2009-03-04 16:16:52****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1-10. ADDRESSED.
  
 11. SPECIFY ROOF DESIGN PRESSURE, FBC R301.
  
 2ND REVIEW, NOT ADDRESSED. SEE FBC1609. PLEASE SPECIFY
 PRESSURES AS REQUESTED.
  
 3RD REVIEW, NOT ADDRESSED.
  
 NEW COMMENTS:
  
 PLEASE CHECK ALL INFORMATION ON A1. LEVEL 1 ALTERATION
 DECLARED; THIS IS AN ADDITION, HOW CAN THIS BE A LEVEL
 I? BUILDING TYPE III V DECLARED; PLEASE GIVE CODE
 SECTION WHERE III V IS A BUILDING TYPE. .18 PRESSURE
 COEFFICIENT STATED; THIS IS A PORCH OPEN ON TWO SIDES.
 SHOULDN'T YOU BE DESIGNING TO A PARTIALLY ENCLOSED
 CONDITION? HOW HAVE "ACTUAL LOADS' ON THE TRUSS
 ANCHORAGE SCHEDULE BEEN DETERMINED?
  
 SHUTTER PRODUCT APPRPOVALS SUBMITTED; WHY ARE THEY IN
 THIS PACKAGE? PLEASE REMOVE; IT APPEARS THEY BELONG TO
 A DIFFERENT PERMIT.
  
 A SET HAS BEEN RETAINED. WHEN RESUBMITTING, PROVIDE TWO
 COMPLETE ORIGINAL SETS.
  