Plan Review Notes
Plan Review Notes For Permit 08120295
Permit Number 08120295
Review Stop G
Sequence Number 1
Notes
Date Text
2009-01-27 16:09:51DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
  
 1. SHT 3.0P SUBMIT THE FOLLOWING INFORMATION REQUIRED
 FOR THE GAS PERMIT:
  
 A. TYPE OF GAS, (LP OR NATURAL).
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. -- INDICATE THE
 PIPE SIZE OF ALL VALVES. THEY SHALL BE FULL SIZE AS PER
 TABLE 402.4(2). THE PIPE SIZE TO THE UPPER PIZZA OVEN
 IS INDICATED AS 3/4". MINIMUM 1" IS REQUIRED. TABLE
 402.4(2).
  
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  