Plan Review Notes For Permit 08120054 |
Permit Number |
08120054 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-12-14 11:57:33 | REVIEW #: 1ST | | ACTION: PASS W/ PROVISO | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | THE FOLLOWING RED-LINE NOTES HAVE BEEN PLACED ON PLANS. | | PLEASE MAKE CORRECTION, REVISE AND RESUBMIT CORRECTED | | PLANS FOR REVISION. | | | | **PROVISO** | | PAGE M2.1: THERE ARE TWO VAV BOXES LABELED AS | | "VAV-3-32" AND THERE IS NO VAV 3-21 SHOWN ON FLOOR | | PLAN. PLEASE CORRECT AND REVISE. FBCM 603.1 AND FBCB | | 106.1.1. | | | | **PROVISO** | | PAGE M6.1: FLEX DUCT DETAIL CALLS FOR MIN. 1" WIDE | | STRAP FOR FLEX DUCT SUPPORT. THE SUPPORT SHALL BE MIN. | | 1 1/2" WIDE IN ACCORDANCE WITH FBCM 603.5.6.6. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|