Plan Review Notes For Permit 08110565 |
Permit Number |
08110565 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2009-05-15 14:24:03 | **DENIED 3RD REVIEW ** | | | | 1) NOTE: THE PREVIOUS NOTES STATED TO PLEASE BE SURE | | AND UPDATE AND COORDINATE ALL PLANS AND DOCUMENTS WITH | | THE CHANGES OF SITE LIGHTING TO THE BUILDING. | | THE SAME EXACT ENERGY CALCULATIONS WERE SUBMITTED BACK | | WITH NO CHANGES TO THE EXTERIOR LIGHTING IN THE INPUT | | DATA REPORT. PLEASE SEE FBC 13-415.2.ABC.1.3 WHICH | | REQUIRES ALL LIGHTING FOR EXTERIOR PORTIONS TO BE | | FIGURED. | | DO NOT REVISE ONE SHEET ON THE IDR AS WAS SUBMITTED FOR | | BUILDING. THE INFORMATION ON THE IDR WILL AFFECT | | SUMMARY SHEET AND TOTALS ON THE CALCULATIONS. THERE ARE | | MULTIPLE SHEETS IN THE CALCULATIONS SUMMARY AND IDR | | WHICH NEED TO BE REVISED. THE CERTIFICATION SHEETS AS | | WELL ALL NEED TO BE REVISED. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|