2008-12-26 15:59:50 | ** DENIED REVIEW ** |
| |
| 1) NOTE: PLEASE SUBMIT COMPLETED LIGHTING SCHEDULE FOR |
| LIGHTING BEING CONTROLLED BY LCP. |
| PLEASE INDICATE THE REQUIRED MINIMUM 10HR BATTERY BACK |
| UP FOR THE ASTRONOMICAL TIME CLOCK. |
| PLEASE SEE SECTION FOR LIGHTING THAT IS REQUIRED TO BE |
| CONTROLLED AT POINT OF ENTRANCE AND SO THAT THE |
| OCCUPANT CAN VISUALLY SEE ALL LIGHTING BEING CONTROLLED |
| OR MEET EXCEPTIONS. AS THIS HAS BEEN A COMMON NOTED ON |
| OTHER PROJECTS PERHAPS A SMALL TYPICAL DETAIL FOR THE |
| TYPICAL KEYPAD BEING USED WHICH SHOWS THE OVER RIDES AS |
| BEING LIT, AND A TYPICAL LABELING OF THE SAME OVER |
| RIDES. PLEASE CALL TO GO OVER THIS IF DESIRED. |
| A TYPICAL KEYPAD IS USED ON MANY PROJECTS WHICH |
| INDICATES THE LIGHTED OVER RIDES AND SIGNAGE. |
| 13-415.1.ABC.1.1,.1.2, .1.3 AND .1.4. |
| .1.4 FOR EXTERIOR. |
| |
| 2) NOTE: PLEASE COMPLETE THE FIXTURE INFORMATION, |
| LEGEND AND PLANS. PLEASE SEE FIXTURES SUCH AS FIXTURE |
| *C* WHICH IS SHOWN ON PLANS IS NOT ON ANY LEGEND. |
| PLEASE SEE FBC 13-415.2.ABC.1.1, AND .1.2. ALL WATTAGES |
| ARE BASED ON THE RATING OF THE FIXTURE NOT THE BULB |
| WATTAGES USED. |
| PLEASE SEE 13-415.2.ABC.1.2 (3.) AS THIS GIVES THE |
| MINIMUM VA TO BE 30VA PER FT OF TRACK OR THE TOTAL |
| NUMBER OF FIXTURES AT THE RATED VA PER FIXTURE WHICH |
| EVER IS GREATER. |
| |
| 3) NOTE: PLEASE SEE 220.43A ALONG WITH COMMENTARY |
| ATTACHED BELOW DIRECTLY FROM THE NEC. THE LOAD USED TO |
| SIZE THE BRANCH CIRCUIT MAY BE THE 180VA ONLY WHEN |
| SIZING THE BRANCH OR THE 200VA PER FT. HOWEVER PER |
| 220.43A, THE LOAD REQUIRED TO SIZE FEEDERS IS 200VA PER |
| FOOT NOT 180VA PER RECEPTACLE. I HAVE EXTRACTED THE |
| SECTION FROM THE CODE. PLEASE READ THE LAST TWO |
| SENTENCES AS THIS IS FROM THE HANDBOOK COMMENTARY WHICH |
| CLEARLY NOTES THE LOAD TO BE FIGURED FOR FEEDERS. |
| |
| **** 220.43 SHOW-WINDOW AND TRACK LIGHTING |
| (A) SHOW WINDOWS FOR SHOW-WINDOW LIGHTING, A LOAD OF |
| NOT LESS THAN 660 VOLT-AMPERES/LINEAR METER OR 200 |
| VOLT-AMPERES/LINEAR FOOT SHALL BE INCLUDED FOR A SHOW |
| WINDOW, MEASURED HORIZONTALLY ALONG ITS BASE. |
| FPN:SEE 220.14(G) FOR BRANCH CIRCUITS SUPPLYING SHOW |
| WINDOWS. |
| |
| THE CALCULATION OF 200 VOLT-AMPERES FOR EACH LINEAR |
| FOOT OF A SHOW WINDOW IS REQUIRED TO DETERMINE THE |
| FEEDER LOAD. SEE THE COMMENTARY FOLLOWING 220.14(G) FOR |
| LOAD CALCULATIONS FOR BRANCH CIRCUITS IN SHOW WINDOWS. |
| |
| *** |
| |
| 4) NOTE: PLEASE SEE 600.5, 215.3, 230.42 ETC AS THE |
| SIGN CIRCUIT IS A LIGHTING LOAD TO BE SHOWN AT 125%. |
| |
