Plan Review Notes
Plan Review Notes For Permit 08120189
Permit Number 08120189
Review Stop P
Sequence Number 1
Notes
Date Text
2009-01-12 16:42:25DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1 (ADMIN)
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT T-1 PLUMBING NOTES:
 #2, 2-1/2" AND LESS 1/4" PER LINEAR FOOT SLOPE
 REQUIRED. TABLE 704.1.
 #5 FBC-2004 WITH 2007 AMENDMENTS IS THE CODE ADOPTED.
 THE SOUTH FLORIDA BUILDING CODE WAS FOR BROWARD AND
 DADE COUNTIES ONLY AND THE FLORIDA BUILDING CODE HAS
 BEEN IN EFFECT SINCE THE 2001 VERSION WHICH WENT INTO
 EFFECT ON MARCH 1, 2003.
 #8 AIR CHAMBERS ARE NOT APPROVED. PLEASE DELETE
 REFERENCE. SECTION 604.9.
  
 2. ALL SHEETS WITH THE BENEDICT GROUP ARCHITECTURE &
 PLANNING. THE PRINTED NAME OF THE PERSON SEALING THE
 PLANS IS REQUIRED IN THE TITLE BLOCK OF EACH SHEET. FAC
 61G1-16.004(6) & FS 481.2055.
  
 3. ALL SHEETS WITH THE BENEDICT GROUP ARCHITECTURE &
 PLANNING. THE SIGNATURE OF THE ARCHITECT SHALL APPEAR
 ON ALL ARCHITECTURAL DOCUMENTS TO BE FILED FOR PUBLIC
 RECORD. IT APPEARS THAT INITIALS WERE USED. IF THIS IS
 INDEED THE LEGAL SIGNATURE OF THE ARCHITECT OF RECORD,
 THEN A SIGNED, SEALED, NOTORIZED LETTER INDICATING THE
 LEGAL SIGNATURE SHALL BE SUBMITTED TO THIS OFFICE FOR
 OUR RECORD. FAC 61G1-16.003, 61G1-16.004(5) AND FS
 481,2055.
  
 4. SHTS M-1.0, M-1.2, M-1.3 & M-1.4 PLUMBING NOTES:
 #2, 2-1/2" AND LESS 1/4" PER LINEAR FOOT SLOPE
 REQUIRED. TABLE 704.1.
 #5 FBC-2004 WITH 2007 AMENDMENTS IS THE CODE ADOPTED.
 THE SOUTH FLORIDA BUILDING CODE WAS FOR BROWARD AND
 DADE COUNTIES ONLY AND THE FLORIDA BUILDING CODE HAS
 BEEN IN EFFECT SINCE THE 2001 VERSION WHICH WENT INTO
 EFFECT ON MARCH 1, 2003.
 #8 AIR CHAMBERS ARE NOT APPROVED. PLEASE DELETE
 REFERENCE. SECTION 604.9.
  
 5. SHTS M-1.0, M-1.2, M-1.3 & M-1.4 NOTE STATES VTR'S
 SHALL MERGE TO ONE VTR BEFORE IT TERMINATES OFF THE
 ROOF. EXCEPT LAUNDRY VENT. PLEASE SHOW THE PIPING ON
 THE ISOMETRIC SANITARY RISER DIAGRAM. SHOW ALL PIPE
 SIZES OF VENTS. SECTIONS 106.1.1 & TABLE 916.1.
  
 6. SHTS M-1.0, M-1.2, M-1.3 & M-1.4 EXPLAIN THE FLOOR
 DRAIN FOR THE WATER HEATER. SECTION 106.1.2. A TRAP
 PRIMER MAY BE REQUIRED PER SECTION 1002.4.
  
 7. SHTS M-1.0, M-1.2, M-1.3 & M-1.4 WATER HEATER
 DETAIL. THE P/T DISCHARGE PIPE SHALL HAVE NOT TRAPPED
 SECTIONS AND SHALL HAVE AN AIR GAP OR AIR GAP FITTING
 IN THE SAME ROOM PER SECTION 504.6.1. PLEASE INDICATE
 HOW THE P/T LINE WILL BE RUN TO THE OUTSIDE FROM THE
 INTERIOR UNITS. SECTION 106.1.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  