 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY. THE COST OF THE WORK BEING OVER
 $50,000 1. 471.003 REQUIRES AN ELECTRICAL OR PLUMBING
 OR AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A
 VALUE OF $50,000 OR LESS; AND 2(A) REQUIRES AN
 AGGREGATE SERVICE CAPACITY OF 600 AMPERES (240 VOLTS)
 OR LESS ON A RESIDENTIAL ELECTRICAL SYSTEM OR 800
 AMPERES (240 VOLTS) OR LESS ON A COMMERCIAL OR
 INDUSTRIAL ELECTRICAL SYSTEM;
  
 2} IF THE HEADS ARE BEING REPLACED PROVIDE
 MANUFACTURERS SPECIFICATIONS (WITH WATTAGE AND VOLTAGE)
 FOR SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  