Date |
Text |
2008-12-26 17:02:51 | ** DENIED REVIEW ** |
| |
| 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES |
| ARE LISTED ON ELECTRICAL PLANS. |
| 2004 FBC W/2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| COORDINATE WITH THE SUBMITTED PANEL SCHEDULE. |
| 240.4,310.16, 408.4 |
| FBC 106.1.1,106.1.2, 106.3.5.1.2, 106.5. CLARITY, |
| COORDINATION AND ADDITIONAL INFORMATION OF RECORD |
| PLANS. |
| |
| 3) NOTE: PLEASE OBTAIN MORE INFORMATION ON THE BASE |
| BUILDING ELECTRICAL SERVICE WHICH FEEDS THIS TENANT |
| SPACE. |
| THE SERVICE RISER AS SHOWN IS NOT ENTIRELY ACCURATE. |
| THIS SPACE IS NOT FED BY A SEPARATE SERVICE FROM FPL. |
| PLEASE REVISE RISER. |
| 230,225,215.5 ETC |
| |
| 4) NOTE: PLEASE KNOW THAT ALL CONDUITS, CONDUCTORS |
| AFTER THE FIRST MEANS OF DISCONNECT IS REQUIRED TO |
| CONTAIN EQUIPMENT GROUNDING CONDUCTORS. 250.6,250.24 |
| ETC. THE METER AS SHOWN IS TENANT METER AND IS REQUIRED |
| TO CONTAIN A FLOATING NEUTRAL. |
| |
| 5) NOTE: PLEASE SEE NEC 517.1 FOR HEALTH CARE. THIS IS |
| NOW SHOWN AS A DOCTOR?S OFFICE USED FOR EXAMS WHICH IS |
| REQUIRED TO MEET 517 PART II. PLEASE SEE 517.10 AND |
| REVISE ALL WIRING AS REQUIRED. |
| PLEASE KNOW BASED ON A MIXED OCCUPANCY AS SUBMITTED THE |
| WIRING METHODS IN THE MEDICAL/EXAM OFFICES SHALL MEET |
| 517 AS NOTED. |
| |
| 6) NOTE: PLEASE SUBMIT LOAD CALCULATIONS IN ACCORDANCE |
| WITH NEC 220. PLEASE SEE 220.112,220.14, 220.42, |
| 220.43, 220.44 ETC. |
| PLEASE SEE 215.3,230.42 FOR ALL CONTINUOUS LOADS WHICH |
| ARE REQUIRED TO BE SHOWN AT 125% AND 422.13 FOR |
| ELECTRICAL STORAGE TYPE WATER HEATERS. |
| THE LOAD CALCULATIONS AS SUBMITTED ARE FOR A |
| RESIDENTIAL UNIT ONLY. |
| |
| 7) NOTE: PLEASE SEE 600.5 FOR REQUIRED SIGN CIRCUIT. |
| PLEASE SURE THE MINIMUM VA REQUIRED FOR THE SIGN |
| CIRCUIT AT A CONTINUOUS LOAD RATING IS FIGURED INTO THE |
| CALCULATIONS. |
| (1200VA AT 125%). |
| |
| 8) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, .1.3 |
| AND .1.4 FOR MINIMUM REQUIRED LIGHTING CONTROLS FOR NEW |
| INSTALLED. |
| PLEASE SEE 13-415.1.ABC.1. THIS IS A TENANT SPACE IN A |
| BUILDING GREATER THAN 5K SQ FT. |
| |
| 9) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE LEVELS |
| CALCULATIONS FOR NEW BUSINESS AREAS. PLEASE BE SURE TO |
| SEE 13-415.2, 13-415.2.ABC.1.1,.1.2. |
| PLEASE BE SURE TO SUBMIT A FIXTURE LEGEND FOR ALL NEW |
| FIXTURES AND PLEASE BE SURE ALL WATTAGES ETC ARE SHOWN. |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |