Plan Review Notes
Plan Review Notes For Permit 08120059
Permit Number 08120059
Review Stop B
Sequence Number 1
Notes
Date Text
2008-12-03 12:04:07RESIDENTIAL (R2) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FBC WITH 2007 REVISIONS.
  
 1- PROPOSED ACCORDION SHUTTERS INSTALLATION DEVIATES
 FROM APPROVED PRODUCT EVALUATION DOCUMENT (P.E.D.).
 SITE SPECIFIC DRAWINGS NEED TO BE REVIEWED AND APPROVED
 BY THE P.E.D. ENGINEER AS REQUIRED BY GENERAL NOTE 12
 (D) OF SHEET 1 OF 14 OF DRAWING NO 05-196 OF FLORIDA
 PRODUCT APPROVAL FL389-R1 SUBMITTED. PROVIDE PROOF THAT
 P.E.D. ENGINEER APPROVED THE SITE SPECIFIC DRAWINGS.
  
  
 2- CLARIFY WHY THE ACCORDION SHUTTERS ARE GOING TO BE
 INSTALLED ON STEEL STUDS. ISN'T THIS IS A
 CONCRETE/MASONRY BUILDING?
  
 3- INSTALLATION SCHEDULE SUBMITTED STATES THAT OPENINGS
 ARE 47"X54". CLARIFY HOW COME THE SHUTTER SPAN IS 51".
 WHY IS IT SHORTER THAN THE OPENING AND HOW ARE YOU
 ACHIEVING THE 3 1/2" EDGE DISTANCE.
 ***NOTE: COORDINATE THIS INFORMATION WITH ITEM #1
 ABOVE.
  
 4- ENGINEER FOR SITE SPECIFIC DRAWINGS/CALCULATIONS
 NEED TO PROVIDE ORIGINAL SIGNATURE NOT COPY AS REQUIRED
 BY CHAPTER 471 FLORIDA STATUTES AND SEC. 61G15-23.002
 OF FLORIDA ADMINISTRATIVE CODE.
 SIGN AND SEAL ALL SHEETS THAT ARE PART OF THE SITE
 SPECIFIC DOCUMENTATION WITH ORIGINAL SEAL AND
 SIGNATURE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712