2009-01-05 12:20:35 | DENIED |
| REFERENCE: |
| FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| CITY WPB MUNICIPAL CODE |
| |
| 1. SHT T CODE CRITERIA TO INCLUDE THE 2007 AMENDMENTS |
| TO THE FBC-2004. SECTION 106.1.1. |
| |
| 2. SHT A1.2 DETAIL G1(3)(4) SHOW COMPLIANCE WITH THE |
| FOLLOWING: |
| ___FOR W/C'S: |
| A. 11-4.16.3 HEIGHT |
| B. 11-4.16.6 DISPENSERS |
| ___FOR LAVS: |
| A. 11-4.19.4 EXPOSED PIPES & SURFACES |
| |
| 3. SHT A1.2 DETAIL D1 SHOW THE BACKING REQUIRED FOR THE |
| GRAB BARS AT THE W/C FOR ADAPTABILITY. SECTIONS |
| 11-4.1.3(11) & 11-4.1.6(1)(B). |
| |
| 4. SHT A1.2 DETAIL 9(2) CABINET DOOR ARE NOT APPROVED |
| IN THE CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| SECTION 11-4.22.2(1). PLEASE DELETE CABINET DOORS. |
| |
| 5. SHT A2.1 SHOW COMPLIANCE FOR THE FOLLOWING: |
| ___FOR SINK: |
| A. 11-4.24.4 SINK DEPTH |
| B. 11-4.24.5 CLEAR FLOOR SPACE (SHOW ON FLOOR PLAN SHT |
| A1.1). |
| C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| D. 11-4.24.7 FAUCETS |
| |
| 6. SHT P1 SHOWS THE DISH WASHER DRAINING THROUGH THE |
| GREASE TRAP. PER ARTICLE III SECTION 90-124(7)(B) |
| GREASE TRAPS ARE TO BE INSTALLED OUTSIDE THE FLLD |
| PREPARATION AREA WITH THE DISH WASHER DISCHARGING VIA A |
| SEPARATE LINE. |
| |
| 7. SHT P1 PER SECTION 1003.3.2 WHERE FOOD WASTE |
| GRINDERS CONNECT TO GREASE TRAPS, A SOLIDS INTERCEPTOR |
| SHALL SEPARATE THE DISCHARGE BEFORE CONNECTING TO THE |
| GREASE TRAP. PLEASE INDICATE IF THERE WILL BE A FOOD |
| WASTE GRINDER OR NOT ON PLANS. |
| |
| 8. ALL GREASE INTERCEPTORS AND TRAPS SHALL BE SIZED BY |
| THE UTILITY DEPARTMENT, ENVIRONMENTAL COMPLIANCE. |
| PLEASE CONTACT HOLLY MCGRATH BY PHONE AT (561) |
| 822-2200, OR BY FAX AT (561) 822-2279, OR BY E-MAIL AT |
| [email protected]. A WRITTEN DETERMINATION IS REQUIRED |
| FOR PERMIT APPROVAL. SECTION 90-124(7). |
| |
| 9. SHT P1 FLOOR PLAN AND P2 SANITARY ISOMETRIC RISER |
| DIAGRAM. FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE |
| RECEPTORS. A FLOOR SINK OR HUB DRAIN IS APPROVED. |
| SECTIONS 802.3 & 802.3.2. |
| |
| 10. SUBMIT A CONDENSATE ISOMETRIC RISER DIAGRAM. SHOW |
| ALL PIPE SIZES, TRAPS & VENTS. SECTION 106.2.5.1.3. |
| |
| 11. SHT P2 WATER HEATER PIPING DETAIL SHOWS THE P&T |
| DISCHARGE LINE TO THE EXTERIOR AND ALSO TO THE |
| EMERGENCY WATER HEATER PAN. THE DETAIL ALSO SHOWS AN |
| EXPANSION TANK AND A WATTS MODEL 530 VALVE FOR |
| EXPANSION RELIEF. PLEASE CLARIFY. SECTIONS 106.1.1, |
| 504.6.1 & 607.3.1/607.3.2. |
| |
| 12. SHT P3 SAFE WASTE DETAIL SHOWS THE SAFE WASTE |
| DOUBLE TRAPPED. THIS IS NOT APPROVED. SECTION 1002.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |