2009-02-10 14:59:28 | RESIDENTIAL (R3) REPAIRS, BUILDING REVIEW SECOND |
| CHECKLIST. |
| REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| REVISIONS. |
| |
| 1- FLOOR PLANS SPECIFY EXISTING 33"X40" SINGLE HUNG |
| WINDOWS TO REMAIN AS IS. CONTRACTOR STATES THAT WINDOWS |
| ARE GOING TO BE REPLACED. REVISE PLANS AS REQUIRED. |
| ***NOTE: IF WINDOWS ARE NOT TO BE REPLACED, THEN WHY |
| ENGINEER IS APPROVING PRODUCT APPROVAL FOR WINDOWS AND |
| SHUTTERS?. |
| |
| 2- REVISE WIND INFORMATION ON SHEET A1: |
| A) DESIGN PRESSURES FOR DOORS AND WINDOWS ARE MISSING. |
| THERE IS NOT SHEET A-2. |
| |
| B) PROVIDE ACTUAL ROOF CLADDING CALCULATIONS. SPECIFY |
| TRIBUTARY AREA AND REVISE DIMENSION FOR ROOF ZONE 2 AND |
| 3. SEE FOOTNOTE "A" ON FIGURE R301.2(8) OF 2004 FLORIDA |
| RESIDENTIAL CODE FOR MINIMUM REQUIRED DIMENSIONS. |
| |
| ***NOTE: CLARIFY WHY PROVIDING ROOF CLADDING PRESSURES |
| IF NOT WORK IS TO BE DONE ON THE ROOF. |
| |
| 3- PRODUCT APPROVAL FOR SHUTTERS FL722 AND NOA |
| 06-0110.04 SUBMITTED DON'T CORRESPOND TO EACH OTHER. IF |
| USING FL722, THEN NEED TO PROVIDE COMPLETE SET OF |
| DRAWINGS THAT WERE APPROVED FOR THIS PRODUCT APPROVAL. |
| GO TO WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRECT SET |
| OF DRAWINGS. |
| IF USING THE NOA 06-0110.04, THEN ENGINEER NEEDS TO |
| REVIEW AND APPROVE THIS PRODUCT APPROVAL ACCORDINGLY. |
| |
| 4- PROVIDE COMPLETE INFORMATION ON INSTALLATION |
| SCHEDULE FOR STORM SHUTTERS. |
| |
| 5- ENERGY CALCULATIONS NEED TO BE SIGNED AND DATED BY |
| THE OWNER/AGENT. |
| |