Plan Review Notes
Plan Review Notes For Permit 08120295
Permit Number 08120295
Review Stop E
Sequence Number 1
Notes
Date Text
2008-12-26 15:59:50** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT COMPLETED LIGHTING SCHEDULE FOR
 LIGHTING BEING CONTROLLED BY LCP.
 PLEASE INDICATE THE REQUIRED MINIMUM 10HR BATTERY BACK
 UP FOR THE ASTRONOMICAL TIME CLOCK.
 PLEASE SEE SECTION FOR LIGHTING THAT IS REQUIRED TO BE
 CONTROLLED AT POINT OF ENTRANCE AND SO THAT THE
 OCCUPANT CAN VISUALLY SEE ALL LIGHTING BEING CONTROLLED
 OR MEET EXCEPTIONS. AS THIS HAS BEEN A COMMON NOTED ON
 OTHER PROJECTS PERHAPS A SMALL TYPICAL DETAIL FOR THE
 TYPICAL KEYPAD BEING USED WHICH SHOWS THE OVER RIDES AS
 BEING LIT, AND A TYPICAL LABELING OF THE SAME OVER
 RIDES. PLEASE CALL TO GO OVER THIS IF DESIRED.
 A TYPICAL KEYPAD IS USED ON MANY PROJECTS WHICH
 INDICATES THE LIGHTED OVER RIDES AND SIGNAGE.
 13-415.1.ABC.1.1,.1.2, .1.3 AND .1.4.
 .1.4 FOR EXTERIOR.
  
 2) NOTE: PLEASE COMPLETE THE FIXTURE INFORMATION,
 LEGEND AND PLANS. PLEASE SEE FIXTURES SUCH AS FIXTURE
 *C* WHICH IS SHOWN ON PLANS IS NOT ON ANY LEGEND.
 PLEASE SEE FBC 13-415.2.ABC.1.1, AND .1.2. ALL WATTAGES
 ARE BASED ON THE RATING OF THE FIXTURE NOT THE BULB
 WATTAGES USED.
 PLEASE SEE 13-415.2.ABC.1.2 (3.) AS THIS GIVES THE
 MINIMUM VA TO BE 30VA PER FT OF TRACK OR THE TOTAL
 NUMBER OF FIXTURES AT THE RATED VA PER FIXTURE WHICH
 EVER IS GREATER.
  
 3) NOTE: PLEASE SEE 220.43A ALONG WITH COMMENTARY
 ATTACHED BELOW DIRECTLY FROM THE NEC. THE LOAD USED TO
 SIZE THE BRANCH CIRCUIT MAY BE THE 180VA ONLY WHEN
 SIZING THE BRANCH OR THE 200VA PER FT. HOWEVER PER
 220.43A, THE LOAD REQUIRED TO SIZE FEEDERS IS 200VA PER
 FOOT NOT 180VA PER RECEPTACLE. I HAVE EXTRACTED THE
 SECTION FROM THE CODE. PLEASE READ THE LAST TWO
 SENTENCES AS THIS IS FROM THE HANDBOOK COMMENTARY WHICH
 CLEARLY NOTES THE LOAD TO BE FIGURED FOR FEEDERS.
  
 **** 220.43 SHOW-WINDOW AND TRACK LIGHTING
 (A) SHOW WINDOWS FOR SHOW-WINDOW LIGHTING, A LOAD OF
 NOT LESS THAN 660 VOLT-AMPERES/LINEAR METER OR 200
 VOLT-AMPERES/LINEAR FOOT SHALL BE INCLUDED FOR A SHOW
 WINDOW, MEASURED HORIZONTALLY ALONG ITS BASE.
 FPN:SEE 220.14(G) FOR BRANCH CIRCUITS SUPPLYING SHOW
 WINDOWS.
  
 THE CALCULATION OF 200 VOLT-AMPERES FOR EACH LINEAR
 FOOT OF A SHOW WINDOW IS REQUIRED TO DETERMINE THE
 FEEDER LOAD. SEE THE COMMENTARY FOLLOWING 220.14(G) FOR
 LOAD CALCULATIONS FOR BRANCH CIRCUITS IN SHOW WINDOWS.
  
 ***
  
 4) NOTE: PLEASE SEE 600.5, 215.3, 230.42 ETC AS THE
 SIGN CIRCUIT IS A LIGHTING LOAD TO BE SHOWN AT 125%.
  
 5) NOTE: NO LIGHTING FOR EGRESS PATH UP TO ELECTRIC
 EQUIPMENT PANELS IS SHOWN. PLEASE SEE 700.12F, 700.16,
 NFPA-101 7.8.1.3, 7.8.1.2.2, 7.9.1.2, 7.9.2.2, FBC
 1006.1.2 ETC
  
 6) NOTE: PLEASE FBC 108.3. ALL EQUIPMENT, DESIGN COST,
 MATERIALS AND LABOR SHALL BE INCLUDING EVEN IF ANY OF
 THESE ITEMS ARE OWNER SUPPLIED.
 THE APPLIED VALUE FOR SCOPE AS SHOWN IS LOW. THIS
 COMMENT IS NOT FOR THE DESIGNER.
  
 7) NOTE: PLEASE COORDINATE PANELS AND RISER. SEE PANEL
 *A* SHOWN AS MLO AND ON RISER AS MCB.
 225,230, 215, 240, ETC
 FBC 106.1.1, 106.1.2 FOR COORDINATION AND CLARITY.
  
 8) NOTE: PLEASE SEE NEC 210.8B2 FOR ALL 15AMP AND 20AMP
 RECEPTACLES CIRCUITS INSIDE KITCHEN AREAS WHICH ARE
 REQUIRED TO BE GFI OR GFI PROTECTED. THIS IS REQUIRED
 WHETHER OR NOT THEY ARE RECEPTACLES ONLY FEEDING
 COUNTER SPACES.
  
 9) NOTE: PLEASE SEE NOTE AT THE BOTTOM OF SHEET 2.1E
 WHICH REFERENCES TO SEE SHEET 3.2P FOR ELECTRICAL ON
 ROOF-TOP, HOWEVER THERE IS NO SHEET 3.2P IN PLANS
 SUBMITTED.
 THERE IS HOWEVER A SHEET 3.2M WHICH INDICATES THE ROOF
 TOP ELECTRICAL. THIS SEEMS TO HAVE BEEN A MISPRINT AND
 COULD HAVE BEEN REDLINED. HOWEVER SHOULD BE REVISED AT
 THIS TIME WITH OTHER COMMENTS.
  
 10) NOTE: PLEASE REVISE CODE REFERENCE ON ELECTRICAL
 PLANS. THE COVER SHEET IS CORRECT HOWEVER SEE 2.0E.
 FBC 2004 W/2007 REVISIONS.
 ALSO ANOTHER ITEM WHICH COULD HAVE BEEN REDLINED
 HOWEVER PLANS WERE COMING BACK FOR CORRECTIONS.
  
 11) NOTE: WHERE IS THE LIGHTING CONTROL PANEL GOING TO
 BE LOCATED? NOT SHOWN ON LIGHTING OR POWER PLANS.
 110.26, 240.24 ETC
 FBC 106.1.1, .1.2 FOR ADDITIONAL INFORMATION,
 COORDINATION, AND CLARITY OF RECORD PLANS.
  
 12) NOTE: PLEASE SEE 422.13 AS THE ELECTRIC STORAGE
 TYPE WATER HEATER LOAD IS REQUIRED TO BE SHOWN AT 125%.
 PLEASE SEE THE 2005 NEC HANDBOOK WHICH PROVIDES A
 COMMENTARY OF THE REVISION IN THE 2005 NEC.
 PLEASE SEE THE LAST SENTENCE OF COMMENTARY.
  
 13) NOTE: PLEASE SEE POWER PLANS. THE WATER HEATER IS
 BEING SHOWN IN THE BATHROOM ON A RECEPTACLE WHICH IS
 NOT PERMITTED. ANOTHER WATER HEATER IS SHOWN ON THE
 SECOND FLOOR EQUIPMENT ROOM AREA LAYOUT HOWEVER THIS
 SEEMS TO BE THE SAME WATER HEATER. EACH UNIT SHOWN
 CONTAINS THE SAME CIRCUIT B-37, 39.
 PLEASE SEE 422.30,31 A DISCONNECTING MEANS OF SOME TYPE
 IS REQUIRED. THE WATER HEATER ON THE SECOND FLOOR DOES
 ACTUALLY SHOW THE REQUIRED DISCONNECT.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  