2009-11-04 11:13:542004 FBC W/2007 REVISIONS
  
 1)THE REVISION TO CHANGE THE ROOF SHEATHING FASTENING
 ON SHEET S-2 TO 6D RING SHANK NAILS OR 8D COMMON NAILS
 DOES NOT COMPLY WITH THE MINIMUM REQUIREMENTS OF THE
 FBC RESIDENTIAL. SECTION R803.2.3.1 WHICH REQUIRES 8D
 RING SHANK NAILS. EXCEPTION #3 ALLOWS 8D COMMON WHERE
 DESIGN WIND-SPEEDS ARE 100 MPH OR LESS, HOWEVER, THIS
 PROJECT REQUIRES A DESIGN WIND-SPEED OF 140 MPH.
 THEREFORE, 8D RING SHANK NAILS ARE REQUIRED. ALSO SEE
 BOAF INFORMAL INTERPRETATION REPORT NUMBERS 5600 AND
 5954 AT THE LINKS PROVIDED BELOW.
 HTTP://WWW.BOAF.NET/PDF/I-LIST/5600.PDF AND
 HTTP://WWW.BOAF.NET/PDF/I-LIST/5954.PDF
 NOTE: IN THE PROPOSED MODIFICATION TO THE FLORIDA
 BUILDING CODE RESIDENTIAL SECTION R803.2.3, THAT WAS
 ADOPTED INTO THE CODE, TEST RESULTS FROM CLEMSON
 UNIVERSITY (REINHOLD 2000 - 2002, MCKINLEY 2001) AND AT
 THE INTERNATIONAL HURRICANE CENTER - FLORIDA
 INTERNATIONAL UNIVERSITY (REINHOLD, ALVAREZ 2003)
 COMPARED MEAN FAILURE PRESSURE IN PSF FOR 5/8 INCH
 THICK PLYWOOD ROOF SHEATHING PANELS USING BOTH 8D
 COMMON AND 8D RING SHANK NAILS SPACED AT 6 INCHES AND
 ATTACHED TO 2 X 4 SOUTHERN YELLOW PINE RAFTERS WERE
 REFERENCED. THE TESTS SHOWED A MEAN ULTIMATE UPLIFT
 CAPACITY OF 126 PSF FOR PANELS ATTACHED WITH 8D COMMONS
 AND 292 PSF FOR THOSE ATTACHED WITH 8D RING SHANK.
 USING THIS TEST DATA AND A DESIGN PROCEDURE (REINHOLD
 2002) CALCULATED THE DESIGN UPLIFT PRESSURE FOR 19/32
 THICK PLYWOOD ROOF SHEATHING TO BE 58 PSF FOR THE 8D
 COMMON NAILS AND 150 PSF FOR 8D RING SHANK NAILS. THESE
 RESULTS SHOWED THAT THE 8D COMMON NAILS WOULD ONLY MEET
 ALLOWABLE DESIGN UPLIFT PRESSURES FOR SOME LIMITED ROOF
 CONDITIONS, ROOF HEIGHTS AND ONLY UP TO WIND SPEEDS OF
 120 MPH.
  
 2) THE REVISION TO DETAIL C/S3 ON SHEET S3 REMOVING THE
 FIRE RETARDANT FROM THE UNDERSIDE OF THE ROOF SHEATHING
 THAT IS REQUIRED BY FBC R317.2.2 DOES NOT COMPLY WITH
 CODE. ALL PORTIONS OF THE TWO ROOFS SEPARATED BY THE
 COMMON WALL WHERE THE HIGHER ROOF IS LESS THAN 18
 INCHES ABOVE THE LOWER ROOF ARE REQUIRED TO HAVE THE
 FIRE RETARDANT FOR A DISTANCE OF FOUR FEET ON EACH SIDE
 OF THE WALL AS REQUIRED BY FBC R317.2.2.
  