| 5) NOTE: NO LIGHTING FOR EGRESS PATH UP TO ELECTRIC |
| EQUIPMENT PANELS IS SHOWN. PLEASE SEE 700.12F, 700.16, |
| NFPA-101 7.8.1.3, 7.8.1.2.2, 7.9.1.2, 7.9.2.2, FBC |
| 1006.1.2 ETC |
| |
| 6) NOTE: PLEASE FBC 108.3. ALL EQUIPMENT, DESIGN COST, |
| MATERIALS AND LABOR SHALL BE INCLUDING EVEN IF ANY OF |
| THESE ITEMS ARE OWNER SUPPLIED. |
| THE APPLIED VALUE FOR SCOPE AS SHOWN IS LOW. THIS |
| COMMENT IS NOT FOR THE DESIGNER. |
| |
| 7) NOTE: PLEASE COORDINATE PANELS AND RISER. SEE PANEL |
| *A* SHOWN AS MLO AND ON RISER AS MCB. |
| 225,230, 215, 240, ETC |
| FBC 106.1.1, 106.1.2 FOR COORDINATION AND CLARITY. |
| |
| 8) NOTE: PLEASE SEE NEC 210.8B2 FOR ALL 15AMP AND 20AMP |
| RECEPTACLES CIRCUITS INSIDE KITCHEN AREAS WHICH ARE |
| REQUIRED TO BE GFI OR GFI PROTECTED. THIS IS REQUIRED |
| WHETHER OR NOT THEY ARE RECEPTACLES ONLY FEEDING |
| COUNTER SPACES. |
| |
| 9) NOTE: PLEASE SEE NOTE AT THE BOTTOM OF SHEET 2.1E |
| WHICH REFERENCES TO SEE SHEET 3.2P FOR ELECTRICAL ON |
| ROOF-TOP, HOWEVER THERE IS NO SHEET 3.2P IN PLANS |
| SUBMITTED. |
| THERE IS HOWEVER A SHEET 3.2M WHICH INDICATES THE ROOF |
| TOP ELECTRICAL. THIS SEEMS TO HAVE BEEN A MISPRINT AND |
| COULD HAVE BEEN REDLINED. HOWEVER SHOULD BE REVISED AT |
| THIS TIME WITH OTHER COMMENTS. |
| |
| 10) NOTE: PLEASE REVISE CODE REFERENCE ON ELECTRICAL |
| PLANS. THE COVER SHEET IS CORRECT HOWEVER SEE 2.0E. |
| FBC 2004 W/2007 REVISIONS. |
| ALSO ANOTHER ITEM WHICH COULD HAVE BEEN REDLINED |
| HOWEVER PLANS WERE COMING BACK FOR CORRECTIONS. |
| |
| 11) NOTE: WHERE IS THE LIGHTING CONTROL PANEL GOING TO |
| BE LOCATED? NOT SHOWN ON LIGHTING OR POWER PLANS. |
| 110.26, 240.24 ETC |
| FBC 106.1.1, .1.2 FOR ADDITIONAL INFORMATION, |
| COORDINATION, AND CLARITY OF RECORD PLANS. |
| |
| 12) NOTE: PLEASE SEE 422.13 AS THE ELECTRIC STORAGE |
| TYPE WATER HEATER LOAD IS REQUIRED TO BE SHOWN AT 125%. |
| PLEASE SEE THE 2005 NEC HANDBOOK WHICH PROVIDES A |
| COMMENTARY OF THE REVISION IN THE 2005 NEC. |
| PLEASE SEE THE LAST SENTENCE OF COMMENTARY. |
| |
| 13) NOTE: PLEASE SEE POWER PLANS. THE WATER HEATER IS |
| BEING SHOWN IN THE BATHROOM ON A RECEPTACLE WHICH IS |
| NOT PERMITTED. ANOTHER WATER HEATER IS SHOWN ON THE |
| SECOND FLOOR EQUIPMENT ROOM AREA LAYOUT HOWEVER THIS |
| SEEMS TO BE THE SAME WATER HEATER. EACH UNIT SHOWN |
| CONTAINS THE SAME CIRCUIT B-37, 39. |
| PLEASE SEE 422.30,31 A DISCONNECTING MEANS OF SOME TYPE |
| IS REQUIRED. THE WATER HEATER ON THE SECOND FLOOR DOES |
| ACTUALLY SHOW THE REQUIRED DISCONNECT. |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |