2009-01-02 16:58:01BUILDING PLAN REVIEW
 PERMIT: 08120369
 ADD: 100 N CLEMATIS ST
 CONT: CATALFUMO
 TEL: (561)282-8265
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. 106.1* /2004
 SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE
 CODE.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. SHEET
 S-3 INDICATES TWICE TO BE DESIGNED TO THE 2004 FBC WITH
 2006 SUPPLEMENTS, PLEASE UPDATE TO THE 2007
 SUPPLEMENTS.
  
 2) QUEATIONABLE SOILS WITHIN THE PERMIT PACKAGE IS A
 PRELIMINARY REPORT FORM ARDAMAN FILE # 08-2035. WITHIN
 THE REPORT IT STATES "WE WILL PERSENT SPECIFIC
 RECOMMENDATIONS ONCE THE NATURE OF THE BUILDINGS AND
 THE STRUCTURAL LOADS ARE DEFINED." APPRENTLY THERE IS
 ADDITIONAL INFORMATION THAT HAS BEEN SUBMITTED TO
 ARDAMAN SINCE A AUGOR PILE AND GRADE BEAM FOUNDATION
 HAS BEEN DESIGNED.
 PLEASE PROVIDE THE ADDITIONAL SOILS REPORT WITH THE
 RECOMMENDATION FOR AUGOR CAST PLIE SYSTEM.
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 3) BUILDING LOCATION: THIS STRUCTURE IS LOCATED WITH A
 A-5 FLOOD ZONE. THE FINISH FLOOR CAN NOT HAVE A FINISH
 FLOOR ELEVATION LESS THAN 7'-6". AT THE EAST END OF THE
 BUILDING ELECTRIC ROOM# 104 THE FLOOR ELEVATION IS
 INDICATED AT 5'-6" OR 2 FEET BELOW THE ALLOWABLE FINISH
 FLOOR LEVEL.
  
 4) SHEET A1.1 PHASE 1A TEMORARY CONSTRUCTION PLAN,
 INDICATES A 4'-0" WAIDE WALKWAY ON THE WEST SIDE OF THE
 BUILDING. PLEASE GIVE ELEVATION MARKERS ON THIS
 SIDEWALK FROM THE EXISTING SIDEWALK TO THE EXTERIOR
 LANDING IN FORNT OF THE RESTROOMS AT ELEVATION 7'-6".
 THE DIFFERENCE IN GRADE MAY MAKE THIS PORTION OF
 SIDEWALK TO BE CONSIDERED A RAMP AND REQUIRE HANDRAILS
 ON BOTH SIDES, AND GUARD RAILS. 11-4.8.
  
 5) DURING PHASE 1A ARE ALL OF THE PILING AND GRADE
 BEAMS GOING TO BE PLACED AT THIS TIME OR WILL SOME OF
 THIS WORK OCCUR DURING A LATER PHASE?
  
 6) BOTH LS1.0 & VC A-1.0 INDICATE THE STAIRWAY DIRECTLY
 IN FRONT OF THE RESTROOMS. THE HANDRAIL EXTENSIONS (
 HORIZONTAL) ARE MISSING AT THE BOTTOM OF THE STAIRS.
 11-4.9.4(2) SEE FIGURE 11-19(C-D)
  
 7) SHEET VC A-1.0 ACCESS RAMP DETAILS 1& 2 BOTH
 INDICATE HANDRAILS LOCATED 2'-6" ABOVE THE RAMPS
 SURFACE, PLEASE REVIEW 11-4.8.5(5) TOP OF HANDRAIL
 GRIPPING SURFACES SHALL BE MOUNTED BETWEEN 34INCHES AND
 38 INCHES ABOVE THE RAMP SURFACES.
  
 8) SHEET VC A-1.0 ACCES RAMP SECTION INDICATES THE USE
 OF STAINLESS STEEL CABLES ON ALUMINUM POST HANDRAIL
 SYSTEM. SHOW COMPLIANCE WITH:
 1607.7.1.1 CONCENTRATED LOAD.
 HANDRAIL ASSEMBLIES AND GUARDS SHALL BE ABLE TO RESIST
 A SINGLE CONCENTRATED LOAD OF 200 POUNDS (0.89 KN),
 APPLIED IN ANY DIRECTION AT ANY POINT ALONG THE TOP,
 AND HAVE ATTACHMENT DEVICES AND SUPPORTING STRUCTURE TO
 TRANSFER THIS LOADING TO APPROPRIATE STRUCTURAL
 ELEMENTS OF THE BUILDING. THIS LOAD NEED NOT BE ASSUMED
 TO ACT CONCURRENTLY WITH THE LOADS SPECIFIED IN THE
 PRECEDING PARAGRAPH.
 1607.7.1.2 COMPONENTS.
 INTERMEDIATE RAILS (ALL THOSE EXCEPT THE HANDRAIL),
 BALUSTERS AND PANEL FILLERS SHALL BE DESIGNED TO
 WITHSTAND A HORIZONTALLY APPLIED NORMAL LOAD OF 50
 POUNDS (0.22 KN) ON AN AREA EQUAL TO 1 SQUARE FOOT
 (0.093M2), INCLUDING OPENINGS AND SPACE BETWEEN RAILS.
 REACTIONS DUE TO THIS LOADING ARE NOT REQUIRED TO BE
 SUPERIMPOSED WITH THOSE OF SECTION 1607.7.1 OR
 1607.7.1.1.
  
 9) VC A-1.0, VC A-5.0 & VC A-6.0 ALL INDICATE THE USE
 OF HI-LO DRINKING FOUNTAINS SHEET VC A-6.0 INDICATES
 THE MAXIMUM HEIGHT THE UNITS ARE TO BE SEET AT BUT FAIL
 TO INDICATE THE MINIMUMHIGTH TO NOT BE CONSIDERED
 PROTRUDING OBJECTS 11-4.4.1.SEE FIGURE 11-8(A)(B).
  
 10) VC A-3.0 THE LEFT HAND SECTION OF THE ROOF SYSTEM
 THE PLANS INDICATE DRAINAGE OF THE ROOF WITH SECONDARY
 DRAINAGE OVERFLOOW SCUPPER IN FLASHING, FORTHIS AREA OF
 ROOFING SAME ON THE RIGHT SIDE OF ROOF, THIS IS THE
 ONLY DRAINAGE FOR THIS PORTION OF ROOF, ALSO THERE IS
 NO DOWNSPOUT AS LOCATED ON THE RIGHT SIDE OF THE ROOF.
 1503.4.2 & 1503.4.3.
  
 11) DISCREPANCY IN PLANS BETWEEN VC A-3.0 & VC A-7.0
 PLEASE REVIEW WHERE THE TRUE LOWEST POINT IN THE ROOF
 WILL BE AND THE DISTANCE FROM THE FRONT EDGE OF THE
 ROOF. IT APPEARS THE ROOF DRAINS ARE
 LOCATED APPROXIMATELY 5'-9" BACK FROM THE FRONT DEGE OF
 THE ROOF WHERE AS THE SSCUPPERS ARE LOCATED ONLY 4'-0"
 AWAY FROM THE FRONT EDGE OF THE ROOF.SHHE VC A-7.0 IT
 APPEARS THE ROOF DRAINS ARE NOT LOCATED IN THE LOWEST
 PORTION OF ROOF. 1503.4.
  
 12) PLEASE PROVIDE A ROOFING CUT SECTION AT THE ROOF
 DRAINS INDICATING THE TYPE OF INSULATION TO BE
 INSTALLED, PLEASE ALSO NOTE THE ENERGY CALCULATIONS
 INDACATE A MINIMUM OF R-20.4 VALUE FOR ROOF INSULATION.
 WITHIN THE ROOFING PRODUCT APPROVAL PLEASE HIGHLIGHT OR
 CIRCLE THE SUB-SYSTEM TO BE INSTALLED AND PLEASE
 SPECIFY THE TYPE OF INSULATION AND HICKNESS IT WILL
 TAKE TO MEET THE REQUIREMEENTS OF THE ENERGY CODE,
 PLEASE SEE BOAFS INFORMAL INTERPRETATION ON
 13-404.ABCD.1
  
 13) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 13A) FIXED WINDOWS/STOREFRONT
 13B) EXTERIOR GLAZED DOORS
 13C) EXTERIOR HOLLOW METAL DOORS
 13D) METAL WALL PANELS
 13E) WALL LOUVERS
 13F) SOFFIT MATERIALS
 13G) ROOFING SYSTEMS
  
 THE DESIGNER OF RECORD HAS ISSUED A LETTER WITH THE
 LISTED PRODUCT APPROVALS FOR THE BUILDING, THE
 CONTRACTOR WILL STILL NEED TO SUBMIT 2 COPIES OT HTE
 FULL REPORT FOR VARIFICATION OF PRESSURES, EXCEPTIONS,
 AND LIMITATIONS WITH IN EACH REPORT. EVEN THOUGH SOME
 REPORTS ARE LISTED UNDER THE 2004 FBC WEBSITE, THEY MAY
 BE OLDER NOA'S UNDERTHE 2001 FBC WHERE 1 1/3RD STEEL
 INCREASES WERE TAKEN ON
 FASTENERS.
  
 14) S-1A FOUNDATION NOTE# 1 INDICATES ELEVATION 100'-0"
 IS XX.XX' NGVD, PLEASE FILL IN THE UNKNOWNS. FLOOD ZONE
 A5, MINIMUM FLOOR ELEVATION OF 7.5 NGVD. CITY CODE OF
 ORDINANCES.
  
 15) SHEET S-3 INDICATES THE DESIGN TO THE 2004 FBCBASE
 CODE WITH 2006 SUPPLEMENTS, UPDATE TO 2007 SUPPLEMENTS.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.