Notes |
Date |
Text |
2008-12-03 12:04:07 | RESIDENTIAL (R2) SHUTTERS, BUILDING REVIEW CHECKLIST. | | REVIEW UNDER 2004 FBC WITH 2007 REVISIONS. | | | | 1- PROPOSED ACCORDION SHUTTERS INSTALLATION DEVIATES | | FROM APPROVED PRODUCT EVALUATION DOCUMENT (P.E.D.). | | SITE SPECIFIC DRAWINGS NEED TO BE REVIEWED AND APPROVED | | BY THE P.E.D. ENGINEER AS REQUIRED BY GENERAL NOTE 12 | | (D) OF SHEET 1 OF 14 OF DRAWING NO 05-196 OF FLORIDA | | PRODUCT APPROVAL FL389-R1 SUBMITTED. PROVIDE PROOF THAT | | P.E.D. ENGINEER APPROVED THE SITE SPECIFIC DRAWINGS. | | | | | | 2- CLARIFY WHY THE ACCORDION SHUTTERS ARE GOING TO BE | | INSTALLED ON STEEL STUDS. ISN'T THIS IS A | | CONCRETE/MASONRY BUILDING? | | | | 3- INSTALLATION SCHEDULE SUBMITTED STATES THAT OPENINGS | | ARE 47"X54". CLARIFY HOW COME THE SHUTTER SPAN IS 51". | | WHY IS IT SHORTER THAN THE OPENING AND HOW ARE YOU | | ACHIEVING THE 3 1/2" EDGE DISTANCE. | | ***NOTE: COORDINATE THIS INFORMATION WITH ITEM #1 | | ABOVE. | | | | 4- ENGINEER FOR SITE SPECIFIC DRAWINGS/CALCULATIONS | | NEED TO PROVIDE ORIGINAL SIGNATURE NOT COPY AS REQUIRED | | BY CHAPTER 471 FLORIDA STATUTES AND SEC. 61G15-23.002 | | OF FLORIDA ADMINISTRATIVE CODE. | | SIGN AND SEAL ALL SHEETS THAT ARE PART OF THE SITE | | SPECIFIC DOCUMENTATION WITH ORIGINAL SEAL AND | | SIGNATURE. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|