Plan Review Notes For Permit 08120123
Permit Number 08120123
Review Stop E
Sequence Number 2
Notes
Date Text
2009-02-03 10:59:06 
 PROVISO
  
  
 NOTE TO SHEET EP3-03 AND EP3-04 CHANGES PER 225. PER
 225.30, 31 AND 32 THE DISCONNECTING MEANS REQUIRED "
 SHALL CONSIST OF NOT MORE THAN SIX SWITCHES OR SIX
 CIRCUIT BREAKERS MOUNTED IN A SINGLE ENCLOSURE, IN A
 GROUP OF SEPARATE ENCLOSURES, OR IN OR ON A
 SWITCHBOARD. THERE SHALL BE NO MORE THAN SIX
 DISCONNECTS PER SUPPLY GROUPED IN ANY ONE LOCATION".THE
 CIRCUITS FOR DOCK #3 MUST MEET THESE CODES. IF THE
 PANEL IS RECIRCUITED A REVISION WILL BE REQUIRED.
  
 THIS PERMIT IS BEING ISSUED TO EXPEDITE THIS START OF
 THIS PROJECT. THE COMMENTS FROM THE PREVIOUS REVIEW
 HAVE NOT BEEN ADDRESSED SUFFICIENTLY TO SHOW CODE
 COMPLIANCE. PLEASE RESUBMIT A REVISION SHOWING
 CORRECTIONS PRIOR TO CALLING ROUGH ELECTRICAL
 INSPECTION. THE REVIEWED PLAN MUST BE ON THE JOB SITE
 AT TIME OF INSPECTION. ALLOW AT LEAST ONE WEEK (PER
 TRADE) FOR PLAN REVIEW.
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS INCLUDING
 LISTING INFORMATION, FOR THE FIXTURES AND FIRE
 EXTINGUISHER STORAGE EQUIPMENT THAT ARE INTENDED TO BE
 INSTALLED UNDER THIS PERMIT.***THE LISTING WERE NOT
 GIVEN.
 ..
 3} INCLUDE THE ADDRESS OF THE PROJECT ON THE PLANS PER
 106.1.1 FBC AS AMENDED.*** ALL SHEETS AND INCLUDE THE
 DOCK NUMBER AS THE MAIN ADDRESS IS THE SAME FOR THE
 ENTIRE PROJECT WHICH IS 100 S. FLAGLER DR.
  
 5} THE "FLEX CABLE" SHOWN ON CUT #2, SHEET EP3-02 MUST
 COMPLY WITH 555.13(A)(2) NEC, 3.10.5 NFPA-303, WITH A
 UL LISTING OF PDYQ OR QPMU OR COMPARABLE. INDICATE THE
 TYPE INTENDED FOR USE ON THE PLAN.*** THE INFORMATION
 WAS IN THE RESPONSE SHEETS BUT NOT ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  