2008-12-24 12:35:07 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| REVISIONS. |
| |
| 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD. |
| (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING |
| BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| DUE. |
| |
| 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| **NOTE: THIS MAY BE RECORDED AND SUBMITTED AT TIME OF |
| PERMIT PICK UP. |
| |
| 3- CLEARLY SPECIFY THE BREAKDOWN OF NEW AREAS IN |
| ARCHITECTURAL PLANS (EG: GARAGE, PORCH AND NEW |
| CONDITIONED SPACES) TO VERIFY RADON FEES AND PROPER |
| VALUATION. SEC. 106.8 OF CITY AMENDMENTS TO FBC 2004. |
| |
| 4- SPECIFY ATTIC ACCESS LOCATION AND SIZE AS REQUIRED |
| BY SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| 5- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) GARAGE DOOR. SEE PLANS. |
| B) ROOF SHINGLES. |
| C) OPERABLE ALUMINUM SHUTTERS. AND PROVIDE COMPLETE |
| INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE. ALSO, MARK |
| ON SHUTTER DRAWINGS SPECIFIC MOUNTING CONDITIONS AND |
| ANCHOR TYPE AND SPACING TO BE USED. |
| D) HARDIE BOARD SUBMITTED HAS A NOA AND A LEGACY |
| REPORT. SPECIFY WHICH ONE IS GOING TO BE USED TO VERIFY |
| INSTALLATION COMPLIANCE. |
| E) HALF ROUND VENT SHOWN ON GABLE END. UNLESS SUCH VENT |
| IS DECORATIVE ONLY. |
| |
| 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY |
| AMENDMENTS TO FBC 2004. |
| |
| 7- PROVIDE 2 COPIES OF SOIL TEST REPORT WITH ORIGINAL |
| SEAL AND SIGNATURE. ONLY ONE WAS SUBMITTED. |
| |
| 8- REVISE ENERGY CALCULATIONS: |
| A) NEED TO USE REVISED 2004 FORM 600C-04R. |
| B) MISSING FLOOR TYPE ABOVE GARAGE AND FLOOR TYPE ABOVE |
| LAUNDRY AREA. SEE PLANS. |
| C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| D) COMPLETE BUILDER INFORMATION ON TOP OF FORM. |
| |
| 9- PROVIDE COMPLETE STAIRS AND RAILING DETAILS TO |
| VERIFY COMPLIANCE WITH SECTIONS R311.5 AND SEC. R312 OF |
| 2004 FLORIDA RESIDENTIAL CODE. |
| |
| 10- SHEET S-1: |
| A) SPECIFY ALL DEAD LOADS AND ALL LIVE LOADS REQUIRED |
| BY TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL CODE. |
| (INCLUDING ATTIC LIVE LOADS). |
| B) SPECIFY THE OPENINGS DESIGN PRESSURES. DESIGN |
| PRESSURES SHOWN ON SHEET A-2 DON'T CORRESPOND TO |
| EXPOSURE "C". REVISE AND COORDINATE WITH INFORMATION ON |
| SHEET A-2. |
| C) CONNECTOR SCHEDULE: UPLIFT ACTUAL LOADS ON CONNECTOR |
| "E" EXCEED THE MAXIMUM ALLOWED. REVISE AS REQUIRED. |
| ALSO COORDINATE LOADS ON CONNECTOR "B" WITH THOSE LOADS |
| SHOWN ON FRAMING PLANS. |
| D) REVISE NAILING PATTERN SCHEDULE. ROOF ZONE 3 |
| REQUIRES 4"O.C. NAILS AT EDGES AND INTERMEDIATE. SEE |
| SEC. R803.2.3.1. |
| E) REVISE ROOF ZONE SHOWN ON GABLE END SKETCH. SEE |
| FIGURE R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE. |
| F) REVISE SPACING FOR SUPPORTS OF W.W.F ON CONCRETE |
| SLAB. 3'-0" SPACING. SEE SEC. R506.2.4 EXCEPTION #2. |
| NOTE: REVISE THESE SPECS ON ALL BUILDING SECTIONS ALSO. |
| G) REVISE SECTION SPECIFIED FOR THE BUILDING DESIGN. |
| SEC. 1609 APPLIES TO OTHER BUILDINGS. 1 AND 2 FAMILY |
| RESIDENCES ARE TO BE DESIGNED PER SEC. R301 OF 2004 |
| FLORIDA RESIDENTIAL CODE. REVISE AS REQUIRED. |
| |
| 11- SHEET A-2: |
| A) PROVIDE SPECIFICATIONS FOR GARAGE SWING DOOR LEADING |
| TO THE LAUNDRY AREA TO SHOW COMPLIANCE WITH FIRE RATING |
| OF SEC. R309.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| B) REVISE DESIGN PRESSURES AND EXPOSURE SHOWN ON DOORS |
| AND WINDOWS. SEE ITEM 10 B ABOVE AND COORDINATE |
| INFORMATION. |
| C) REVISE GENERAL NOTES TO INCLUDE 2007 REVISIONS. |
| |
| 12- SHEET A-3: CLARIFY IF WINDOWS ARE WOOD DOUBLE HUNG |
| OR ALUMINUM SINGLE HUNG. SEE WINDOW SCHEDULE AND |
| PRODUCT APPROVAL SUBMITTED AND REVISE AS REQUIRED. |
| |
| 13- SHEETS A-5, A-6 AND A-7: SPECIFY FIREBLOCKING |
| MATERIAL AND LOCATION AS REQUIRED TO COMPLY WITH SEC. |
| R602.1.2 OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| 14- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806 |
| OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |