Plan Review Notes
Plan Review Notes For Permit 08120285
Permit Number 08120285
Review Stop P
Sequence Number 2
Notes
Date Text
2009-02-27 17:48:35DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
  
 6. SHT P1 SHOWS THE DISH WASHER DRAINING THROUGH THE
 GREASE TRAP. PER ARTICLE III SECTION 90-124(7)(B)
 GREASE TRAPS ARE TO BE INSTALLED OUTSIDE THE FLLD
 PREPARATION AREA WITH THE DISH WASHER DISCHARGING VIA A
 SEPARATE LINE.
 ****RESPONSE NOTED, BUT THE DISHWASHER IS STILL
 DISCHARGING THRU THE GREAS TRAP. THE DISH WASHER SHALL
 DISCHARGE DOWNSTREAM OF THE GREASE TRAP.
  
 7. OK
 8. OK
 9. OK
 10. OK
  
 11. SHT P2 WATER HEATER PIPING DETAIL SHOWS THE P&T
 DISCHARGE LINE TO THE EXTERIOR AND ALSO TO THE
 EMERGENCY WATER HEATER PAN. THE DETAIL ALSO SHOWS AN
 EXPANSION TANK AND A WATTS MODEL 530 VALVE FOR
 EXPANSION RELIEF. PLEASE CLARIFY. SECTIONS 106.1.1,
 504.6.1 & 607.3.1/607.3.2.
 ****RESPONSE NOTED, BUT THE P/T AND PAN DRAIN ARE NOW
 INDICATING AS BEING RUN TO THE MECHANICAL ROOM. PLEASE
 CLARIFY. PLEASE INDICATE THE "SAFE PLACE OF DISPOSAL"
 FOR THE P/T VALVE AS REQUIRED IN SECTION 504.6.1. ALSO
 THE PAN DRAIN SHALL TERMINATE OVER A SUITABLY LOCATED
 INDIRECT WAST RECEPTOR OR FLOOR DRAIN OR EXTEND TO THE
 EXTERIOR OF THE BUILDING. SECTION 504.7.2. PLEASE
 INDICATE THE TERMINATION POINT FOR THE PAN DRAIN. --
 DETAIL NOW SHOWS THE DRAIN LINE FROM THE WATTS MODEL
 530C THERMAL EXPANSION VALVE DRAINING INTO THE PAN. THE
 WATER HEATER SHALL BE RAISED IN THE PAN TO KEEP IT FROM
 SITTING IN WATER DISCHARGE FROM THE VALVE. SECTION
 303.2.
  
 12. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved