Plan Review Notes
Plan Review Notes For Permit 08120189
Permit Number 08120189
Review Stop B
Sequence Number 5
Notes
Date Text
2009-10-15 11:20:17THE SIGNED AND SEALED LETTER DATED SEPTEMBER 22, 2009
 FROM THE ENGINEER OF RECORD, STEPHEN R. WALSH P.E.#
 33915, STATING THAT THE DRYWALL CEILING WILL SERVE AS A
 RIGID CEILING DIAPHRAGM AND THAT PERMANENT BOTTOM CORD
 LATERAL BRACING IS NOT REQUIRED HAS BEEN REVIEWED. THIS
 IS ACCEPTABLE TO THE BUILDING OFFICIAL, WITH THE
 STIPULATION THAT THE TEMPORARY BOTTOM CORD BRACING
 REQUIRED BY TPI/WTCA BCSI 1 AS REFERENCED BY FBC
 R802.1.6.3 IS INSTALLED AND REMAINS IN PLACE UNTIL THE
 PERMANENT DRYWALL CEILING DIAPHRAGM IS IN PLACE.