| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} 250.52(A)(3) CONCRETE-ENCASED ELECTRODE AN ELECTRODE |
| ENCASED BY AT LEAST 50 MM (2 IN.) OF CONCRETE, LOCATED |
| WITHIN AND NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR |
| FOOTING THAT IS IN DIRECT CONTACT WITH THE EARTH, |
| CONSISTING OF AT LEAST 6.0 M (20 FT) OF ONE OR MORE |
| BARE OR ZINC GALVANIZED OR OTHER ELECTRICALLY |
| CONDUCTIVE COATED STEEL REINFORCING BARS OR RODS OF NOT |
| LESS THAN 13 MM ( 1/ 2 IN.) IN DIAMETER, OR CONSISTING |
| OF AT LEAST 6.0 M (20 FT) OF BARE COPPER CONDUCTOR NOT |
| SMALLER THAN 4 AWG. REINFORCING BARS SHALL BE PERMITTED |
| TO BE BONDED TOGETHER BY THE USUAL STEEL TIE WIRES OR |
| OTHER EFFECTIVE MEANS. ADD TO THE RISER DIAGRAM. |
| |
| 2} 408.36(D) SUPPLIED THROUGH A TRANSFORMER- WHERE A |
| PANELBOARD IS SUPPLIED THROUGH A TRANSFORMER, THE |
| OVERCURRENT PROTECTION REQUIRED BY 408.36(A), (B), AND |
| (C) SHALL BE LOCATED ON THE SECONDARY SIDE OF THE |
| TRANSFORMER. PANEL "B" MUST PROVIDE SECONDARY |
| PROTECTION FOR THE 45KVA TRANSFORMER BY INSTALLING A |
| MAIN, OR ADDING A DISCONNECT WITH OCP PER 450.3(B). |
| |
| 3} PER THE FBC THE USE IS "A3" ASSEMBLY, ART GALLERY, |
| THEREFORE 1 WATT PER SQUARE FOOT SHOULD BE USED FOR THE |
| LIGHTING LOAD CALCULATION FOR ASSEMBLY HALLS 220.12. |
| |
| 4} PER FLORIDA STATUTE 471.003 AN ENGINEER MUST DESIGN |
| THIS SERVICE. THE CONTRACTOR OF RECORD MAY BE THE |
| DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES |
| ARE APPLICABLE. IN THIS CASE ENGINEERING IS REQUIRED |
| BECAUSE THE SERVICE VOLTAGE IS OVER 240 VOLTS AND |
| $50,000. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |