Plan Review Notes For Permit 08120123 |
Permit Number |
08120123 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-12-11 16:27:08 | CITY COMMONS DOCK # 3 | | 100 SOUTH FLAGLER DRIVE | | 08120123 | | | | 1. PRESSURE TESTS ARE REQUIRED OF THE DOCK FIRE LINE | | AND FIRE DEPARTMENT CONNECTION FOR DOCK # 3. | | | | 2. CHAIN AND LOCK REQUIRED ON FIRE LINE BACKFLOW | | DEVICE. | | | | 3. DOCK ADDRESS AND IDENTITY SHALL BE PROVIDED. | | | | 4. PORTABLE FIRE EXTINGUISHERS SHALL BE CURRENTLY | | SERVICE TAGGED WHEN PLACED INSIDE THE FIRE EXTINGUISHER | | CABINETS. | | | | 5. WATER WILL BE FLOWED FROM EACH HOSE VALVES WHEN THE | | DOCK IS COMPLETED. | | | | 6. THE NEW FIRE HYDRANT AFTER INSTALLATION SHALL BE | | TESTED TO ENSURE THAT ALL VALVES ARE OPENED. | | | | 7. DOCK SHALL COMPLY WITH NFPA 303. | | | | 8. DOCK IS SUBJECT TO FIELD INSPECTION AND APPROVAL. | | | | 9. KNOX-BOX LOCKING CAPS ARE TO BE PROVIDED FOR THE | | FIRE DEPARTMENT CONNECTION (FDC). | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | |
|