2009-01-09 12:04:11 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. THE WOLF VENTLESS HOOD INSTALLED ABOVE THE COOKTOP |
| SHALL BE TESTED IN ACCORDANCE WITH UL 197 FOR |
| COMMERCIAL KITCHEN RECIRCULATING SYSTEMS PER FBCM |
| 507.1(2). PROVIDE SUPPORTING DOCUMENTATION. |
| |
| 2. OTHER HEAT PRODUCING APPLIANCES IN THE KITCHEN (SUCH |
| AS THE OVEN) SHALL BE PROVIDED WITH A TYPE II HOOD IN |
| ACCORDANCE WITH FBCM 507.2.2. |
| |
| 3. AHU HANGING DETAIL CALLS FOR AN AUXILIARY PAN DRAIN |
| FROM AN AUXILIARY DRAIN PAN. THE AUXILIARY PAN DRAIN |
| SHALL DISCHARGE TO A CONSPICUOUS POINT OF DISPOSAL TO |
| ALERT OCCUPANTS IN THE EVENT OF A STOPPAGE OF THE |
| PRIMARY DRAIN IN ACCORDANCE WITH FBCM 307.2.3(1). |
| PLEASE SHOW THE LOCATION OF THE AUXILIARY DRAIN |
| DISCHARGE TO DEMONSTRATE COMPLIANCE WITH THIS SECTION. |
| NOTE: ANY OF THE METHODS OF AUXILIARY/SECONDARY DRAIN |
| PROTECTION LISTED UNDER FBCM 307.2.3 MAY BE EMPLOYED |
| AND SHOWN ON PLANS TO DEMONSTRATE COMPLIANCE. |
| |
| 4. ALUMINUM ROOF STAND APPEARS TO BE OF THE |
| PRE-ENGINEERED TYPE. PRE-ENGINEERED A/C STANDS ARE |
| DEFINED AS STRUCTURAL COMPONENTS IN ACCORDANCE WITH FAC |
| RULE 9B-72. PLEASE PROVIDE PRODUCT APPROVAL FOR THE |
| STAND TO BE USED, REVIEWED AND APPROVED BY THE DESIGNER |
| OF RECORD IN ACCORDANCE WITH FBCB 106.3.3. |
| |
| 5. PLANS CALL FOR AN 18? ELEVATION FROM THE FOOT OF THE |
| A/C STAND TO THE BOTTOM OF THE BEAM. THE ELEVATION OF |
| THE STAND SHALL BE DETERMINED IN ACCORDANCE WITH FBCB |
| TABLE 1509.7 BASED ON THE WIDTH OF THE ELEVATED |
| APPLIANCE. THIS MEASUREMENT SHALL BE FROM ABOVE THE |
| ROOF SURFACE. PROVIDE DIMENSIONS OF THE CONDENSERS TO |
| CONFIRM REQUIRED HEIGHT OF STANDS AND THE SIZE OF |
| CONDENSER ALLOWED ON THE STAND PER THE PRODUCT APPROVAL |
| DOCUMENTATION. |
| |
| 6. MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT |
| ARE EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO |
| RESIST THE WIND PRESSURES IN ACCORDANCE WITH FBCM |
| 301.13. PROVIDE INFORMATION SHOWING OUTDOOR APPLIANCES, |
| SUCH AS CONDENSING UNITS, ARE DESIGNED TO RESIST WIND |
| PRESSURES IN ACCORDANCE WITH THIS SECTION. |
| |
| 7. DETAIL CALLS FOR RUSKIN FIRE/SMOKE DAMPER TO BE |
| INSTALLED AT RATED WALL ASSEMBLIES. PLEASE SHOW HOW |
| SMOKE DAMPERS ARE TO BE ACTUATED IN ACCORDANCE WITH |
| FBCM 607.3.2.1. |
| ALSO, ELECTRICAL PLANS SHOW NO PROVISIONS FOR POWER TO |
| THE SMOKE DAMPER ACTUATING MOTORS. PLEASE COORDINATE |
| MECHANICAL AND ELECTRICAL PLANS IN ACCORDANCE WITH FBCB |
| 106.1.1. |
| |