2008-12-11 16:27:08CITY COMMONS DOCK # 3
 100 SOUTH FLAGLER DRIVE
 08120123
  
 1. PRESSURE TESTS ARE REQUIRED OF THE DOCK FIRE LINE
 AND FIRE DEPARTMENT CONNECTION FOR DOCK # 3.
  
 2. CHAIN AND LOCK REQUIRED ON FIRE LINE BACKFLOW
 DEVICE.
  
 3. DOCK ADDRESS AND IDENTITY SHALL BE PROVIDED.
  
 4. PORTABLE FIRE EXTINGUISHERS SHALL BE CURRENTLY
 SERVICE TAGGED WHEN PLACED INSIDE THE FIRE EXTINGUISHER
 CABINETS.
  
 5. WATER WILL BE FLOWED FROM EACH HOSE VALVES WHEN THE
 DOCK IS COMPLETED.
  
 6. THE NEW FIRE HYDRANT AFTER INSTALLATION SHALL BE
 TESTED TO ENSURE THAT ALL VALVES ARE OPENED.
  
 7. DOCK SHALL COMPLY WITH NFPA 303.
  
 8. DOCK IS SUBJECT TO FIELD INSPECTION AND APPROVAL.
  
 9. KNOX-BOX LOCKING CAPS ARE TO BE PROVIDED FOR THE
 FIRE DEPARTMENT CONNECTION (FDC).
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  