2009-01-28 13:40:39 | DENIED |
| REFERENCE: |
| FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. SHT A-1 SHOW COMPLIANCE WITH THE FOLLOWING: |
| ___LAV: |
| A. 11-4.19.2 CLEARANCE (29" REQD) |
| B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| C. 11-4.19.5 FAUCETS |
| |
| 2. SHT A-1 SHOW THE WATER CLOSET 1'6" OFF THE WALL TO |
| THE CENTERLINE OF THE FIXTURE. CHAPTER 11 FIGURE 28. -- |
| SHOW THE LAV MINIMUM 15" OFF THE WALL TO THE CENTERLINE |
| OF THE FIXTURE. (FIXTURE SHALL BE CENTERED ON THE 30" |
| MEASUREMENT OF THE 30"X48" CLEAR FLOOR SPACE). |
| |
| 3. SHT A-1 TOILET ROOM. PLEASE INDICATE THE LENGTH AND |
| WIDTH DIMENSIONS OF THE TOILET ROOM AND INDICATE |
| COMPLIANCE WITH THE FINISH REQUIREMENTS PER SECTIONS |
| 1210.1 & 1210.2. FLOOR REQUIREMENTS & WALLS WITHIN 2 |
| FEET OF THE WATER CLOSET SHALL HAVE A SMOOTH, HARD, |
| NONABSORBENT SURFACE. SECTION 106.1.2. |
| |
| 4. SHT MEP-1 PLUMBING NOTES, CODE CRITERIA INDICATES |
| COMPLIANCE WITH THE STANDARD PLUMBING CODE. THE CODE |
| ADOPTED IS THE FBC-2004 PLUMBING CODE WITH 2007 |
| AMENDMENTS. PLEASE INDICATE ON PLANS. SECTION 106.1.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |