Plan Review Notes For Permit 08120123
Permit Number 08120123
Review Stop E
Sequence Number 1
Notes
Date Text
2008-12-10 10:07:51 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, NFPA-303 2000, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS INCLUDING
 LISTING INFORMATION, FOR THE FIXTURES AND FIRE
 EXTINGUISHER STORAGE EQUIPMENT THAT ARE INTENDED TO BE
 INSTALLED UNDER THIS PERMIT.
  
 2} INDICATE THE TYPE OF JUNCTION BOXES SHOWN ON THE
 "TYPICAL LIGHT POLE INSTALLATION" CUT, SHEET EP3-02,
 AND A CLEARER CUT OF THE INSTALLATION METHOD. MUST
 COMPLY WITH 3.10.5.2, NFPA-303 (2000 ED)..
  
 3} INCLUDE THE ADDRESS OF THE PROJECT ON THE PLANS PER
 106.1.1 FBC AS AMENDED.
  
 4} SEE NFPA STANDARDS ON SHEET G-2. THE REFERENCE TO
 NFPA-303, SHOULD REFERENCE THE 2000 EDITION INSTEAD OF
 2006, THAT IS THE REFERENCE IN ARTICLE 555 OF THE 2005
 NEC, CURRENTLY ADOPTED.
  
 5} THE "FLEX CABLE" SHOWN ON CUT #2, SHEET EP3-02 MUST
 COMPLY WITH 555.13(A)(2) NEC, 3.10.5 NFPA-303, WITH A
 UL LISTING OF PDYQ OR QPMU OR COMPARABLE. INDICATE THE
 TYPE INTENDED FOR USE ON THE PLAN.
  
 6} REGARDING THE "STAINLESS STEEL SUPPORT BRACKET",
 SAME SHEET AND CUT IN COMMENT #5, SEE
 555-13(B)(4)(A)(3) "CABLES SHALL BE SECURELY FASTENED
 BY NONMETALLIC CLIPS TO STRUCTURAL MEMBERS OTHER THAN
 THE DECK PLANKING.".
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  