Plan Review Notes
Plan Review Notes For Permit 08120189
Permit Number 08120189
Review Stop E
Sequence Number 1
Notes
Date Text
2009-01-02 11:37:40** DENIED REVIEW **
  
 ** IMPORTANT**
 AS THERE IS SOME INFORMATION OR ITEMS NOT YET SUBMITTED
 FOR CODE COMPLIANCE THERE MAY VERY WELL BE NEW COMMENTS
 ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS
 TIME. PLEASE ALSO BE WARE THAT SOME OF THE COMMENTS
 BELOW WILL CASE REVISIONS TO PLANS WHICH SOMETIMES
 CREATE NEW COMMENTS.
  
 1) NOTE: PLEASE KNOW ONCE THE ADDRESS OF EACH FEE
 SIMPLE UNIT IS DONE AND COMPLETED, EACH SET OF PLANS
 FOR EACH PERMITTED TOWN HOUSE WILL BE REQUIRED TO BE
 ADDRESSED INCLUDING THE ADDRESS ON THE TITLE BLOCKS.
 THE ADDRESSES FOR EACH HAS YET TO BE CONFIRMED AND THIS
 WILL BE DONE BY THE BUILDING AND ADDRESSING REVIEWER.
 THE PERMIT APPLICATION AS SUBMITTED WAS FOR ONE 5 UNIT
 BUILDING HOWEVER THIS PERMIT HAS AN APPLIED VALUE FOR
 ONE UNIT ONLY. ONCE ALL FINAL APPLICATIONS AND
 ADDRESSES HAVE BEEN CONFIRMED PLEASE BE SURE PLANS ARE
 COORDINATED.
 FAC61G1-16.004
 FBC 106.5
  
 2) NOTE: PLEASE SEE FAC 61G1-16.004, AS THE TITLE
 BLOCKS FOR THE ARCHITECTURAL FIRM IS MISSING THE
 REQUIRED PRINTED NAME AND PRINTED LICENSE NUMBER OF
 SAID DESIGNER. THIS IS REQUIRED FOR ALL TRADES AND FOR
 AL SHEETS WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 3) NOTE: PLEASE BE SURE PLANS CONTAIN THE FOLLOWING
 CODES. SOME ARE ALREADY SHOWN HOWEVER THESE ARE
 REQUIRED FOR THIS REVIEWER.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
  
 *** PLEASE KEEP IN MIND ALL PERMIT APPLICATIONS FOR ALL
 UNITS MUST BE APPLIED FOR BEFORE MARCH 1ST, 2009
 OTHERWISE ANY PERMIT APPLICATIONS AFTER THIS DATE WILL
 ALL FOR UNDER THE NEW CODES COMING INTO AFFECT BY THE
 STATE OF FLORIDA. PLEASE ALSO BE AWARE OF CHANGES IN
 THE NEC/NFPA-70 WHICH WILL ALSO BE CHANGING COMING UP
 IN MONTHS TO COME.
  
 4) NOTE: PLEASE SEE 210.52D AS THE GFI SHOWN ON THE
 FIRST LEVEL BATH ROOM SHALL BE PLACED IN THE MIDDLE
 BETWEEN THE TWO SINKS OR A SECOND DEVICE WILL BE
 REQUIRED TO BE ADDED. AN OCCUPANT MAY NOT CROSS OVER
 ONE SINK TO PLUG IN ANY APPLIANCE.
  
 5) NOTE: PLEASE SEE 422.13 UNDER THE 2005 NEC AS THE
 WATER HEATER LOAD IS NOW CONSIDERED A CONTINUOUS LOAD
 AND NEEDS TO BE SHOWN AT 125%.
 THE PREVIOUS CODE REQUIRED THE SIZING FROM BRANCH
 CIRCUIT AND WIRING TO BE AT 125%, HOWEVER THE NEW
 CHANGE IS TO CARRY THE 125% LOAD FOR SIZING FEEDERS AND
 SERVICE.
 PLEASE ADJUST PLANS.
  
 6) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 FOR
 REQUIRED LOADS ON CIRCUITS FOR SMALL APPLIANCES, DINING
 AND BREAKFAST ROOM. THE OTHER TWO LOCATIONS CAN NOT BE
 CONFIRMED DUE TO NO CIRCUITING BEING SHOWN ON THE PLANS
 AT THIS TIME.
 PLEASE KNOW THAT THE ONE OR *MORE* CIRCUITS REQUIRE THE
 1.5KVA. THE LOADS SHOWN ON PANEL SCHEDULE FOR DINING
 ROOM ARE WELL BELOW THE REQUIRED MINIMUM OF 1500VA.
  
 7) NOTE: PLEASE SUBMIT AND INDICATE THE AIC RATING FOR
 ALL SERVICE EQUIPMENT PER 110.9.
  
 8) NOTE: PLEASE SEE 110.26 FOR MINIMUM CLEARANCE
 REQUIREMENTS OF THE A/C DISCONNECT FOR THE CONDENSING
 UNIT. AS SHOWN ON THE PLANS THIS DISCONNECT IS BEHIND
 THE UNIT WHICH DOES NOT MEET MINIMUM CLEARANCES.
  
 9) NOTE: PLEASE SEE 210.8A7 FOR REQUIRED GFI PROTECTION
 OF ALL 15/20AMP 120V RECEPTACLES WITHIN 6FT OF A
 LAUNDRY SINK. THIS WAS A CHANGE IN THE 2005 NEC AND IS
 REQUIRED EVEN FOR DEDICATED CIRCUITS SUCH AS THE WASHER
 CIRCUIT.
  
 10) NOTE: RISER IS SHOWING AN EQUIPMENT GROUNDING
 CONDUCTOR FROM THE METER TO THE MAIN BREAKER PANEL
 WHICH IS NOT PERMITTED. THE CONDUCTOR IS ALSO SHOWN
 AS#5. THERE NO SUCH CONDUCTOR SIZE BASED ON THE AWG
 (AMERICAN WIRE GAUGE).
 PLEASE SEE THE FOLLOWING COMMENT WITH RESPECT TO MAIN
 SHOWN ON PLANS. THIS WILL AFFECT THIS COMMENT.
 250.6,250.24,250.110, ETC SIZE PER 250.122.
  
 11) NOTE: PLEASE COORDINATE RISER AND PLANS. THE RISER
 DOES NOT SHOW A MAIN DISCONNECT OUTSIDE YET THE PLANS
 DO SHOW A MAIN NEXT TO THE METER.
 PLEASE ALSO SEE THE PLANS DO NOT SHOW THE ELECTRICAL
 PANEL LOCATION. 240.24,110.26 ETC
 PLEASE COORDINATE AND PLEASE SEE 230.70,230.71 AS NO
 MORE THAN 8FT OF UNPROTECTED CONDUCTORS ARE PERMITTED
 INSIDE THE BUILDING.
 FBC 106.1.1 FOR CLARITY OF PLANS AND COORDINATION.
  
 12) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE
 SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS
 SMOKE DETECTORS.
 BY THE DEFINITIONS AS STATED IN NFPA-72 AND THE FLORIDA
 BUILDING CODE A SD/ SMOKE DETECTOR IS ONLY A DEVICE
 WHICH WILL DETECT AND WILL NOT SOUND AN AUDIBLE ALARM.
 THIS WOULD BE DONE BY HORN/SIREN TYPE DEVICES.
 PLEASE SEE THE DEFINITIONS OF SA/SMOKE ALARMS; THESE
 ARE DEVICES WHICH ARE 120V (AS SHOWN) AND WOULD DETECT
 AND SOUND AN ALARM.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72. IF THESE ARE
 INDEED SMOKE DETECTORS, PLEASE SUBMIT COMPLETE PLANS
 SHOWING THE REQUIRED FIRE ALARM PANEL AND HORN/SOUNDING
 DEVICES. IF THESE ARE INDEED SMOKE ALARMS, PLEASE
 ADJUST DESIGNATIONS ON PLANS AND SYMBOL LEGEND.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3, R313
  
 ** PLEASE SEE 11.8.3 ABOVE IN NFPA-72 AS THE SMOKE
 DEVICE IN THE MASTER BEDROOM IS REQUIRED TO BE LOCATED
 WITHIN 12 INCHES OF THE HIGHEST POINT OF CEILINGS. WHEN
 THERE ARE TRAY CEILINGS THIS MAY AFFECT THE LOCATION.
 BASED ON THE ARCHITECTURAL SHEET WHICH INDICATES THE
 CEILING DIFFERENCE OF ONLY 6INCHES THE LOCATION AS
 SHOWN IS OK AS LONG AS THERE ARE NO HEADERS INSTALLED
 AT OPENING. IF THE CEILING HEIGHT DOES CHANGE THIS MAY
 AFFECT THE LOCATION.
  
 13) NOTE: PLANS SHOW BOTH DISPOSAL AND DISHWASHER ON
 SEPARATE RECEPTACLES WHICH IS OK HOWEVER PLEASE BE SURE
 TO SEE 210.4B. PLEASE VERIFY IF BOTH WILL BE ON THE
 SAME YOKE. IF SO THEN THIS WILL BE REQUIRED TO BE A
 2-POLE BREAKER. THIS IS ONLY NOTED AS NO CHANGES ARE
 NEEDED AT THIS TIME.
 NEC 300, 210.4B
 FBC 106.1.1 FOR INFORMATION ONLY.
  
 14) NOTE: PLEASE PROVIDE THE WORST CASE VOLTAGE DROP
 FOR FEEDERS AND BRANCH CIRCUITS.
 PLEASE KEEP IN MIND THIS NEEDS TO SHOW THE ENTIRE FEED
 THRU FROM THE SOURCE TO THE END USE. THE CODE REQUIRES
 A MAXIMUM ON THE ENTIRE RUN NOT FROM A PANEL TO THE END
 DEVICE ON A CIRCUIT. THIS MAY AFFECT FEEDERS OR BRANCH
 CIRCUIT CONDUCTORS.
 PLEASE SEE FBC13-413.1ABC.1.
  
 15 ) NOTE: PLEASE PLACE NOTES ON PLANS AS REQUIRED PER
 13-413.ABC.2, .2.1 AND .2.2. THE WORDING AS STATED IN
 THE FBC IS ACCEPTABLE. THIS WAS CONFIRMED WITH
 DEPARTMENT OF COMMUNITY AFFAIRS.
  
 16) NOTE: PLEASE INCLUDE TYPE OF RECESSED LIGHTING
 FIXTURES PER FBC 13-606.1.ABC.1.2.4
 RECESSED LIGHTING FIXTURES INSTALLED IN CEILINGS THAT
 ABUT AN ATTIC SPACE SHALL MEET ONE OF THE FOLLOWING
 REQUIREMENTS:
 1. TYPE IC RATED, MANUFACTURED WITH NO PENETRATIONS
 BETWEEN THE INSIDE OF THE RECESSED FIXTURE AND CEILING
 CAVITY AND SEALED OR GASKETED TO PREVENT AIR LEAKAGE
 INTO THE UNCONDITIONED SPACE.
 2. TYPE IC OR NON-IC RATED, INSTALLED INSIDE A SEALED
 BOX [MINIMUM OF ?-INCH-THICK (12.7 MM)] GYPSUM WALL
 BOARD, PREFORMED POLYMERIC VAPOR BARRIER, OR OTHER AIR
 TIGHT ASSEMBLY MANUFACTURED FOR THIS PURPOSE) AND
 MAINTAINING REQUIRED CLEARANCES OF NOT LESS THAN
 ?-INCH-THICK (12.7 MM) FROM COMBUSTIBLE MATERIAL AND
 NOT LESS THAN 3 INCH (76 MM) FROM INSULATION MATERIAL.
 3. TYPE IC RATED, WITH NO MORE THAN 2.0 CFM (.00094
 M3/S) AIR MOVEMENT FROM THE CONDITIONED SPACE TO THE
 CEILING CAVITY WHEN MEASURED IN ACCORDANCE WITH ASTM E
 283. THE FIXTURE SHALL BE TESTED AT 75 PA AND SHALL BE
 LABELED.
  
 17) NOTE: PLEASE SEE 410.8 FOR MINIMUM CLEARANCES
 REQUIRED FOR CLOSET LIGHTING FIXTURES. BASED ON THE
 PLANS THEY APPEAR TO INDICATE SHELVING RIGHT UP NEXT TO
 THE FIXTURE. PLEASE ADJUST LOCATION OF FIXTURES. SEE
 BEDRM #2 CLOSET FOR ONE EXAMPLE.
  
 18) NOTE: PLEASE SEE 422.17 FOR WATER INSTALLATION
 LOCATION WHICH IS NOT PERMITTED TO HAVE COMBUSTIBLES
 STORED UP AGAINST UNIT.
  
 19) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING
 KITCHEN COUNTER SPACE SHALL BE GFI OR GFI PROTECTED.
 SEE UNIT COUNTER WHICH IS MISSING GFI DESIGNATION.
  
 20) NOTE: PLEASE SEE 210.52C1 FOR RECEPTACLES SPACING
 WHICH REQUIRES A GFI RECEPTACLE WITHIN 2FT OF THE END
 OF A COUNTER SPACE. THE COUNTER SPACE NEXT TO THE RANGE
 TOWARDS THE SINK EXCEEDS THE 2FT.
  
 21) NOTE: THE GARAGE DOOR OPENER SHOWS A JUNCTION BOX
 FOR THE DOOR OPENER. IF THIS IS A HARDWIRED UNIT A
 DISCONNECT IS REQUIRED PER 422.30, 31.
 IF THIS IS GOING TO BE A PLUG IN TYPE UNIT USING THE
 EXCEPTION FOR SOME EQUIPMENT WHICH IS PERMITTED TO BE
 CORD AND PLUG CONNECTED AND USING THE PLUG AS THE
 DISCONNECTING MEANS PLEASE SHOW THE RECEPTACLE.
  
 22) NOTE: PLEASE SEE 210.52 FOR RECEPTACLE SPACING
 ALONG WALLS. ONE EXAMPLE WOULD BE THE WALL IN THE
 BREAKFAST AREA WHICH EXCEEDS 12FT BETWEEN COUNTER SPACE
 AND DOOR WAY OF GARAGE. AS ONLY ONE IS SHOWN THIS WOULD
 REQUIRE AN ADDITIONAL RECEPTACLE.
 PLEASE ALSO SEE MASTER BEDROOM FOR TWO FT WALL
 SPACE(S).
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  
  