Plan Review Notes For Permit 08120340 |
Permit Number |
08120340 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-01-16 15:25:35 | ***DENIED*** | | | | 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | SAFETY TO COMPLY WITH NFPA 101, 2003. PLEASE ADD NOTE | | TO DRAWINGS. | | | | 2) PLEASE INDICATE THE MINIMUM INTERIOR FINISH | | CLASSIFICATION FOR WALLS AND CEILING. | | | | 3) PLEASE SHOW THE LOCATION(S) OF THE REQUIRED 2A-10B,C | | RATED FIRE EXTINGUISHERS. | | | | 4) FIRE SPRINKLER REMODEL TO COMPLY WITH NFPA 13, 2002 | | EDITION. IN ADDITION, SEPARATE SHOP DRAWINGS AND | | PERMITS REQUIRED FOR FIRE SPRINKLER AND FIRE ALARM | | REMODEL IF APPLICABLE PRIOR TO EQUIPMENT INSTALLATION. | | | | 5) WORK SHALL NOT INTERFERE WITH OR INTERUPT THE | | BUILDING FIRE PROTECTION SYSTEMS. | | | | 6) PLEASE ADD THE NUMERICAL ADDRESS TO EACH SHEET | | SUBMITTED FOR REVIEW. | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|