Plan Review Notes
Plan Review Notes For Permit 08120285
Permit Number 08120285
Review Stop E
Sequence Number 4
Notes
Date Text
2009-08-05 17:39:31 
 ** DENIED REVIEW OF REVISIONS **
  
 1) NOTE: PLANS HAVE BEEN REVISED TO NOW INCLUDE MANUAL
 TRANSFER SWITCH FOR TENANT SPACE. HOW WILL FEED COME
 INTO BUILDING FOR TRANSFER SWITCH?
 PLEASE SHOW HOW THIS WILL TAKE PLACE.
 PLEASE EXPLAIN HOWEVER AND WHERE THE DISCONNECT MEANS
 WILL BE PROVIDED FOR POWER FROM GENERATOR.
 PLEASE SEE 225.34, 225.31-225.39, ALSO 702.11.
  
 2) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW PROPOSED MTS. 90.7,110.3, 702.6.
  
 3) NOTE: PANEL SCHEDULES AND LOAD CALCULATIONS HAVE
 REVISED ITEMS SHOWN IN REV #4 HOWEVER NO OTHER
 ELECTRICAL PLANS FOR LAYOUT OF ELECTRICAL EQUIPMENT WAS
 SUBMITTED TO REVISE THE ACTUAL ITEMS ON PLANS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  