2009-06-15 10:57:43 | 2004 FBC W/2007 REVISIONS |
| NEW TOWNHOUSE (BLDG 9/LOT58) |
| |
| DENIED BY BUILDING |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. (561) 233-5025 |
| |
| 2) THE STRUCTURE IS LOCATED IN AN "AO" FLOOD ZONE. AN |
| ELEVATION CERTIFICATE WILL BE REQUIRED. |
| |
| 3) THE SOIL REPORT CONTAINING THE ORIGINAL SIGNATURES |
| DOES NOT HAVE THE EMBOSSED SEAL OF THE ENGINEER. |
| ORIGINAL SIGNATURES AND EMBOSSED SEALS ARE REQUIRED PER |
| FS 471.025 R401.4 SOIL TESTS. IN AREAS LIKELY TO HAVE |
| EXPANSIVE, COMPRESSIBLE, SHIFTING OR OTHER UNKNOWN SOIL |
| CHARACTERISTICS, THE BUILDING OFFICIAL SHALL DETERMINE |
| WHETHER TO REQUIRE A SOIL TEST TO DETERMINE THE SOIL?S |
| CHARACTERISTICS AT A PARTICULAR LOCATION. THIS TEST |
| SHALL BE MADE BY AN APPROVED AGENCY USING AN APPROVED |
| METHOD. SUBMIT A GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF THE SOIL. |
| |
| 4) FAC 61G1-16.004(6) REQUIRES THE PRINTED NAME OF THE |
| ARCHITECT SEALING THE DOCUMENT TO APPEAR IN THE TITLE |
| BLOCK ON EACH SHEET OF THE PLANS. |
| |
| 5) SUBMIT SIGNED AND SEALED TRUSS DRAWINGS AND LAYOUTS |
| THAT HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER OF |
| RECORD FOR THE STRUCTURE. R502.1.3.4 |
| |
| 6) NOTE: ALTHOUGH THIS BUILDING IS LOCATED IN EXPOSURE |
| CATEGORY B, SOME OF THE STRUCTURES IN THE PROJECT WILL |
| BE LOCATED IN EXPOSURE CATEGORY C, WHICH REQUIRES |
| HIGHER DESIGN PRESSURES THAN EXPOSURE B. IN ORDER FOR |
| THE PLANS TO BE MASTERED, THE STRUCTURES WILL NEED TO |
| BE DESIGNED EXPOSURE C, WHICH IS WORST CASE. SEE FBC |
| R301.2.1.4 R301.2.1.4 EXPOSURE CATEGORY. |
| FOR EACH WIND DIRECTION CONSIDERED, AN EXPOSURE |
| CATEGORY THAT ADEQUATELY REFLECTS THE CHARACTERISTICS |
| OF GROUND SURFACE IRREGULARITIES SHALL BE DETERMINED |
| FOR THE SITE AT WHICH THE BUILDING OR STRUCTURE IS TO |
| BE CONSTRUCTED. FOR A SITE LOCATED IN THE TRANSITION |
| ZONE BETWEEN CATEGORIES, THE CATEGORY RESULTING IN THE |
| LARGEST WIND FORCES SHALL APPLY. ACCOUNT SHALL BE TAKEN |
| OF VARIATIONS IN GROUND SURFACE ROUGHNESS THAT ARISE |
| FROM NATURAL TOPOGRAPHY AND VEGETATION AS WELL AS FROM |
| CONSTRUCTED FEATURES. FOR ANY GIVEN WIND DIRECTION, THE |
| EXPOSURE IN WHICH A SPECIFIC BUILDING OR OTHER |
| STRUCTURE IS SITED SHALL BE ASSESSED AS BEING ONE OF |
| THE FOLLOWING CATEGORIES: 3. EXPOSURE C. OPEN TERRAIN |
| WITH SCATTERED OBSTRUCTIONS, INCLUDING SURFACE |
| UNDULATIONS OR OTHER IRREGULARITIES, HAVING HEIGHTS |
| GENERALLY LESS THAN 30 FEET (9144 MM) EXTENDING MORE |
| THAN 1,500 FEET (457.2 M) FROM THE BUILDING SITE IN ANY |
| QUADRANT. THIS EXPOSURE SHALL ALSO APPLY TO ANY |
| BUILDING LOCATED WITHIN EXPOSURE B-TYPE TERRAIN WHERE |
| THE BUILDING IS DIRECTLY ADJACENT TO OPEN AREAS OF |
| EXPOSURE C-TYPE TERRAIN IN ANY QUADRANT FOR A DISTANCE |
| OF MORE THAN 600 FEET (182.9 M). SHORT-TERM (LESS THAN |
| TWO YEAR) CHANGES IN THE PRE-EXISTING TERRAIN EXPOSURE, |
| FOR THE PURPOSES OF DEVELOPMENT, SHALL NOT BE |
| CONSIDERED OPEN FIELDS. WHERE DEVELOPMENT BUILD OUT |
| WILL OCCUR WITHIN THREE YEARS AND THE RESULTANT |
| CONDITION WILL MEET THE DEFINITION OF EXPOSURE B, |
| EXPOSURE B SHALL BE REGULATING FOR THE PURPOSE OF |
| PERMITTING. THIS CATEGORY INCLUDES FLAT OPEN COUNTRY, |
| GRASSLANDS AND OCEAN OR GULF SHORELINES. THIS CATEGORY |
| DOES NOT INCLUDE INLAND BODIES OF WATER THAT PRESENT A |
| FETCH OF 1 MILE (1.61 KM) OR MORE OR INLAND WATERWAYS |
| OR RIVERS WITH A WIDTH OF 1 MILE (1.61 KM) OR MORE (SEE |
| EXPOSURE D). |
| |
| 7) SHOW COMPLIANCE WITH R314.4 THERMAL BARRIER. |
| UNLESS OTHERWISE NOTED IN SECTION R314.5, FOAM PLASTIC |
| SHALL BE SEPARATED FROM THE INTERIOR OF A BUILDING BY |
| AN APPROVED THERMAL BARRIER OF MINIMUM 0.5 INCH (12.7 |
| MM) GYPSUM WALLBOARD OR AN APPROVED FINISH MATERIAL |
| EQUIVALENT TO A THERMAL BARRIER MATERIAL THAT WILL |
| LIMIT THE AVERAGE TEMPERATURE RISE OF THE UNEXPOSED |
| SURFACE TO NO MORE THAN 250?F (121?C) AFTER 15 MINUTES |
| OF FIRE EXPOSURE COMPLYING WITH THE ASTM E 119 STANDARD |
| TIME TEMPERATURE CURVE. THE THERMAL BARRIER SHALL BE |
| INSTALLED IN SUCH A MANNER THAT IT WILL REMAIN IN PLACE |
| FOR 15 MINUTES BASED ON NFPA 286 WITH THE ACCEPTANCE |
| CRITERIA OF SECTION R315.4, FM4880, UL 1040, OR UL |
| 1715. |
| |
| 8) SHOW COMPLIANCE WITH R314.5.3 ATTICS. |
| WHERE ATTIC ACCESS IS REQUIRED BY SECTION R807.1 AND |
| WHERE ENTRY IS MADE ONLY FOR SERVICE OF UTILITIES, FOAM |
| PLASTICS SHALL BE PROTECTED AGAINST IGNITION BY |
| 1.5-INCH-THICK (38 MM) MINERAL FIBER INSULATION, |
| 1/4-INCH-THICK (6.4 MM) WOOD STRUCTURAL PANELS, |
| 3/8-INCH (9.5 MM) PARTICLEBOARD, 1/4-INCH (6.4 MM) |
| HARDBOARD, 3/8-INCH (9.5 MM) GYPSUM BOARD, OR |
| CORROSION-RESISTANT STEEL HAVING A BASE METAL THICKNESS |
| OF 0.016 INCH (0.406 MM) AND THE THERMAL BARRIER |
| SPECIFIED IN SECTION R314.4 IS NOT REQUIRED. THE |
| IGNITION BARRIER IS NOT REQUIRED WHERE THE FOAM PLASTIC |
| INSULATION HAS BEEN TESTED IN ACCORDANCE WITH SECTION |
| R314.6. |
| |
| 9) SUBMIT MANUFACTURER'S SPECIFICATIONS AND EVALUATION |
| REPORT FOR THE SPRAY FOAM INSULATION (ICYNENE). SEE |
| COMMENTS 7 AND 8 ABOVE. |
| |
| 10) SHOW COMPLIANCE WITH R803.2.3.1 SHEATHING |
| FASTENINGS. |
| WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO |
| ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON |
| CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE |
| FRAMING. WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY, |
| 0.42 < G < 0.49 IS USED, SPACING OF RING-SHANK |
| FASTENERS SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 |
| FOR 130 MPH OR GREATER DESIGN WIND SPEEDS IN ACCORDANCE |
| WITH FIGURE R803.2.3.1. |
| |
| 11) PROVIDE A DETAIL INDICATING THE DESIGN OF THE TWO |
| HOUR FIRE WALL AND ROOF ASSEMBLY AT THE COVERED REAR |
| PATIOS SHOWING COMPLIANCE WITH R317.2.1 CONTINUITY. |
| THE COMMON WALL FOR TOWNHOUSES SHALL BE CONTINUOUS FROM |
| THE FOUNDATION TO THE UNDERSIDE OF THE ROOF SHEATHING, |
| DECK OR SLAB AND SHALL EXTEND THE FULL LENGTH OF THE |
| COMMON WALL INCLUDING WALLS EXTENDING THROUGH AND |
| SEPARATING ATTACHED ACCESSORY STRUCTURES. ALSO SEE |
| 317.2.4 AND R317.2.2. |
| |
| 12) THE OPENING DESIGN PRESSURES FOR THE DOORS IN THE |
| WINDLOAD SCHEDULE ON S-3 AND THE DOOR SCHEDULES ON |
| SHEETS TU-1.0 THRU TU-3.0 DO NOT CORRESPOND. PLEASE |
| CORRECT. FBC R301.2.1 |
| |
| 13) SPECIFY THE INSULATION ON THE PLANS AT THE 2 HOUR |
| FIRE RATED CONCRETE BLOCK AND WOOD FRAME ADJACENT WALLS |
| SEPARATING THE UNITS. THE WALLS ARE REQUIRED TO BE |
| INSULATED FROM THE FLOOR SLAB TO THE SPRAY FOAM |
| INSULATION AT THE ROOF. PLEASE SPECIFY INSULATION TYPE |
| AND R-VALUE ON THE PLANS FOR THE ADJACENT BLOCK WALLS |
| AT THE WOOD TRUSS SECTION OF THE 2 HOUR FIRE RATED |
| ASSEMBLY. ALSO REVISE ENERGY CALCULATION FORMS TO |
| INCLUDE THIS AREA. FBC 13-6. |
| |
| 14) ON SHEET A4 SPECIFY THE APPROVED AND LISTED 2-HOUR |
| FIRE RATED WOOD FRAME ASSEMBLY THAT WILL BE USED. |
| |
| 15) THE ENERGY CALCULATIONS FORMS THAT WERE SUBMITTED |
| ARE FOR THE 2007 FBC AND THE PLANS ARE FOR THE 2004 |
| FBC. PLEASE REVISE. |
| |
| 16) THE R-VALUE LISTED FOR THE UNVENTED ATTIC IS R1.O. |
| THE PLANS SPECIFY R-19. PLEASE CORRECT. |
| |
| 17) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED |
| TO INSTALL THE CONCRETE ROOF TILE. R905.3 PLEASE CIRCLE |
| THE APPROPRIATE FASTENER AND CORRESPONDING ATTACHMENT |
| RESISTANCE ON THE NOA. PLEASE NOTE THAT THE OVERTURN |
| MOMENT FOR THE ROOF TILE VARIES WITH THICKNESS OF THE |
| ROOF SHEATHING FOR SOME ATTACHMENTS. |
| |
| 18) SUBMIT TWO COPIES OF AN NOA OR OTHER APPROVED |
| EVALUATION REPORT INCLUDING INSTALLATION INSTRUCTIONS |
| AS REQUIRED BY DCA RULE 9B-72 FOR THE OVERHEAD GARAGE |
| DOORS AND THE SLIDING GLASS DOORS. |
| |
| 19) THE PRODUCT APPROVAL NUMBERS THAT ARE LISTED IN THE |
| WINDOW SCHEDULE FOR THE SINGLE HUNG WINDOWS AND THE |
| SLIDING WINDOWS ARE REVERSED. PLEASE CORRECT. |
| |
| 20) THE DOOR SCHEDULE ON THE PLANS SPECIFIES LARGE |
| MISSILE IMPACT RATED DOORS AND THE PRODUCT APPROVAL FOR |
| THE FRONT DOOR IS FOR A NON-RATED DOOR. PLEASE CLARIFY. |
| IF NON-RATED DOOR IS TO BE USED, SUBMIT PRODUCT |
| APPROVALS FOR STORM PANELS. |
| |
| 21) ON SHEET S-1 DETAILS A AND B SPECIFY #4 DOWELS IN |
| THE FILLED CELLS AND THE COLUMN SCHEDULE SPECIFIES #5 |
| BARS. PLEASE CLARIFY. |
| |
| 22) THE BUILDINGS ARE REQUIRED TO HAVE APPROVED |
| ADDRESSES BEFORE THE PERMITS WILL BE ISSUED. CONTACT |
| JOHN NGUYEN AT 561-822-1239. |
| |
| 23) THE ROOF DESIGN DOES NOT APPEAR TO PROVIDE PROPER |
| SEPARATION AT THE GABLES AND HIP ROOFS THAT INTERSECT |
| THE PROPERTY LINES. ADDITIONAL DETAILS AND TRUSS |
| DRAWINGS ARE REQUIRED IN ORDER TO DETERMINE IF THE |
| SEPARATION REQUIREMENTS OF R317.2 HAVE BEEN COMPLIED |
| WITH. |
| |
| 24) THE GABLE ROOF OVERHANGS CAN NOT EXTEND BEYOND THE |
| PROPERTY LINES. R302.1 EXTERIOR WALLS.EXTERIOR WALLS |
| SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL HAVE NOT |
| LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING WITH |
| EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT EXTEND |
| TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN |
| ADJACENT PROJECTION OR WALL. |
| |
| 25) SHEET T-1 OF THE ARCHITECTURAL DRAWINGS SPECIFIES |
| THAT THE CODE USED FOR THE DESIGN IS THE 2004 FBC AND |
| ON S1 THE STRUCTURAL DRAWINGS SPECIFIES THE 2007 FBC AS |
| THE CODE USED FOR DESIGN. THE PLANS ARE REQUIRED TO BE |
| DESIGNED USING ONLY ONE EDITION OF THE BUILDING CODE. |
| THE CODES CAN NOT BE MIXED FOR THE DESIGN OF A |
| STRUCTURE. PLEASE CHOOSE ONE CODE AND USE IT FOR ALL OF |
| THE DESIGN. |
| |
| 26) THE BUILDING OFFICIAL WILL BE REQUIRED TO DETERMINE |
| IF THE NO BURN FIRE-RETARDANT CAN BE USED IN PLACE OF |
| THE 5/8" TYPE X DRYWALL AT THE SEPARATION WALLS. FBC |
| 104.11* CITY AMENDMENTS |
| |
| 27) SUBMIT PRODUCT APPROVALS, TESTING AND EVALUATION |
| REPORTS FOR THE 1/2" HUBER ADVANCED TECH ENGINEERED |
| ROOF SHEATHING. DCA RULE 9B-72 |
| |
| 28) THE VALUE OF THE PRODUCT IS LOW AND HAS BEEN |
| ADJUSTED. ADDITIONAL FEES OF $ 2877.30 ARE DUE. FBC |
| 108.3* CITY AMENDMENTS. |
| |
| 29) IF THE PROJECT IS INTENDED TO BE "MASTERED" SUCH |
| THAT ALL PERMIT DOCUMENTS DO NOT HAVE TO SUBMITTED WITH |
| THE PERMIT APPLICATIONS FOR EACH INDIVIDUALLY PERMITTED |
| TOWNHOUSE UNIT, PLEASE KNOW THAT ALL SUCH PERMITS MUST |
| BE APPLIED FOR PRIOR TO THE IMPLEMENTATION OF THE 2007 |
| FLORIDA BUILDING CODE ON MARCH 1, 2009. THE PROJECT |
| WILL NEED TO BE "RE-MASTERED" TO COMPLY WITH THE 2007 |
| FBC AT THAT TIME. |
| |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |