2009-01-27 16:31:34 | DENIED |
| REFERENCE: |
| FBC-2004 PLUMBING |
| CITY WPB MUNICIPAL CODE |
| |
| 1. SHT 3.0P WATER RISER DIAGRAM. NO WATER SUPPLY IS |
| SHOWN TO THE DISHWASHER, NOR TO THE ICE MAKER. PLEASE |
| INDICATE ON THE RISER AND SHOW THE REQUIRED WATER |
| HAMMER ARRESTORS. SECTIONS 106.1.1 & 604.9. -- THERE IS |
| A 1/2" COLD WATER LINE TO "SODA". THIS REQUIRES |
| PROTECTION FROM BACKFLOW PER SECTION 608.16.1. PLEASE |
| SHOW ON SUPPLY LINE. |
| |
| 2. SHT 3.0P SEE GAS REVIEW FOR COMMENTS ON GAS RISER |
| DIAGRAM. TABLE 402.4(2). |
| |
| 3. SHT 3.2M THE SANITARY RISER DIAGRAM DOES NOT RELFECT |
| THE FLOOR PLAN FOR THE FLOOR SINK AT THE 3 COMPARTMENT |
| SINK. PLEASE CORRELATE. SECTION 106.1.1. -- PLEASE |
| CLARIFY "STEAM" FOR INDIRECT FLOOR SINK. PER SECTION |
| 701.7 WASTEWATER WHEN DISCHARGED INTO THE BUILDING |
| DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT HIGHER |
| THAN 140 DEGREES F, (60 DEG C). WHEN HIGHER |
| TEMPERATURES EXIST, APPROVED COOLING METHODS SHALL BE |
| PROVIDED. |
| |
| 4. THE GREASE INTERCEPTOR SHALL BE APPROVED BY THE |
| UTILITY DEPT. INDUSTRIAL PRETREATMENT. PLEASE CONTACT |
| HOLLY MCGRATH, LABORATORY SUPERVISOR BY PHONE (561) |
| 822-2271, OR BY FAX (561) 822-2279 OR BY E-MAIL |
| [email protected]. ARTICLE III SECTION 90-124(7). A |
| WRITTEN DETERMINATION SHALL BE SUBMITTED FOR PERMIT |
| APPROVAL. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |