 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE POWER DENSITY CALCULATION ON SHEET E2 IS
 INCORRECT AS IT USES 2.1 W/SQ.FT. TABLE 13-415.2.C.1
 INDICATES 1.5 W/SQ.FT FOR RETAIL. PLEASE CORRECT THE
 CALCULATION.
  
 2} THE SQUARE FOOTAGE GIVEN IN THE CALCULATION DOES NOT
 CORRELATE WITH THE SQUARE FOOTAGE ON SHEET A1.
 CORRELATE SAME.
  
 3} SHEET E4 ELECTRICAL RISER DIAGRAM THE GEC SIZE IS
 NOT INDICATED FOR MAIN2 OF 3 BUT MUST BE A MINIMUM OF
 #4 PER 250.66. INDICATE SIZE.
  
 4} THE GEC FOR MAIN 3OF 3 IS LABELED AS 4-600KMCM.
 ALTHOUGH NOT A VIOLATION, IF PART OF THE PERMITTED SET
 OF PLANS THEY MUST BE INSTALLED, OR A REVISION WILL BE
 MUST BE SUBMITTED TO MAKE A CHANGE IN THE FUTURE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  