Plan Review Notes
Plan Review Notes For Permit 08120272
Permit Number 08120272
Review Stop B
Sequence Number 1
Notes
Date Text
2008-12-29 10:37:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. INFORMATIONAL ONLY - SEPARATE PERMIT REQUIRED, ROOF.
 PLEASE NOTE THAT INFORMATION REGARDING ROOF TILE
 ATTACHMENT WILL BE REQUIRED WITH THE ROOF PERMIT
 APPLICATION. NOA 06-0526.09 SUBMITTED.
  
 2. PLEASE CLARIFY USE OF EXPOSURE B, FBC R301.
  
 3. GOVERNING CODE IS TO INCLUDE 2007
 REVISIONS/SUPPLEMENTS.
  
 4. PLEASE EXPLAIN LEVEL OF ALTERATION 3, FBC EB CHAPTER
 3.
  
 5. PLEASE EXPLAIN CONSTRUCTION TYPE II AND CONSTRUCTION
 TYPE IIIB (BOTH DECLARED IN DIFFERENT PLACES). NOTE
 THAT TYPE IIIB HAS A 2 HOUR EXTERIOR BEARING WALL
 REQUIREMENT. THIS BUILDING IS TWO STORY; ARE ALL
 BEARING WALLS 2 HOUR INCLUDING SECOND FLOOR?
  
 6. HOW WILL TRUSSES CONNECT TO THE LEDGER? NOTHING
 SPECIFIFED. FBC*106, FBC R301.
  
 7. WHAT IS 3" A.B., ROOF FRAMING PLAN?
  
 8. SPECIFY ROOF PITCH, FBC R301. PLANS STATE THAT IT IS
 TO MATCH EXISTING, NOTHING SPECIFIED FOR EXISTING.
  
 9. SPECIFY BEAM CONSTRUCTION. NO INFORMATION PROVIDED.
  
 10. PLANS DO NOT CLEARLY REFLECT SCOPE OF WORK. SITE
 PLAN APPEARS TO SHOW THE SLAB ADJACENT TO HOUSE AS
 EXISTING, AS IT IS NOT INCLUDED WITH THE LABEL "NEW
 CONC SLAB" AS THE OTHER SECTION. BUT THE FOUNDATION
 PLAN SHOWS THIS AREA AS "TYPICAL" WITH A SPEC AND
 FOOTING. PLEASE CORRELATE, FBC*106.
  
 11. SPECIFY ROOF DESIGN PRESSURE, FBC R301.
  
 A SET HAS BEEN RETAINED. WHEN RESUBMITTING, PROVIDE TWO
 COMPLETE ORIGINAL SETS.
  