Date |
Text |
2009-01-06 15:59:14 | NOTE ADDED 1/6/08 3:58PM |
| |
| IF BUILDIGN CONTAINS NEW OR EXISTING FIRE ALARM SYSTEM, |
| PLEASE INCLUDE ALL LOCATIONS, DEVICE HIGGHTS AND LEVELS |
| TO MEET THE ADA SECTION OF THE FBC. SEE 11-4.28.1,.2 |
| AND .3. |
2009-01-06 11:48:50 | ** DENIED REVIEW ** |
| |
| |
| |
| 1) NOTE: PLEASE SUBMIT THE REQUIRED LIGHTING |
| PERFORMANCE CALCULATIONS PER 13-415.2, |
| 13-415.2.ABC.1.1, .1.2. |
| PLEASE BE SURE TO COMPLETE THE FIXTURE LEGEND WITH |
| SPECIFIC FIXTURES. CODE COMPLIANCE CAN NOT BE |
| DETERMINED OF LIGHTING LEVELS AND FOR ITEMS SUCH AS |
| TANDEM WIRING PER 13-415.1.ABC.3 NEEDS TO BE CONFIRMED. |
| |
| 2) NOTE: PLEASE SEE NEC 645.4 FOR REQUIREMENTS OF AN IT |
| ROOM. THE PLANS INDICATE AN IT ROOM HOWEVER ALL ITEMS |
| LISTED IN 645.4 ARE NOT SHOWN ON PLANS. |
| NO DISCONNECTING MEANS SHOWN FOR PANEL OR A/C |
| EQUIPMENT. |
| IF THIS IS NOT AN IT ROOM BECAUSE IT DOES NOT MEET ALL |
| ITEMS IN THE SECTION ABOVE THEN *NO* WIRING METHODS AS |
| PERMITTED IN 645 IS PERMITTED. THE FACT IS ALL WIRING |
| SHALL COMPLY WITH CHAPTERS 1-4. |
| PLEASE VERIFY WIRING METHODS, PLEASE VERIFY WHAT THE |
| ACTUAL ROOM DESIGNATION IS GOING TO BE AND PLEASE |
| ADJUST ALL AS REQUIRED. |
| |
| 3) NOTE: PLEASE SEE 13-415.1.ABC.1.1,.1.2 FOR LIGHTING |
| CONTROLS. SOME LOCATIONS ON PLANS ONLY INDICATE WHAT |
| APPEAR TO BE A SINGLE POLE SWITCH AND NOT AN OCCUPANCY |
| SENSOR TYPE OF DEVICE. |
| (IT ROOM ETC). |
| |
| 4) NOTE: PANEL *D* SHOWS HOW THE LOADS WERE DETERMINED |
| PER 220.56 FOR APPLIANCES IN OTHER THAN DWELLING UNITS |
| HOWEVER HOW ARE THE OTHER LOADS SHOWN ON PANEL DERIVED. |
| RECEPTACLES, LIGHTING, CONTINUOUS LOADS? |
| 220.12, 220.14, 220.42, 220.44 ETC. CONTINUOUS LOADS, |
| 215.3,230.42 ETC. |
| WATER HEATER CONTINUOUS LOAD AT 125%. |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |