2008-12-20 11:08:12 | REVIEW #: 1ST | | ACTION: DENIED | | | | REVIEWED FOR COMPLIANCE WITH THE FOLLOWING: | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS, REVISE PLANS | | ACCORDINGLY AND RESUBMIT FOR REVIEW: | | | | 1. PAGE M1 SHOWS A PLENUM RETURN CEILING CAVITY. IN | | ADDITION, THIS PAGE ALSO SHOWS TWO CEILING MOUNTED | | BATHROOM EXHAUST FANS (EF1 AND EF2). THESE FANS ARE | | DISCHARGING THROUGH AN EXHAUST DUCT WHICH IS LOCATED IN | | THE PLENUM CEILING CAVITY. THIS DUCT WOULD BE UNDER A | | POSITIVE PRESSURE. EXHAUST DUCTS UNDER POSITIVE | | PRESSURE SHALL NOT PASS THROUGH DUCTS OR PLENUMS IN | | ACCORDANCE WITH FBCM 601.3. PLEASE SHOW AN EXHAUST | | CONFIGURATION WHICH DOES NOT PLACE A POSITIVELY | | PRESSURIZED EXHAUST DUCT WITHIN THE PLENUM SPACE IN | | ACCORDANCE WITH THIS SECTION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|