Plan Review Notes
Plan Review Notes For Permit 08120340
Permit Number 08120340
Review Stop E
Sequence Number 1
Notes
Date Text
2008-12-26 17:02:51** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE LISTED ON ELECTRICAL PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 COORDINATE WITH THE SUBMITTED PANEL SCHEDULE.
 240.4,310.16, 408.4
 FBC 106.1.1,106.1.2, 106.3.5.1.2, 106.5. CLARITY,
 COORDINATION AND ADDITIONAL INFORMATION OF RECORD
 PLANS.
  
 3) NOTE: PLEASE OBTAIN MORE INFORMATION ON THE BASE
 BUILDING ELECTRICAL SERVICE WHICH FEEDS THIS TENANT
 SPACE.
 THE SERVICE RISER AS SHOWN IS NOT ENTIRELY ACCURATE.
 THIS SPACE IS NOT FED BY A SEPARATE SERVICE FROM FPL.
 PLEASE REVISE RISER.
 230,225,215.5 ETC
  
 4) NOTE: PLEASE KNOW THAT ALL CONDUITS, CONDUCTORS
 AFTER THE FIRST MEANS OF DISCONNECT IS REQUIRED TO
 CONTAIN EQUIPMENT GROUNDING CONDUCTORS. 250.6,250.24
 ETC. THE METER AS SHOWN IS TENANT METER AND IS REQUIRED
 TO CONTAIN A FLOATING NEUTRAL.
  
 5) NOTE: PLEASE SEE NEC 517.1 FOR HEALTH CARE. THIS IS
 NOW SHOWN AS A DOCTOR?S OFFICE USED FOR EXAMS WHICH IS
 REQUIRED TO MEET 517 PART II. PLEASE SEE 517.10 AND
 REVISE ALL WIRING AS REQUIRED.
 PLEASE KNOW BASED ON A MIXED OCCUPANCY AS SUBMITTED THE
 WIRING METHODS IN THE MEDICAL/EXAM OFFICES SHALL MEET
 517 AS NOTED.
  
 6) NOTE: PLEASE SUBMIT LOAD CALCULATIONS IN ACCORDANCE
 WITH NEC 220. PLEASE SEE 220.112,220.14, 220.42,
 220.43, 220.44 ETC.
 PLEASE SEE 215.3,230.42 FOR ALL CONTINUOUS LOADS WHICH
 ARE REQUIRED TO BE SHOWN AT 125% AND 422.13 FOR
 ELECTRICAL STORAGE TYPE WATER HEATERS.
 THE LOAD CALCULATIONS AS SUBMITTED ARE FOR A
 RESIDENTIAL UNIT ONLY.
  
 7) NOTE: PLEASE SEE 600.5 FOR REQUIRED SIGN CIRCUIT.
 PLEASE SURE THE MINIMUM VA REQUIRED FOR THE SIGN
 CIRCUIT AT A CONTINUOUS LOAD RATING IS FIGURED INTO THE
 CALCULATIONS.
 (1200VA AT 125%).
  
 8) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, .1.3
 AND .1.4 FOR MINIMUM REQUIRED LIGHTING CONTROLS FOR NEW
 INSTALLED.
 PLEASE SEE 13-415.1.ABC.1. THIS IS A TENANT SPACE IN A
 BUILDING GREATER THAN 5K SQ FT.
  
 9) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE LEVELS
 CALCULATIONS FOR NEW BUSINESS AREAS. PLEASE BE SURE TO
 SEE 13-415.2, 13-415.2.ABC.1.1,.1.2.
 PLEASE BE SURE TO SUBMIT A FIXTURE LEGEND FOR ALL NEW
 FIXTURES AND PLEASE BE SURE ALL WATTAGES ETC ARE SHOWN.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved