Plan Review Notes For Permit 08120071 |
Permit Number |
08120071 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2009-08-19 17:58:10 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | *** 1- NEW GYM AREA CAN NOT BE USED FOR SLEEPING. SEC. | | R309.1 OF 2004 FLORIDA RESIDENTIAL CODE. | | *** 2- FLAT ROOF PRODUCT APPROVAL NOA 07-0730.03 | | SUBMITTED: | | A) MARK WHICH APPROVED ASSEMBLY AND BASE SHEET FASTENER | | OPTION IS GOING TO BE INSTALLED. | | B) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | LIMITATION #7. | | *** 3- SOIL TEST REPORT SUBMITTED: | | A) ENGINEER NEEDS TO PROVIDE HIS SEAL AND LICENSE | | NUMBER. | | B) PROVIDE ENGINEERING FIRM CURRENT CERTIFICATE OF | | AUTHORIZATION AS REQUIRED BY CHAPTER 471 FLORIDA | | STATUTES. | | *** 4- REVISE SHEET A-1: | | A) REVISE ALL LOADS ON STRUCTURAL NOTE #2 TO MATCH | | LOADS SHOWN ON SHEET S-1. | | B) REVISE STRUCTURAL NOTE #14. WHAT'S 1/2" EXT. PLYWOOD | | VENT SYSTEM REQUIRED?. | | *** 5- PROVIDE SPECIFICATIONS FOR EXISTING GENERATOR TO | | VERIFY REQUIRED CLEARANCES FROM WALL. | | *** 6- ENERGY CALCULATIONS ARE TAKING THE CROSS | | VENTILATION CREDIT. PROVIDE INFORMATION SHOWING | | COMPLIANCE WITH THE CROSS VENTILATION REQUIREMENTS OF | | SEC. B4.1.3 OF CHAPTER 11 OF 2007 FLORIDA RESIDENTIAL | | CODE (2009 REVISIONS). |
|