Plan Review Notes
Plan Review Notes For Permit 08120285
Permit Number 08120285
Review Stop E
Sequence Number 2
Notes
Date Text
2009-03-05 09:45:28NOTE ADDED 3/5/08
  
 THE LIFE SAFETY CODE NOTED ON PLANS STATES THE 2005
 EDITION. HOWEVER THERE IS A 2003 OR 2006. THERE IS NO
 2005. THIS PROJECT AS APPLIED FOR PERMIT IS UNDER THE
 2003 NFPA-101. PLEASE ADJUST NOTES WHEN MAKING CHANGES
 TO PLANS.
2009-03-04 14:38:19** DENIED 2ND REVIEW **
  
 ** SOME ITEMS REQUESTED TO SHOW MINIMUM CODE COMPLIANCE
 IS NOW ON PLANS FOR FIRST REVIEW.
  
 1) NOTE: A COMMENT PREVIOUSLY MADE BY THE FIRE MARSHAL
 REVIEWER WITH RESPECT TO CO2 DETECTORS WAS ANSWERED
 WITH A STATEMENT THAT THE OVEN HAS NOW BEEN REMOVED.
 HOWEVER THE FACT IS PER THE ELECTRICAL PLANS THE OVEN
 AS WELL AS THE COOK-TOP STILL EXISTS.
 ** THIS IS NOTED FOR INFORMATION AND WILL BE FORWARDED
 TO THE FIRE REVIEWER. THIS MAY ELECTRICAL PLANS
 DEPENDING ON COMMENTS AND TYPE OF EQUIPMENT BEING
 INSTALLED..
  
 2) NOTE: ON PREVIOUS REVIEW THE CODE SECTION WAS GIVEN
 WITH RESPECT TO THE STORAGE TYPE WATER HEATERS NEEDING
 TO HAVE LOAD FIGURED AS A CONTINUOUS LOAD. THE RESPONSE
 MENTIONS REVISED LOADS ARE NOW SHOWN. HOWEVER THE WATER
 HEATER STATES IT IS SHOWN AT 125% WHICH IS 3KW. IF THE
 UNIT IS 3KW, THEN THE 125% REQUIRED WOULD BE ABOVE
 THIS. THE UNIT ON THE PLANS AS WELL AS THE PLUMBING
 PLANS INDICATES THE BASE KW AT 3KW.
 PLEASE ADJUST. 422.13, 220.
  
 3) NOTE: PREVIOUS REVIEW REQUESTED TO SUBMIT AND SHOW
 LIGHTING PERFORMANCE CALCULATIONS/LIGHTING DENSITIES
 PER 13-415.2,13-415.2.ABC.1.1 AND .1.2.
 THE PLANS HAVE NOW BEEN REVISED TO INCLUDE CALCULATIONS
 HOWEVER CODE COMPLIANCE DOES NOT APPEAR TO BE CORRECT.
 FOR EXAMPLE:
 ROOM #305 DOES NOT INCLUDE ANY OF THE *K* FIXTURES ON
 THE CALCULATIONS. THE BD FIXTURES ARE ALSO SHOWN AT A
 MUCH LOWER WATTAGE ON THE TABLE ALONG WITH A NUMBER OF
 FIXTURES LOWER THEN WHAT IS SHOWN ON PLANS.
 ANOTHER ROOM WOULD BE #307.
  
 FOR EXAMPLE: THE NOTES AT THE BOTTOM OF THE
 CALCULATIONS ALSO STATES THERE ARE LIGHTS EXEMPT PER
 13-415.2.ABC.1.1. PLEASE SEE THIS SECTION OF THE CODE
 WHICH ONLY EXEMPTS LIGHT IN ANY ONE ARE FROM BEING
 FIGURED IN THE CALCULATIONS IF THE OTHER LIGHTING IN
 THE AREA WHICH IS CONTROLLED COMPLETELY SEPARATELY IS
 THE GREATER OF THE TWO. IN ORDER TO USE THIS EXEMPTION,
 THERE MUST BE ALIGHTING SYSTEM OR CONTROLS IN PLACE
 WHICH DOES NOT PERMIT BOTH POSSIBLE AREAS/ZONES ETC
 FROM BEING *ON* AT THE SAME TIME. BASED ON THE LIGHTING
 CONTROLS SHOWN IT IS POSSIBLE FOR ALL LIGHTS TO BE ON
 AT THE SAME TIME.
 IF SUCH SYSTEM EXISTS PLEASE PROVIDE WIRING DETAILS OR
 SYSTEM ON PLANS.
  
 FOR EXAMPLE: THE ARCHITECTURAL PLANS SHOW THE LIGHTING
 FIXTURES AND LAYOUTS WHICH ARE NOT THE SAME ON THE
 ELECTRICAL PLANS. ONE LOCATION WOULD BE ROOM 310.
  
 *** PLEASE BE SIRE TO GO OVER THE REST OF THE
 CALCULATIONS AS THERE ARE OTHER AREAS IN WHICH THE
 LIGHTING CALCULATIONS DO NOT INDICATE THE WATTAGES
 SHOWN ON THE FIXTURE LEGEND. PLEASE KEEP IN MIND THE
 WATTAGES ARE BASED ON THE RATINGS OF THE FIXTURES NOT
 THE BULBS INCLUDING THE POWER FACTORS OF BALLAST ON
 HID/FLUORESCENT FIXTURES.
  
 ** THE ABOVE ARE ONLY A FEW EXAMPLES GIVEN AS A BENEFIT
 TO THE DESIGN TEAM. THESE EXAMPLES MAY NOT BE AN
 EXHAUSTED LIST.
  
 4) NOTE: PLEASE IDENTIFY THE ROOF TOP GFI FOR THE
 CONDENSING UNITS. PER 210.63,210.8B3 NEW COMMENT
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  