Plan Review Notes For Permit 08120230 |
Permit Number |
08120230 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-01-26 13:35:17 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE POWER DENSITY CALCULATION ON SHEET E2 IS | | INCORRECT AS IT USES 2.1 W/SQ.FT. TABLE 13-415.2.C.1 | | INDICATES 1.5 W/SQ.FT FOR RETAIL. PLEASE CORRECT THE | | CALCULATION. | | | | 2} THE SQUARE FOOTAGE GIVEN IN THE CALCULATION DOES NOT | | CORRELATE WITH THE SQUARE FOOTAGE ON SHEET A1. | | CORRELATE SAME. | | | | 3} SHEET E4 ELECTRICAL RISER DIAGRAM THE GEC SIZE IS | | NOT INDICATED FOR MAIN2 OF 3 BUT MUST BE A MINIMUM OF | | #4 PER 250.66. INDICATE SIZE. | | | | 4} THE GEC FOR MAIN 3OF 3 IS LABELED AS 4-600KMCM. | | ALTHOUGH NOT A VIOLATION, IF PART OF THE PERMITTED SET | | OF PLANS THEY MUST BE INSTALLED, OR A REVISION WILL BE | | MUST BE SUBMITTED TO MAKE A CHANGE IN THE FUTURE. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|