Date |
Text |
2009-01-26 15:21:40 | *****DENIED***** |
| |
| |
| 1. ON SHEET LS-1.0, AMEND AND/OR INCLUDE IN THE |
| BUIULDING CODE ANALYSIS - FLORIDA FIRE PREVENTION CODE |
| (2007 EDITION) WHICH IS BASED ON NFPA 1, UNIFORM FIRE |
| CODE, 2006 EDITION AND NFPA 101, LIFE SAFETY CODE, 2006 |
| EDITION |
| |
| 2. THE SCOPE OF WORK SHALL NOT HINDER OR INTEREFERE |
| WITH EMERGENCY ACCESS TO THE SITE OR THE VICINITY |
| THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES, ETC.) . |
| |
| 3. DISPLAY/SHOW THE LOCATION OF THE FIRE HYDRANTS |
| WITHIN 500 FEET OF THE SITE. |
| |
| 4. THE NUMERICAL ADDRESS SHALL BE INCLUDED IN THE TITLE |
| BLOCK OF EACH SUBMITTED PLAN SHEET. |
| |
| 5. IN ADDITION TO ELECTRONIC SWITCHES ON THE DOUBLE |
| CHECK DETECTOR ASSEMBLY AS SHOWN ON PAGE C15, THE |
| BACKFLOW DEVICE SHALL BE EQUIPPED WITH A CHAIN AND |
| LOCK. |
| |
| 6. ON SHEET LS-1.0, SMOKE DETECTORS (SD) ARE SHOWN ON |
| THE LIFE SAFETY PLAN. BE REMINDED THAT SMOKE DETECTORS |
| ARE TIED INTO A FIRE ALARM SYSTEM WHEREAS SMOKE ALARMS |
| (SA) ONLY SOUND WITHIN WITHIN AN AREA AND SHALL NOT |
| ACTUATE THE BUILDING FIRE ALARM SYSTEM. PLEASE VERIFY. |
| |
| 7. ON THE APPROPIATE EXTERIOR ELEVATION, SHOW/DISPALY |
| THE NUMERICAL ADDRESS FOR THIS SITE. AS PER WEST PALM |
| BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 6" IN |
| HEIGHT AND NO LESS THAN 1 " IN WIDTH. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |