Plan Review Notes For Permit 08120189
Permit Number 08120189
Review Stop B
Sequence Number 4
Notes
Date Text
2009-10-01 14:01:34REVISED TRUSS DRAWINGS WERE REVIEWED. BRACKET D FOR
 ROOF GIRDER TRUSSES D1G AND K1G ON S-3 OF PLANS REQUIRE
 REVISIONS. ALSO THE TRUSS ANCHOR DETAIL A ON S-3 NEEDS
 TO BE REVISED FOR ONE END OF ROOF GIRDER K1G. UPLIFT
 CAPACITIES ARE EXCEEDED AND BRACKET WIDTH IS FOR 2
 MEMBER NOT 3 MEMBER GIRDER.
  
 CONTINUOUS LATERAL BRACING AND BOTTOM CORD LATERAL
 BRACING IS REQUIRED IN ACCORDANCE WITH TPI/WTCA
 BCSI-03.