Plan Review Notes
Plan Review Notes For Permit 08120285
Permit Number 08120285
Review Stop P
Sequence Number 1
Notes
Date Text
2009-01-05 12:20:35DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
  
 1. SHT T CODE CRITERIA TO INCLUDE THE 2007 AMENDMENTS
 TO THE FBC-2004. SECTION 106.1.1.
  
 2. SHT A1.2 DETAIL G1(3)(4) SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.6 DISPENSERS
 ___FOR LAVS:
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
  
 3. SHT A1.2 DETAIL D1 SHOW THE BACKING REQUIRED FOR THE
 GRAB BARS AT THE W/C FOR ADAPTABILITY. SECTIONS
 11-4.1.3(11) & 11-4.1.6(1)(B).
  
 4. SHT A1.2 DETAIL 9(2) CABINET DOOR ARE NOT APPROVED
 IN THE CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 SECTION 11-4.22.2(1). PLEASE DELETE CABINET DOORS.
  
 5. SHT A2.1 SHOW COMPLIANCE FOR THE FOLLOWING:
 ___FOR SINK:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (SHOW ON FLOOR PLAN SHT
 A1.1).
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
  
 6. SHT P1 SHOWS THE DISH WASHER DRAINING THROUGH THE
 GREASE TRAP. PER ARTICLE III SECTION 90-124(7)(B)
 GREASE TRAPS ARE TO BE INSTALLED OUTSIDE THE FLLD
 PREPARATION AREA WITH THE DISH WASHER DISCHARGING VIA A
 SEPARATE LINE.
  
 7. SHT P1 PER SECTION 1003.3.2 WHERE FOOD WASTE
 GRINDERS CONNECT TO GREASE TRAPS, A SOLIDS INTERCEPTOR
 SHALL SEPARATE THE DISCHARGE BEFORE CONNECTING TO THE
 GREASE TRAP. PLEASE INDICATE IF THERE WILL BE A FOOD
 WASTE GRINDER OR NOT ON PLANS.
  
 8. ALL GREASE INTERCEPTORS AND TRAPS SHALL BE SIZED BY
 THE UTILITY DEPARTMENT, ENVIRONMENTAL COMPLIANCE.
 PLEASE CONTACT HOLLY MCGRATH BY PHONE AT (561)
 822-2200, OR BY FAX AT (561) 822-2279, OR BY E-MAIL AT
 [email protected]. A WRITTEN DETERMINATION IS REQUIRED
 FOR PERMIT APPROVAL. SECTION 90-124(7).
  
 9. SHT P1 FLOOR PLAN AND P2 SANITARY ISOMETRIC RISER
 DIAGRAM. FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE
 RECEPTORS. A FLOOR SINK OR HUB DRAIN IS APPROVED.
 SECTIONS 802.3 & 802.3.2.
  
 10. SUBMIT A CONDENSATE ISOMETRIC RISER DIAGRAM. SHOW
 ALL PIPE SIZES, TRAPS & VENTS. SECTION 106.2.5.1.3.
  
 11. SHT P2 WATER HEATER PIPING DETAIL SHOWS THE P&T
 DISCHARGE LINE TO THE EXTERIOR AND ALSO TO THE
 EMERGENCY WATER HEATER PAN. THE DETAIL ALSO SHOWS AN
 EXPANSION TANK AND A WATTS MODEL 530 VALVE FOR
 EXPANSION RELIEF. PLEASE CLARIFY. SECTIONS 106.1.1,
 504.6.1 & 607.3.1/607.3.2.
  
 12. SHT P3 SAFE WASTE DETAIL SHOWS THE SAFE WASTE
 DOUBLE TRAPPED. THIS IS NOT APPROVED. SECTION 1002.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  