2009-01-02 11:37:40 | ** DENIED REVIEW ** |
| |
| ** IMPORTANT** |
| AS THERE IS SOME INFORMATION OR ITEMS NOT YET SUBMITTED |
| FOR CODE COMPLIANCE THERE MAY VERY WELL BE NEW COMMENTS |
| ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS |
| TIME. PLEASE ALSO BE WARE THAT SOME OF THE COMMENTS |
| BELOW WILL CASE REVISIONS TO PLANS WHICH SOMETIMES |
| CREATE NEW COMMENTS. |
| |
| 1) NOTE: PLEASE KNOW ONCE THE ADDRESS OF EACH FEE |
| SIMPLE UNIT IS DONE AND COMPLETED, EACH SET OF PLANS |
| FOR EACH PERMITTED TOWN HOUSE WILL BE REQUIRED TO BE |
| ADDRESSED INCLUDING THE ADDRESS ON THE TITLE BLOCKS. |
| THE ADDRESSES FOR EACH HAS YET TO BE CONFIRMED AND THIS |
| WILL BE DONE BY THE BUILDING AND ADDRESSING REVIEWER. |
| THE PERMIT APPLICATION AS SUBMITTED WAS FOR ONE 5 UNIT |
| BUILDING HOWEVER THIS PERMIT HAS AN APPLIED VALUE FOR |
| ONE UNIT ONLY. ONCE ALL FINAL APPLICATIONS AND |
| ADDRESSES HAVE BEEN CONFIRMED PLEASE BE SURE PLANS ARE |
| COORDINATED. |
| FAC61G1-16.004 |
| FBC 106.5 |
| |
| 2) NOTE: PLEASE SEE FAC 61G1-16.004, AS THE TITLE |
| BLOCKS FOR THE ARCHITECTURAL FIRM IS MISSING THE |
| REQUIRED PRINTED NAME AND PRINTED LICENSE NUMBER OF |
| SAID DESIGNER. THIS IS REQUIRED FOR ALL TRADES AND FOR |
| AL SHEETS WHETHER OR NOT COMMENT IS MADE BY OTHER |
| TRADES. |
| |
| 3) NOTE: PLEASE BE SURE PLANS CONTAIN THE FOLLOWING |
| CODES. SOME ARE ALREADY SHOWN HOWEVER THESE ARE |
| REQUIRED FOR THIS REVIEWER. |
| 2004 FBC W/2007 REVISIONS. |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| |
| *** PLEASE KEEP IN MIND ALL PERMIT APPLICATIONS FOR ALL |
| UNITS MUST BE APPLIED FOR BEFORE MARCH 1ST, 2009 |
| OTHERWISE ANY PERMIT APPLICATIONS AFTER THIS DATE WILL |
| ALL FOR UNDER THE NEW CODES COMING INTO AFFECT BY THE |
| STATE OF FLORIDA. PLEASE ALSO BE AWARE OF CHANGES IN |
| THE NEC/NFPA-70 WHICH WILL ALSO BE CHANGING COMING UP |
| IN MONTHS TO COME. |
| |
| 4) NOTE: PLEASE SEE 210.52D AS THE GFI SHOWN ON THE |
| FIRST LEVEL BATH ROOM SHALL BE PLACED IN THE MIDDLE |
| BETWEEN THE TWO SINKS OR A SECOND DEVICE WILL BE |
| REQUIRED TO BE ADDED. AN OCCUPANT MAY NOT CROSS OVER |
| ONE SINK TO PLUG IN ANY APPLIANCE. |
| |
| 5) NOTE: PLEASE SEE 422.13 UNDER THE 2005 NEC AS THE |
| WATER HEATER LOAD IS NOW CONSIDERED A CONTINUOUS LOAD |
| AND NEEDS TO BE SHOWN AT 125%. |
| THE PREVIOUS CODE REQUIRED THE SIZING FROM BRANCH |
| CIRCUIT AND WIRING TO BE AT 125%, HOWEVER THE NEW |
| CHANGE IS TO CARRY THE 125% LOAD FOR SIZING FEEDERS AND |
| SERVICE. |
| PLEASE ADJUST PLANS. |
| |
| 6) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 FOR |
| REQUIRED LOADS ON CIRCUITS FOR SMALL APPLIANCES, DINING |
| AND BREAKFAST ROOM. THE OTHER TWO LOCATIONS CAN NOT BE |
| CONFIRMED DUE TO NO CIRCUITING BEING SHOWN ON THE PLANS |
| AT THIS TIME. |
| PLEASE KNOW THAT THE ONE OR *MORE* CIRCUITS REQUIRE THE |
| 1.5KVA. THE LOADS SHOWN ON PANEL SCHEDULE FOR DINING |
| ROOM ARE WELL BELOW THE REQUIRED MINIMUM OF 1500VA. |
| |
| 7) NOTE: PLEASE SUBMIT AND INDICATE THE AIC RATING FOR |
| ALL SERVICE EQUIPMENT PER 110.9. |
| |
| 8) NOTE: PLEASE SEE 110.26 FOR MINIMUM CLEARANCE |
| REQUIREMENTS OF THE A/C DISCONNECT FOR THE CONDENSING |
| UNIT. AS SHOWN ON THE PLANS THIS DISCONNECT IS BEHIND |
| THE UNIT WHICH DOES NOT MEET MINIMUM CLEARANCES. |
| |
| 9) NOTE: PLEASE SEE 210.8A7 FOR REQUIRED GFI PROTECTION |
| OF ALL 15/20AMP 120V RECEPTACLES WITHIN 6FT OF A |
| LAUNDRY SINK. THIS WAS A CHANGE IN THE 2005 NEC AND IS |
| REQUIRED EVEN FOR DEDICATED CIRCUITS SUCH AS THE WASHER |
| CIRCUIT. |
| |
| 10) NOTE: RISER IS SHOWING AN EQUIPMENT GROUNDING |
| CONDUCTOR FROM THE METER TO THE MAIN BREAKER PANEL |
| WHICH IS NOT PERMITTED. THE CONDUCTOR IS ALSO SHOWN |
| AS#5. THERE NO SUCH CONDUCTOR SIZE BASED ON THE AWG |
| (AMERICAN WIRE GAUGE). |
| PLEASE SEE THE FOLLOWING COMMENT WITH RESPECT TO MAIN |
| SHOWN ON PLANS. THIS WILL AFFECT THIS COMMENT. |
| 250.6,250.24,250.110, ETC SIZE PER 250.122. |
| |
| 11) NOTE: PLEASE COORDINATE RISER AND PLANS. THE RISER |
| DOES NOT SHOW A MAIN DISCONNECT OUTSIDE YET THE PLANS |
| DO SHOW A MAIN NEXT TO THE METER. |
| PLEASE ALSO SEE THE PLANS DO NOT SHOW THE ELECTRICAL |
| PANEL LOCATION. 240.24,110.26 ETC |
| PLEASE COORDINATE AND PLEASE SEE 230.70,230.71 AS NO |
| MORE THAN 8FT OF UNPROTECTED CONDUCTORS ARE PERMITTED |
| INSIDE THE BUILDING. |
| FBC 106.1.1 FOR CLARITY OF PLANS AND COORDINATION. |
| |
| 12) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE |
| SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS |
| SMOKE DETECTORS. |
| BY THE DEFINITIONS AS STATED IN NFPA-72 AND THE FLORIDA |
| BUILDING CODE A SD/ SMOKE DETECTOR IS ONLY A DEVICE |
| WHICH WILL DETECT AND WILL NOT SOUND AN AUDIBLE ALARM. |
| THIS WOULD BE DONE BY HORN/SIREN TYPE DEVICES. |
| PLEASE SEE THE DEFINITIONS OF SA/SMOKE ALARMS; THESE |
| ARE DEVICES WHICH ARE 120V (AS SHOWN) AND WOULD DETECT |
| AND SOUND AN ALARM. |
| ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| RESIDENTIAL CODE/ FBC AND IN NFPA-72. IF THESE ARE |
| INDEED SMOKE DETECTORS, PLEASE SUBMIT COMPLETE PLANS |
| SHOWING THE REQUIRED FIRE ALARM PANEL AND HORN/SOUNDING |
| DEVICES. IF THESE ARE INDEED SMOKE ALARMS, PLEASE |
| ADJUST DESIGNATIONS ON PLANS AND SYMBOL LEGEND. |
| IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE*. |
| PLEASE SEE NFPA-72 11.5.1.1, 11.8.3, R313 |
| |
| ** PLEASE SEE 11.8.3 ABOVE IN NFPA-72 AS THE SMOKE |
| DEVICE IN THE MASTER BEDROOM IS REQUIRED TO BE LOCATED |
| WITHIN 12 INCHES OF THE HIGHEST POINT OF CEILINGS. WHEN |
| THERE ARE TRAY CEILINGS THIS MAY AFFECT THE LOCATION. |
| BASED ON THE ARCHITECTURAL SHEET WHICH INDICATES THE |
| CEILING DIFFERENCE OF ONLY 6INCHES THE LOCATION AS |
| SHOWN IS OK AS LONG AS THERE ARE NO HEADERS INSTALLED |
| AT OPENING. IF THE CEILING HEIGHT DOES CHANGE THIS MAY |
| AFFECT THE LOCATION. |
| |
| 13) NOTE: PLANS SHOW BOTH DISPOSAL AND DISHWASHER ON |
| SEPARATE RECEPTACLES WHICH IS OK HOWEVER PLEASE BE SURE |
| TO SEE 210.4B. PLEASE VERIFY IF BOTH WILL BE ON THE |
| SAME YOKE. IF SO THEN THIS WILL BE REQUIRED TO BE A |
| 2-POLE BREAKER. THIS IS ONLY NOTED AS NO CHANGES ARE |
| NEEDED AT THIS TIME. |
| NEC 300, 210.4B |
| FBC 106.1.1 FOR INFORMATION ONLY. |
| |
| 14) NOTE: PLEASE PROVIDE THE WORST CASE VOLTAGE DROP |
| FOR FEEDERS AND BRANCH CIRCUITS. |
| PLEASE KEEP IN MIND THIS NEEDS TO SHOW THE ENTIRE FEED |
| THRU FROM THE SOURCE TO THE END USE. THE CODE REQUIRES |
| A MAXIMUM ON THE ENTIRE RUN NOT FROM A PANEL TO THE END |
| DEVICE ON A CIRCUIT. THIS MAY AFFECT FEEDERS OR BRANCH |
| CIRCUIT CONDUCTORS. |
| PLEASE SEE FBC13-413.1ABC.1. |
| |
| 15 ) NOTE: PLEASE PLACE NOTES ON PLANS AS REQUIRED PER |
| 13-413.ABC.2, .2.1 AND .2.2. THE WORDING AS STATED IN |
| THE FBC IS ACCEPTABLE. THIS WAS CONFIRMED WITH |
| DEPARTMENT OF COMMUNITY AFFAIRS. |
| |
| 16) NOTE: PLEASE INCLUDE TYPE OF RECESSED LIGHTING |
| FIXTURES PER FBC 13-606.1.ABC.1.2.4 |
| RECESSED LIGHTING FIXTURES INSTALLED IN CEILINGS THAT |
| ABUT AN ATTIC SPACE SHALL MEET ONE OF THE FOLLOWING |
| REQUIREMENTS: |
| 1. TYPE IC RATED, MANUFACTURED WITH NO PENETRATIONS |
