Date |
Text |
2008-12-23 13:43:01 | BUILDING PLAN REVIEW |
| PERMIT: 08120285 |
| ADD: 1919 NORTH FLAGLER DR. |
| CONT: ANDERSON MOORE CONST. |
| TEL: (561)753-7400 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 12/23/08 |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3) SHEET T: PLANS SUBMITTED FOR PERMIT (FIRST TIME |
| REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE |
| 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 4) THE DRAWINGS NEED TO STATE THE TYPE, HEIGHT AND |
| NUMBER OF STORIES OF BUILDING PER TABLE 601 AND 503 AND |
| THE OCCUPANT LOAD PER TABLE 1004.1.2. |
| |
| 5) IF THERE IS A FIRE SPRINKLER SYSTEM IN THE BUILDING |
| PLEASE STATE THIS INFORMATION ON THE DRAWINGS. NOW THE |
| SPACE IS BEING ALTERED, THE DRAWINGS NEED TO SHOW THE |
| LOCATIONS OF THE SPRINKLER HEADS IN RELATION TO THE NEW |
| CONSTRUCTED ROOMS. THE SPRINKLER HEADS CAN BE SHOWN ON |
| THE REFLECTED CEILING PLANS. FBC 106.3.5.1.1(5) FS |
| 553.79 (2). |
| |
| 6) SHEET A1.2 DETAIL D9 BREAK SINKS: 11-4.24.2 SINKS, |
| HEIGHT. SINKS SHALL BE MOUNTED WITH THE COUNTER NO |
| HIGHER THAN 34" ABOVE THE FINISH FLOOR. 11-4.24.3 KNEE |
| CLEARANCE THAT IS AT LEAST 27" HIGH 30" WIDE, AND 19" |
| DEEP SHALL BE PROVIDED UNDERNEATH SINKS. 11-4.24.5 |
| CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT LEAST 30 |
| INCHES BY 48 INCHES COMPLYING WITH SECTION 11-4.2.4 |
| SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD |
| APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN |
| ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 |
| INCHES UNDERNEATH THE SINK TYPE OF FAUCETS 11-4.24.7 |
| ETC. THE MICROWAVE SHALL MEET THE REQUIREMENTS OF |
| 11-4.27: THE CLEAR FLOOR SPACE 11-4.27.2: THE HEIGHT OF |
| THE EQUIPMENT 11-4.27.3 AND THE OPERATION CONTROLS |
| 11-4.27.4. SHOW COMPLIANCE. |
| |
| 7) SHEET A2.2 FLOOR TRANSITION. 11-4.5.2 CHANGES IN |
| LEVEL GREATER THAN 1/2 INCH SHALL BE ACCOMPLISHED BY |
| MEANS OF A RAMP THAT COMPLIES WITH 11-4.7 OR 11-4.8. |
| CHANGES IN LEVEL BETWEEN 1/4 INCH AND 1/2 INCH SHALL BE |
| BEVELED WITH A SLOPE NO GREATER THAN 1:2[SEE FIGURE |
| 7(D)]. IF CARPET OR TILE IS USED ON A GROUND OR FLOOR |
| SURFACE, THE MAXIMUM PILE THICKNESS SHALL BE 1/2 INCH. |
| 11-4.5.3. THE 9/16 INCH TRANSITION STRIP IS GREATER |
| THAN 1/2 INCH. |
| |
| 8) SHEET A2.1: 715.3 THE DOOR SCHEDULE NEED TO STATE |
| THE PROTECTION RATING OF NUMBER 2 IN ACCORDANCE WITH |
| TABLE 715.3. THE GLAZING LOCATED BETWEEN ROOMS 300 AND |
| 301 SHALL BE TESTED IN ACCORDANCE WITH NFPA 257, |
| INCLUDING, THE HOSE STREAM TEST, IN ACCORDANCE WITH |
| 715.4. PROVIDE THE MANUFACTURE INFORMATION FOR THE |
| GLAZING IN THE FIRE WALL. FIRE-PROTECTION-RATED GLAZING |
| SHALL BEAR A LABEL OR OTHER IDENTIFICATION SHOWING THE |
| NAME OF THE MANUFACTURE, THE TEST STANDARD AND THE FIRE |
| PROTECTION RATING. THIS INFORMATION SHALL BE |
| PERMANENTLY AFFIXED: SECTION 715.3.6.3. |
| FIRE-PROTECTION-RATED GLAZING INSTALLED IN FIRE |
| ASSEMBLIES IN AREAS SUBJECT TO HUMAN IMPACT IN |
| HAZARDOUS LOCATIONS SHALL COMPLY WITH CH. 24. |
| |
| 9) PROVIDE DETAIL INFORMATION FOR THE STRUCTURAL |
| FRAMING OF THE SOFFITS IN THE LOBBY AND ENTRY AREAS. |
| ADDITIONAL INFORMATION REQUIRED. 106.1.2* |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| PHONE (561)805-6726 |
| FAX (561) 805-6676 |
| [email protected] |
| |