Plan Review Notes
Plan Review Notes For Permit 08120128
Permit Number 08120128
Review Stop P
Sequence Number 1
Notes
Date Text
2008-12-16 16:52:33DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER1
 FBC-2004 EXISTING BUILDING
  
 1. PLEASE INDICATE WHICH UNIT WILL BE PERMITTED FOR
 WORK ON THE APPLICATION . PLANS SHOW APT A & APT B.
 SECTION 106.1.1.
  
 2. SHT A1 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN, NOR DOES IT MEET CODE REQUIREMENTS. THE
 FIXTURE DOWNSTREAM OF THE W/C IS INDICATED AS A SINK ON
 THE RISER DIAGRAM, BUT A LAV ON THE FLOOR PLAN. THE
 FIXTURE IS NOT VENTED AS SHOWN, NOR IS THE TUB. IF THE
 SANITARY PIPING IS TO BE REPLACED, THEN IT SHALL BE
 CODE COMPLIANT. SECTIONS 106.1.1 & 909.1. (SEE RED LINE
 EXAMPLE ON ONE SET OF PLANS). INDICATE PIPE SIZES.
  
 3. PLEASE SUBMIT A CODE SUMMARY SHOWING CODE IN EFFECT,
 (FBC-2004 W/20005, 2006 & 2007 AMENDMENTS), AND
 INDICATE THE LEVEL OF ALTERATION PER CHAPTER 3 OF THE
 EXISTING BUILD CODE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  