Plan Review Notes
Plan Review Notes For Permit 08120285
Permit Number 08120285
Review Stop E
Sequence Number 1
Notes
Date Text
2009-01-06 15:59:14NOTE ADDED 1/6/08 3:58PM
  
 IF BUILDIGN CONTAINS NEW OR EXISTING FIRE ALARM SYSTEM,
 PLEASE INCLUDE ALL LOCATIONS, DEVICE HIGGHTS AND LEVELS
 TO MEET THE ADA SECTION OF THE FBC. SEE 11-4.28.1,.2
 AND .3.
2009-01-06 11:48:50** DENIED REVIEW **
  
  
  
 1) NOTE: PLEASE SUBMIT THE REQUIRED LIGHTING
 PERFORMANCE CALCULATIONS PER 13-415.2,
 13-415.2.ABC.1.1, .1.2.
 PLEASE BE SURE TO COMPLETE THE FIXTURE LEGEND WITH
 SPECIFIC FIXTURES. CODE COMPLIANCE CAN NOT BE
 DETERMINED OF LIGHTING LEVELS AND FOR ITEMS SUCH AS
 TANDEM WIRING PER 13-415.1.ABC.3 NEEDS TO BE CONFIRMED.
  
 2) NOTE: PLEASE SEE NEC 645.4 FOR REQUIREMENTS OF AN IT
 ROOM. THE PLANS INDICATE AN IT ROOM HOWEVER ALL ITEMS
 LISTED IN 645.4 ARE NOT SHOWN ON PLANS.
 NO DISCONNECTING MEANS SHOWN FOR PANEL OR A/C
 EQUIPMENT.
 IF THIS IS NOT AN IT ROOM BECAUSE IT DOES NOT MEET ALL
 ITEMS IN THE SECTION ABOVE THEN *NO* WIRING METHODS AS
 PERMITTED IN 645 IS PERMITTED. THE FACT IS ALL WIRING
 SHALL COMPLY WITH CHAPTERS 1-4.
 PLEASE VERIFY WIRING METHODS, PLEASE VERIFY WHAT THE
 ACTUAL ROOM DESIGNATION IS GOING TO BE AND PLEASE
 ADJUST ALL AS REQUIRED.
  
 3) NOTE: PLEASE SEE 13-415.1.ABC.1.1,.1.2 FOR LIGHTING
 CONTROLS. SOME LOCATIONS ON PLANS ONLY INDICATE WHAT
 APPEAR TO BE A SINGLE POLE SWITCH AND NOT AN OCCUPANCY
 SENSOR TYPE OF DEVICE.
 (IT ROOM ETC).
  
 4) NOTE: PANEL *D* SHOWS HOW THE LOADS WERE DETERMINED
 PER 220.56 FOR APPLIANCES IN OTHER THAN DWELLING UNITS
 HOWEVER HOW ARE THE OTHER LOADS SHOWN ON PANEL DERIVED.
 RECEPTACLES, LIGHTING, CONTINUOUS LOADS?
 220.12, 220.14, 220.42, 220.44 ETC. CONTINUOUS LOADS,
 215.3,230.42 ETC.
 WATER HEATER CONTINUOUS LOAD AT 125%.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  