2009-01-27 16:09:51 | DENIED |
| REFERENCE: |
| FBC-2004 FUEL GAS |
| |
| |
| 1. SHT 3.0P SUBMIT THE FOLLOWING INFORMATION REQUIRED |
| FOR THE GAS PERMIT: |
| |
| A. TYPE OF GAS, (LP OR NATURAL). |
| |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. -- INDICATE THE |
| PIPE SIZE OF ALL VALVES. THEY SHALL BE FULL SIZE AS PER |
| TABLE 402.4(2). THE PIPE SIZE TO THE UPPER PIZZA OVEN |
| IS INDICATED AS 3/4". MINIMUM 1" IS REQUIRED. TABLE |
| 402.4(2). |
| |
| C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |