LOCATION OF THE CONTROLLER, BACKFLOW, & RAIN SENSOR
 . INDICATE IF THE ITEM IS EXISTING OR TO BE INSTALLED
 IN PHASE I. SECTIONS 106.1.1, 608 AND APPENDIX F
 SUBSECTION J AS WELL AS FS 373.62.
  
 3. SHT VC A-1.0 ROOM FINISH SCHEDULE FOR ROOMS 102 &
 103. INDICATE HOW THE WALLS WITHIN 2 FEET OF THE W/C'S
 AND URINAL SHALL BE NONABSORBENT UP TO 4 FEET ABOVE THE
 FLOOR AS REQUIRED IN SECTION 1210.2.
  
 4. SHT VC A-3.0 SUBMIT A DETAIL FOR THE WEST SIDE
 (LEFT) OF THE ROOF TITLED "SECONDARY DRAINAGE OVERFLOW
 SCUPPER IN FLASHING". THERE IS NO DOWNSPOUT OR GUTTER
 INDICATED AND THE RWL DETAIL 1/VC-A-3.0 IS ONLY SHOWN
 ON THE EAST SIDE (RIGHT) OF THE BUILDING. PLEASE
 CLARIFY IF THIS IS THE PRIMARY DRAIN AND WHERE THE RAIN
 WATER FROM THIS DRAIN WILL TERMINATE. SECTIONS 106.1.1,
 106.1.2 &1106 AS WELL AS TABLES 1106.3 & 1106.6.
  
 5. SHT A-6.0 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___W/C:
 A. 11-4.16.5 FLUSH CONTROLS
 ___URINAL:
 A. 11-4.18.4 FLUSH CONTROLS
 ___LAV
 A. 11-4.19.5 FAUCETS
  
 6. ALL A/C & PLUMBING SHEETS. THE SEAL HAS NOT
 IMPRESSED ALL INFORMATION REQUIRED. THE STATE OF
 FLORIDA IS NOT INDICATED ON ANY SHEET. PLEASE RESEAL TO
 IMPRESS ALL INFORMATION REQUIRED. FAC 61G1-23.001 & FS
 471.025.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved