Plan Review Notes
Plan Review Notes For Permit 08120102
Permit Number 08120102
Review Stop B
Sequence Number 1
Notes
Date Text
2008-12-05 09:17:302004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) ON SHEET A.1 THE FLOOD ZONE IS INCORRECTLY SPECIFIED
 AS "C". THE CORRECT ONE IS "A5". FBC 106.1.1* CITY
 AMENDMENTS AND SEC. 94-541 CITY OF WPB MUNICIPAL CODE.
  
 2) ON A.1 THE LEVEL OF ALTERATION IS SPECIFIED AS LEVEL
 1 AND IT IS ACTUALLY LEVEL 2. FBC EXISTING BUILDING
 CHAPTER 3 SECTION 304.
  
 3) ON A.1 THE ADDRESS OF THE PROJECT IN THE TITLE BLOCK
 IS INCORRECTLY SPECIFIED AS 313 GREGORY PLACE. PLEASE
 CORRECT. SEE FAC 61G-16.004 AND FBC 106.1.1* CITY
 AMENDMENTS.
  
 4) THE S.1 SHEETS THAT WERE SUBMITTED DO NOT MATCH.
 THEY CONTAIN DIFFERENT INFORMATION. BOTH SETS OF PLANS
 ARE REQUIRED TO CONTAIN IDENTICAL INFORMATION. ONE OF
 THE SHEETS SPECIFIES A PROPOSED BARN IN WELLINGTON FOR
 THE PROJECT IDENTIFICATION IN THE TITLE BLOCK. PLEASE
 CORRECT. SEE FAC 61G-16.004 AND FBC 106.1.1* CITY
 AMENDMENTS.
  
 5) PROVIDE A STRUCTURAL DETAIL INDICATING HOW THE
 EXTERIOR BATHROOM WINDOWS WILL BE ENCLOSED. FBC R601.2
  
 6) ON SHEET A1 THE SHOWER ELEVATIONS ARE LABELED DEMO
 PLAN. PLEASE CLARIFY.
  