Plan Review Notes
Plan Review Notes For Permit 08120230
Permit Number 08120230
Review Stop P
Sequence Number 1
Notes
Date Text
2008-12-16 09:41:14DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SUBMIT A CODE SUMMARY. SHOW OCCUPANCY OF BUILDING,
 DESIGN CRITERIA (FBC-2004 W/2005, 2006 2007 REVISIONS),
 INDICATE SQUARE FOOTAGE, ETC. SECTION 106.1.1
  
 2. SHT A1 MOST OCCUPANCIES REQUIRE A DRINKING FOUNTAIN.
 ONCE THE OCCUPANCY IS DECLARED, AND IF REQUIRED, A
 DRINKING FOUNTAIN SHALL BE SHOWN ON THE FLOOR PLAN.
  
 3. IF A DRINKING FOUNTAIN IS REQUIRED, THEN SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 4. SHT A4 SHOW COMPLIANCE WITH SECTION 11-4.16.5 FLUSH
 CONTROLS. DETAILS 04(A) & 05(A) SHOW CONTROLS ON THE
 WALL SIDE. CORRELATE WITH DETAIL 01 WHICH SHOWS &
 INDICATES THE CONTROLS ON THE WIDE SIDE.
  
 5. ALL SHEETS WITH MEINHARDT ENGINEERING TITLE BLOCK.
 THE STATE OF FLORIDA INDICATE FOR EB 25980 THE NAME AS
 MEINHARDT OF TEXAS INC. AND THE ADDRESS AS 5429 LBJ
 FREEWAY SUITE 300 DALLAS TAXAS, BUT THE TITLE BLOCKS DO
 NOT INDICATE THIS. PLEASE HAVE THE TITLE BLOCKS REFLECT
 THE NAME AND ADDRESS AS INDICATED IN THE FLORIDA STATE
 DBPR RECORDS. THE FLORIDA INFORMATION CAN ALSO BE
 INCLUDED IN THE TITLE BLOCKS. FAC 61G15-23.002(2) & FS
 471.025.
  
 6. SHT P0 WATER ISOMETRIC WATER RISER DIAGRAM. IDENTIFY
 THE FITTING AT THE TOP OF THE DROP AS IT IS NOT
 INDICATED IN THE PLUMBING LEGEND. IF IT IS AN AIR
 CHAMBER, PLEASE DELETE AS AIR CHAMBERS ARE NOT
 APPROVED. IF IT IS A WATER HAMMER ARRESTOR, THEN THE
 WATER HAMMER ARRESTOR SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201 & SECTION 604.9.
  
 7. SHT P1 SUBMIT A CONDENSATE ISOMETRIC RISER DIAGRAM
 INDICATING ALL PIPE SIZES, TRAPS, AND THE POINT OF
 DISPOSAL. SECTIONS 106.3.5.1.3 AND 314.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  