2009-01-24 16:58:46 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. PROVIDE COMPLETE SUBMITTALS OF PRODUCT APPROVALS FOR |
| LOUVERS TO BE USED ON THIS PROJECT, INCLUDING |
| INSTALLATION DETAILS. ENSURE PRODUCT APPROVALS ARE |
| CURRENT IN ACCORDANCE WITH FAC RULE 9B-72. PRODUCT |
| APPROVALS ARE TO BE APPROVED IN WRITING BY THE DESIGNER |
| OF RECORD IN ACCORDANCE WITH FBCB 106.3.3. |
| |
| 2. NOTE #13 ON AC-1 CALLS FOR CONDENSATE TO DISCHARGE |
| IN PLANTERS. CONDENSATE LINES SHALL DISCHARGE AT LEAST |
| 1 FOOT AWAY FROM THE STRUCTURE SIDEWALL IN ACCORDANCE |
| WITH FBCB 1503.6. |
| |
| 3. ARCHITECTURAL DOOR SCHEDULE CALLS FOR MECHANICAL |
| ROOM 105 DOOR TO BE ???FRP.??? DOES THIS REPRESENT |
| FIBERGLASS REINFORCED PLASTIC? MATERIALS EXPOSED WITHIN |
| PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A FLAME |
| SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED |
| INDEX OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE |
| WITH ASTM E 84 PER FBCM 602.2.1. PROVIDE A |
| NONCOMBUSTIBLE DOOR AT THIS LOCATION OR PROVIDE ASTM |
| E84 DATA FOR THE SPECIFIED DOOR. |
| |
| 4. PROVIDE SHUTOFF DAMPER CONTROLS FOR THE AHU1 OUTSIDE |
| AIR INTAKE IN ACCORDANCE WITH FBCB 13-409.1.ABC.3.3. |
| |
| 5. FOR OUTDOOR CONDENSING UNITS: APPLIANCES AND |
| SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND |
| INSTALLED TO RESIST THE WIND PRESSURES ON THE EQUIPMENT |
| AND THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM |
| 301.13. PROVIDE MANUFACTURERS DATA SHOWING THESE |
| CONDENSING UNITS DESIGNED FOR WIND RESISTANCE. |
| |
| 6. PROVIDE CONFIRMATION THAT THE CONDENSING UNITS ARE |
| TO BE INSTALLED ABOVE BASE FLOOD ELEVATION IN |
| ACCORDANCE WITH FBCM 301.14. |
| |
| 7. PROVIDE ADEQUATE DOCUMENTATION FOR ROOFING SYSTEM TO |
| BE USED, CONFIRMING THAT MINIMUM R-20 INSULATION SHALL |
| BE PROVIDED ABOVE MECHANICAL ROOM 105 AS REQUIRED BY |
| THE MECHANICAL SPECIFICATIONS. |
| NOTE: MINIMUM R-19 IS REQUIRED IN ACCORDANCE WITH FBCB |
| 13-404.1.ABC.2. |
| |
| 8. SHOW HOW WALLS OF MECHANICAL ROOM 105 ARE TO BE |
| FINISHED IN ACCORDANCE WITH FBCM 603.8 AND 603.9. |
| |
| 9. ALTHOUGH THE DOOR SCHEDULE CALLS FOR GASKETED FRAME |
| AND THRESHOLD, IT IS STRONGLY RECOMMENDED THAT A DUCTED |
| RETURN AND OUTSIDE AIR BE PROVIDED IN MECHANICAL ROOM |
| 105 TO AVOID ANY INCIDENTAL RECIRCULATION OF AIR FROM |
| THE MENS RESTROOM AREA INTO THE CONDITIONED VISITOR |
| CENTER AREAS. THIS CHANGE WOULD ALSO NEGATE SOME OF THE |
| REVIEW COMMENTS LISTED ABOVE. RECIRCULATION OF AIR FROM |
| THIS AREA IS PROHIBITED IN ACCORDANCE WITH FBCM |
| 403.2.1. |
| |