Plan Review Notes
Plan Review Notes For Permit 08120369
Permit Number 08120369
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-01-26 15:21:40*****DENIED*****
  
  
 1. ON SHEET LS-1.0, AMEND AND/OR INCLUDE IN THE
 BUIULDING CODE ANALYSIS - FLORIDA FIRE PREVENTION CODE
 (2007 EDITION) WHICH IS BASED ON NFPA 1, UNIFORM FIRE
 CODE, 2006 EDITION AND NFPA 101, LIFE SAFETY CODE, 2006
 EDITION
  
 2. THE SCOPE OF WORK SHALL NOT HINDER OR INTEREFERE
 WITH EMERGENCY ACCESS TO THE SITE OR THE VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES, ETC.) .
  
 3. DISPLAY/SHOW THE LOCATION OF THE FIRE HYDRANTS
 WITHIN 500 FEET OF THE SITE.
  
 4. THE NUMERICAL ADDRESS SHALL BE INCLUDED IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 5. IN ADDITION TO ELECTRONIC SWITCHES ON THE DOUBLE
 CHECK DETECTOR ASSEMBLY AS SHOWN ON PAGE C15, THE
 BACKFLOW DEVICE SHALL BE EQUIPPED WITH A CHAIN AND
 LOCK.
  
 6. ON SHEET LS-1.0, SMOKE DETECTORS (SD) ARE SHOWN ON
 THE LIFE SAFETY PLAN. BE REMINDED THAT SMOKE DETECTORS
 ARE TIED INTO A FIRE ALARM SYSTEM WHEREAS SMOKE ALARMS
 (SA) ONLY SOUND WITHIN WITHIN AN AREA AND SHALL NOT
 ACTUATE THE BUILDING FIRE ALARM SYSTEM. PLEASE VERIFY.
  
 7. ON THE APPROPIATE EXTERIOR ELEVATION, SHOW/DISPALY
 THE NUMERICAL ADDRESS FOR THIS SITE. AS PER WEST PALM
 BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 6" IN
 HEIGHT AND NO LESS THAN 1 " IN WIDTH.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW