Plan Review Notes
Plan Review Notes For Permit 08120054
Permit Number 08120054
Review Stop E
Sequence Number 1
Notes
Date Text
2008-12-09 13:26:45 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PER 13-415.2.ABC.1.1. PAGE #2 OF THE ENERGY GAUGE
 INPUT DATA REPORT, DOES NOT INDICATE THE CORRECT NUMBER
 OF FIXTURES AS SHOWN ON THE PLAN,
  
 2} THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING
 OR A SEPARATELY METERED OR PERMITTED PORTION OF A
 BUILDING SHALL BE DETERMINED BY EITHER THE BUILDING
 AREA METHOD DESCRIBED IN SECTION 415.2.C.1 OR THE
 SPACE-BY-SPACE METHOD DESCRIBED IN SECTION 415.2.B.1.
 THE INSTALLED INTERIOR LIGHTING POWER IDENTIFIED IN
 ACCORDANCE WITH SECTION 415.2.ABC.1.1 SHALL NOT EXCEED
 THE INTERIOR LIGHTING POWER ALLOWANCE DEVELOPED IN
 ACCORDANCE WITH SECTION 415.2.C.1 OR 415.2.B.1. THIS
 CAN BE DEMONSTRATED ON THE PLANS INDICATING THE
 WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT
 CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES
 ON THE FIXTURE SCHEDULE TO CORRELATE WITH THE ONES IN
 THE CALCULATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  