Plan Review Notes For Permit 08120230 |
Permit Number |
08120230 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-12-17 16:14:45 | *****UNSAT***** | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WIITH NFPA 241. | | | | 2. IN ORDER TO PREVENT DELAY IN EMERGENCY RESPONSE, HOW | | DOES RESCUE PERSONNEL DISTINGUISH THE PROJECTED TENANT | | SPACE FROM THE OTHER TENANT SPACE(S) ON THE FLOOR | | AND/OR THE BUILDING. PLEASE BE ADVISED THAT IF A SUITE | | NUMBER IS REQUIRED, THAT SUITE NUMBER SHALL BE INCLUDED | | IN THE ADDRESS LOCATED IN THE TITLE BLOCK OF EACH | | SUBMITTED PLAN SHEET. | | | | 3. ON SHEET A1 - CAPTION 3 - LIFE SAFETY PLAN, PLEASE | | EXPLAIN WHY THERE IS NO FIRE ALARM STROBE LOCATED IN | | EACH RESTROOM. | | | | 4. SPECIFY THE NEW INTERIOR FINISH MATERIAL FOR THE | | WALLS AND CEILING IN TERMS OF CLASS A, CLASS B, OR | | CLASS C. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|