2008-12-10 10:07:51 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| NEC, NFPA-72 2002, NFPA-101 2003, NFPA-303 2000, 2004 |
| FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH |
| THE FOLLOWING: |
| |
| 1} PROVIDE MANUFACTURERS SPECIFICATIONS INCLUDING |
| LISTING INFORMATION, FOR THE FIXTURES AND FIRE |
| EXTINGUISHER STORAGE EQUIPMENT THAT ARE INTENDED TO BE |
| INSTALLED UNDER THIS PERMIT. |
| |
| 2} INDICATE THE TYPE OF JUNCTION BOXES SHOWN ON THE |
| "TYPICAL LIGHT POLE INSTALLATION" CUT, SHEET EP3-02, |
| AND A CLEARER CUT OF THE INSTALLATION METHOD. MUST |
| COMPLY WITH 3.10.5.2, NFPA-303 (2000 ED).. |
| |
| 3} INCLUDE THE ADDRESS OF THE PROJECT ON THE PLANS PER |
| 106.1.1 FBC AS AMENDED. |
| |
| 4} SEE NFPA STANDARDS ON SHEET G-2. THE REFERENCE TO |
| NFPA-303, SHOULD REFERENCE THE 2000 EDITION INSTEAD OF |
| 2006, THAT IS THE REFERENCE IN ARTICLE 555 OF THE 2005 |
| NEC, CURRENTLY ADOPTED. |
| |
| 5} THE "FLEX CABLE" SHOWN ON CUT #2, SHEET EP3-02 MUST |
| COMPLY WITH 555.13(A)(2) NEC, 3.10.5 NFPA-303, WITH A |
| UL LISTING OF PDYQ OR QPMU OR COMPARABLE. INDICATE THE |
| TYPE INTENDED FOR USE ON THE PLAN. |
| |
| 6} REGARDING THE "STAINLESS STEEL SUPPORT BRACKET", |
| SAME SHEET AND CUT IN COMMENT #5, SEE |
| 555-13(B)(4)(A)(3) "CABLES SHALL BE SECURELY FASTENED |
| BY NONMETALLIC CLIPS TO STRUCTURAL MEMBERS OTHER THAN |
| THE DECK PLANKING.". |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |