2009-02-10 14:59:28RESIDENTIAL (R3) REPAIRS, BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- FLOOR PLANS SPECIFY EXISTING 33"X40" SINGLE HUNG
 WINDOWS TO REMAIN AS IS. CONTRACTOR STATES THAT WINDOWS
 ARE GOING TO BE REPLACED. REVISE PLANS AS REQUIRED.
 ***NOTE: IF WINDOWS ARE NOT TO BE REPLACED, THEN WHY
 ENGINEER IS APPROVING PRODUCT APPROVAL FOR WINDOWS AND
 SHUTTERS?.
  
 2- REVISE WIND INFORMATION ON SHEET A1:
 A) DESIGN PRESSURES FOR DOORS AND WINDOWS ARE MISSING.
 THERE IS NOT SHEET A-2.
  
 B) PROVIDE ACTUAL ROOF CLADDING CALCULATIONS. SPECIFY
 TRIBUTARY AREA AND REVISE DIMENSION FOR ROOF ZONE 2 AND
 3. SEE FOOTNOTE "A" ON FIGURE R301.2(8) OF 2004 FLORIDA
 RESIDENTIAL CODE FOR MINIMUM REQUIRED DIMENSIONS.
  
 ***NOTE: CLARIFY WHY PROVIDING ROOF CLADDING PRESSURES
 IF NOT WORK IS TO BE DONE ON THE ROOF.
  
 3- PRODUCT APPROVAL FOR SHUTTERS FL722 AND NOA
 06-0110.04 SUBMITTED DON'T CORRESPOND TO EACH OTHER. IF
 USING FL722, THEN NEED TO PROVIDE COMPLETE SET OF
 DRAWINGS THAT WERE APPROVED FOR THIS PRODUCT APPROVAL.
 GO TO WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRECT SET
 OF DRAWINGS.
 IF USING THE NOA 06-0110.04, THEN ENGINEER NEEDS TO
 REVIEW AND APPROVE THIS PRODUCT APPROVAL ACCORDINGLY.
  
 4- PROVIDE COMPLETE INFORMATION ON INSTALLATION
 SCHEDULE FOR STORM SHUTTERS.
  
 5- ENERGY CALCULATIONS NEED TO BE SIGNED AND DATED BY
 THE OWNER/AGENT.
  