2009-01-09 12:04:11REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE WOLF VENTLESS HOOD INSTALLED ABOVE THE COOKTOP
 SHALL BE TESTED IN ACCORDANCE WITH UL 197 FOR
 COMMERCIAL KITCHEN RECIRCULATING SYSTEMS PER FBCM
 507.1(2). PROVIDE SUPPORTING DOCUMENTATION.
  
 2. OTHER HEAT PRODUCING APPLIANCES IN THE KITCHEN (SUCH
 AS THE OVEN) SHALL BE PROVIDED WITH A TYPE II HOOD IN
 ACCORDANCE WITH FBCM 507.2.2.
  
 3. AHU HANGING DETAIL CALLS FOR AN AUXILIARY PAN DRAIN
 FROM AN AUXILIARY DRAIN PAN. THE AUXILIARY PAN DRAIN
 SHALL DISCHARGE TO A CONSPICUOUS POINT OF DISPOSAL TO
 ALERT OCCUPANTS IN THE EVENT OF A STOPPAGE OF THE
 PRIMARY DRAIN IN ACCORDANCE WITH FBCM 307.2.3(1).
 PLEASE SHOW THE LOCATION OF THE AUXILIARY DRAIN
 DISCHARGE TO DEMONSTRATE COMPLIANCE WITH THIS SECTION.
 NOTE: ANY OF THE METHODS OF AUXILIARY/SECONDARY DRAIN
 PROTECTION LISTED UNDER FBCM 307.2.3 MAY BE EMPLOYED
 AND SHOWN ON PLANS TO DEMONSTRATE COMPLIANCE.
  
 4. ALUMINUM ROOF STAND APPEARS TO BE OF THE
 PRE-ENGINEERED TYPE. PRE-ENGINEERED A/C STANDS ARE
 DEFINED AS STRUCTURAL COMPONENTS IN ACCORDANCE WITH FAC
 RULE 9B-72. PLEASE PROVIDE PRODUCT APPROVAL FOR THE
 STAND TO BE USED, REVIEWED AND APPROVED BY THE DESIGNER
 OF RECORD IN ACCORDANCE WITH FBCB 106.3.3.
  
 5. PLANS CALL FOR AN 18? ELEVATION FROM THE FOOT OF THE
 A/C STAND TO THE BOTTOM OF THE BEAM. THE ELEVATION OF
 THE STAND SHALL BE DETERMINED IN ACCORDANCE WITH FBCB
 TABLE 1509.7 BASED ON THE WIDTH OF THE ELEVATED
 APPLIANCE. THIS MEASUREMENT SHALL BE FROM ABOVE THE
 ROOF SURFACE. PROVIDE DIMENSIONS OF THE CONDENSERS TO
 CONFIRM REQUIRED HEIGHT OF STANDS AND THE SIZE OF
 CONDENSER ALLOWED ON THE STAND PER THE PRODUCT APPROVAL
 DOCUMENTATION.
  
 6. MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES IN ACCORDANCE WITH FBCM
 301.13. PROVIDE INFORMATION SHOWING OUTDOOR APPLIANCES,
 SUCH AS CONDENSING UNITS, ARE DESIGNED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH THIS SECTION.
  
 7. DETAIL CALLS FOR RUSKIN FIRE/SMOKE DAMPER TO BE
 INSTALLED AT RATED WALL ASSEMBLIES. PLEASE SHOW HOW
 SMOKE DAMPERS ARE TO BE ACTUATED IN ACCORDANCE WITH
 FBCM 607.3.2.1.
 ALSO, ELECTRICAL PLANS SHOW NO PROVISIONS FOR POWER TO
 THE SMOKE DAMPER ACTUATING MOTORS. PLEASE COORDINATE
 MECHANICAL AND ELECTRICAL PLANS IN ACCORDANCE WITH FBCB
 106.1.1.
  