| BETWEEN THE INSIDE OF THE RECESSED FIXTURE AND CEILING |
| CAVITY AND SEALED OR GASKETED TO PREVENT AIR LEAKAGE |
| INTO THE UNCONDITIONED SPACE. |
| 2. TYPE IC OR NON-IC RATED, INSTALLED INSIDE A SEALED |
| BOX [MINIMUM OF ?-INCH-THICK (12.7 MM)] GYPSUM WALL |
| BOARD, PREFORMED POLYMERIC VAPOR BARRIER, OR OTHER AIR |
| TIGHT ASSEMBLY MANUFACTURED FOR THIS PURPOSE) AND |
| MAINTAINING REQUIRED CLEARANCES OF NOT LESS THAN |
| ?-INCH-THICK (12.7 MM) FROM COMBUSTIBLE MATERIAL AND |
| NOT LESS THAN 3 INCH (76 MM) FROM INSULATION MATERIAL. |
| 3. TYPE IC RATED, WITH NO MORE THAN 2.0 CFM (.00094 |
| M3/S) AIR MOVEMENT FROM THE CONDITIONED SPACE TO THE |
| CEILING CAVITY WHEN MEASURED IN ACCORDANCE WITH ASTM E |
| 283. THE FIXTURE SHALL BE TESTED AT 75 PA AND SHALL BE |
| LABELED. |
| |
| 17) NOTE: PLEASE SEE 410.8 FOR MINIMUM CLEARANCES |
| REQUIRED FOR CLOSET LIGHTING FIXTURES. BASED ON THE |
| PLANS THEY APPEAR TO INDICATE SHELVING RIGHT UP NEXT TO |
| THE FIXTURE. PLEASE ADJUST LOCATION OF FIXTURES. SEE |
| BEDRM #2 CLOSET FOR ONE EXAMPLE. |
| |
| 18) NOTE: PLEASE SEE 422.17 FOR WATER INSTALLATION |
| LOCATION WHICH IS NOT PERMITTED TO HAVE COMBUSTIBLES |
| STORED UP AGAINST UNIT. |
| |
| 19) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING |
| KITCHEN COUNTER SPACE SHALL BE GFI OR GFI PROTECTED. |
| SEE UNIT COUNTER WHICH IS MISSING GFI DESIGNATION. |
| |
| 20) NOTE: PLEASE SEE 210.52C1 FOR RECEPTACLES SPACING |
| WHICH REQUIRES A GFI RECEPTACLE WITHIN 2FT OF THE END |
| OF A COUNTER SPACE. THE COUNTER SPACE NEXT TO THE RANGE |
| TOWARDS THE SINK EXCEEDS THE 2FT. |
| |
| 21) NOTE: THE GARAGE DOOR OPENER SHOWS A JUNCTION BOX |
| FOR THE DOOR OPENER. IF THIS IS A HARDWIRED UNIT A |
| DISCONNECT IS REQUIRED PER 422.30, 31. |
| IF THIS IS GOING TO BE A PLUG IN TYPE UNIT USING THE |
| EXCEPTION FOR SOME EQUIPMENT WHICH IS PERMITTED TO BE |
| CORD AND PLUG CONNECTED AND USING THE PLUG AS THE |
| DISCONNECTING MEANS PLEASE SHOW THE RECEPTACLE. |
| |
| 22) NOTE: PLEASE SEE 210.52 FOR RECEPTACLE SPACING |
| ALONG WALLS. ONE EXAMPLE WOULD BE THE WALL IN THE |
| BREAKFAST AREA WHICH EXCEEDS 12FT BETWEEN COUNTER SPACE |
| AND DOOR WAY OF GARAGE. AS ONLY ONE IS SHOWN THIS WOULD |
| REQUIRE AN ADDITIONAL RECEPTACLE. |
| PLEASE ALSO SEE MASTER BEDROOM FOR TWO FT WALL |
| SPACE(S). |
| |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |