Plan Review Notes
Plan Review Notes For Permit 08120178
Permit Number 08120178
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-12-16 15:36:37***DENIED***
  
 FIRE ALARM DRAWING APPEARS TO BE CODE COMPLIANT. PLEASE
 SEE THE FOLLOWING COMMENTS:
  
 1) EQUIPMENT SUBMITTALS FOR A SINGLE DOOR ACCESS SYSTEM
 HAVE BEEN PROVIDED WITH THIS PERMIT APPLICATION. IF
 ACCESS CONTROL EQUIPMENT IS INCLUDED IN THE SCOPE OF
 THIS WORK, ILLUSTRATE SPECIFIC EQUIPMENT ON THE DRAWING
 AND LEGEND.
  
 2) ACCESS-CONTROLLED EGRESS DOORS SHAL COMPLY WITH THE
 REQUIREMENTS OF NFPA 101, SEC. 7.2.1.6.2.
  
 3) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756