2009-03-05 09:45:28 | NOTE ADDED 3/5/08 |
| |
| THE LIFE SAFETY CODE NOTED ON PLANS STATES THE 2005 |
| EDITION. HOWEVER THERE IS A 2003 OR 2006. THERE IS NO |
| 2005. THIS PROJECT AS APPLIED FOR PERMIT IS UNDER THE |
| 2003 NFPA-101. PLEASE ADJUST NOTES WHEN MAKING CHANGES |
| TO PLANS. |
2009-03-04 14:38:19 | ** DENIED 2ND REVIEW ** |
| |
| ** SOME ITEMS REQUESTED TO SHOW MINIMUM CODE COMPLIANCE |
| IS NOW ON PLANS FOR FIRST REVIEW. |
| |
| 1) NOTE: A COMMENT PREVIOUSLY MADE BY THE FIRE MARSHAL |
| REVIEWER WITH RESPECT TO CO2 DETECTORS WAS ANSWERED |
| WITH A STATEMENT THAT THE OVEN HAS NOW BEEN REMOVED. |
| HOWEVER THE FACT IS PER THE ELECTRICAL PLANS THE OVEN |
| AS WELL AS THE COOK-TOP STILL EXISTS. |
| ** THIS IS NOTED FOR INFORMATION AND WILL BE FORWARDED |
| TO THE FIRE REVIEWER. THIS MAY ELECTRICAL PLANS |
| DEPENDING ON COMMENTS AND TYPE OF EQUIPMENT BEING |
| INSTALLED.. |
| |
| 2) NOTE: ON PREVIOUS REVIEW THE CODE SECTION WAS GIVEN |
| WITH RESPECT TO THE STORAGE TYPE WATER HEATERS NEEDING |
| TO HAVE LOAD FIGURED AS A CONTINUOUS LOAD. THE RESPONSE |
| MENTIONS REVISED LOADS ARE NOW SHOWN. HOWEVER THE WATER |
| HEATER STATES IT IS SHOWN AT 125% WHICH IS 3KW. IF THE |
| UNIT IS 3KW, THEN THE 125% REQUIRED WOULD BE ABOVE |
| THIS. THE UNIT ON THE PLANS AS WELL AS THE PLUMBING |
| PLANS INDICATES THE BASE KW AT 3KW. |
| PLEASE ADJUST. 422.13, 220. |
| |
| 3) NOTE: PREVIOUS REVIEW REQUESTED TO SUBMIT AND SHOW |
| LIGHTING PERFORMANCE CALCULATIONS/LIGHTING DENSITIES |
| PER 13-415.2,13-415.2.ABC.1.1 AND .1.2. |
| THE PLANS HAVE NOW BEEN REVISED TO INCLUDE CALCULATIONS |
| HOWEVER CODE COMPLIANCE DOES NOT APPEAR TO BE CORRECT. |
| FOR EXAMPLE: |
| ROOM #305 DOES NOT INCLUDE ANY OF THE *K* FIXTURES ON |
| THE CALCULATIONS. THE BD FIXTURES ARE ALSO SHOWN AT A |
| MUCH LOWER WATTAGE ON THE TABLE ALONG WITH A NUMBER OF |
| FIXTURES LOWER THEN WHAT IS SHOWN ON PLANS. |
| ANOTHER ROOM WOULD BE #307. |
| |
| FOR EXAMPLE: THE NOTES AT THE BOTTOM OF THE |
| CALCULATIONS ALSO STATES THERE ARE LIGHTS EXEMPT PER |
| 13-415.2.ABC.1.1. PLEASE SEE THIS SECTION OF THE CODE |
| WHICH ONLY EXEMPTS LIGHT IN ANY ONE ARE FROM BEING |
| FIGURED IN THE CALCULATIONS IF THE OTHER LIGHTING IN |
| THE AREA WHICH IS CONTROLLED COMPLETELY SEPARATELY IS |
| THE GREATER OF THE TWO. IN ORDER TO USE THIS EXEMPTION, |
| THERE MUST BE ALIGHTING SYSTEM OR CONTROLS IN PLACE |
| WHICH DOES NOT PERMIT BOTH POSSIBLE AREAS/ZONES ETC |
| FROM BEING *ON* AT THE SAME TIME. BASED ON THE LIGHTING |
| CONTROLS SHOWN IT IS POSSIBLE FOR ALL LIGHTS TO BE ON |
| AT THE SAME TIME. |
| IF SUCH SYSTEM EXISTS PLEASE PROVIDE WIRING DETAILS OR |
| SYSTEM ON PLANS. |
| |
| FOR EXAMPLE: THE ARCHITECTURAL PLANS SHOW THE LIGHTING |
| FIXTURES AND LAYOUTS WHICH ARE NOT THE SAME ON THE |
| ELECTRICAL PLANS. ONE LOCATION WOULD BE ROOM 310. |
| |
| *** PLEASE BE SIRE TO GO OVER THE REST OF THE |
| CALCULATIONS AS THERE ARE OTHER AREAS IN WHICH THE |
| LIGHTING CALCULATIONS DO NOT INDICATE THE WATTAGES |
| SHOWN ON THE FIXTURE LEGEND. PLEASE KEEP IN MIND THE |
| WATTAGES ARE BASED ON THE RATINGS OF THE FIXTURES NOT |
| THE BULBS INCLUDING THE POWER FACTORS OF BALLAST ON |
| HID/FLUORESCENT FIXTURES. |
| |
| ** THE ABOVE ARE ONLY A FEW EXAMPLES GIVEN AS A BENEFIT |
| TO THE DESIGN TEAM. THESE EXAMPLES MAY NOT BE AN |
| EXHAUSTED LIST. |
| |
| 4) NOTE: PLEASE IDENTIFY THE ROOF TOP GFI FOR THE |
| CONDENSING UNITS. PER 210.63,210.8B3 NEW COMMENT |
| |
| |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |