Plan Review Notes For Permit 08120230 |
Permit Number |
08120230 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-12-16 16:08:18 | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | THE FORE REFERENCE STANDARDS SHALL BE NOTED ON THE | | PLANS. | | | | 1} PER CHAPTER 13 FBC, SUBCHAPTER 13-400.0.C.4, PROVIDE | | PERFORMANCE CALCULATIONS FOR REVIEW PER 13-415.2. | | | | 2} THE CONDUCTORS FOR THE AIR HANDLERS DO NOT COMPLY | | WITH THE OCP IN THE PANEL SCHEDULES PER 310.16, AND DO | | NOT CORRELATE WITH THE MANUFACTURERS SPEC'S ON SHEET | | MO. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|