2008-12-14 11:57:33REVIEW #: 1ST
 ACTION: PASS W/ PROVISO
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING RED-LINE NOTES HAVE BEEN PLACED ON PLANS.
 PLEASE MAKE CORRECTION, REVISE AND RESUBMIT CORRECTED
 PLANS FOR REVISION.
  
 **PROVISO**
 PAGE M2.1: THERE ARE TWO VAV BOXES LABELED AS
 "VAV-3-32" AND THERE IS NO VAV 3-21 SHOWN ON FLOOR
 PLAN. PLEASE CORRECT AND REVISE. FBCM 603.1 AND FBCB
 106.1.1.
  
 **PROVISO**
 PAGE M6.1: FLEX DUCT DETAIL CALLS FOR MIN. 1" WIDE
 STRAP FOR FLEX DUCT SUPPORT. THE SUPPORT SHALL BE MIN.
 1 1/2" WIDE IN ACCORDANCE WITH FBCM 603.5.6.6.
  