2009-01-05 14:18:00BUILDING PLAN REVIEW
 PERMIT: 08120340
 ADD: 410 EVERNIA ST # 115
 CONT: R. W. MARRELL
 TEL: (321)609-1686
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS AND
 2004 EXISTING BUILDING CODE.
 PLEASE PROVIDEE TO WHAT LEVEL ALTERATION THIS PROJECT
 WILL BE? EXISTING BUILDING CODE 301.5 THE DESSIGNER OF
 RECORD OR AN OWNER MUST ELECT THE LEVEL OF ALTERATION
 PURSUANT TO SECTION 303,304 AND 305 OF THIS CODE.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H )NUMBER OF FLOORS WITHIN THE BUILDING
  
 3) THE LIVE/ WORK LOFT, IS THIS A MEZANINE AS INDICATED
 IN THE FIRE SPRINKLER PLAN. SEE AATTACHMENT OF HOW TO
 CALCULATE THE ALLOWABLE FLOOR AREA WHEN WALLS ARE ADDED
 BENEATH THE MEZZANINE LEVEL. SECTION 505.2.AREA OF
 MEZZANINE . THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT EXCEED ONE-THIRD OF
 THE AREA OF THAT ROOM OR SPACE IN WHICH THEY ARE
 LOCATED. THE ENCLOSED PORTIONS OF ROOMS SHALL NOT BE
 INCLUDED IN A DETERMINATION OF THE SIZE OF THE ROOM IN
 WHICH THE MEZZANINE IS LOCATED. IN DETERMINING THE
 ALLOWABLE MEZZANINE AREA, THE AREA OF THE MEZZANINE
 SHALL NOT BE INCLUDED IN THE AREA OF THE ROOM. WITH THE
 ADDITIONAL WALLS BELOW THE MEZANINE THE ALLOWABLE SPACE
 IS DECREASED FOR THE MEZZANINE LEVEL.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved