Notes |
Date |
Text |
2009-05-01 10:29:41 | ******DENIED***** | | | | *THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | PLAN REVIEW STILL NEED TO BE ADDRESSED. FOR SUGGESTION | | ON HOW TO ADDRESS THE COMMENT, SEE THE ATTACHED | | CAPITALIZED ITEM | | | | | | 1 THE ACTUAL/CORRECT ADDRESS SHALL BE IN THE TITLE | | BLOCK OF EACH SUBMITTED PLAN SHEET. SEE SHEETS LS-1 & | | LS-2. | | | | 2. ANY EXISTING AND/OR PROPOSED FIRE HYDRANT(S) SHALL | | BE IN SERVICE PRIOR, DURING, AND AFTER CONSTRUCTION. | | ADD COMMENT TO SHEET C5 | | | | 4. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS | | AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | INTERIOR FINISH MATERIALS HAVE BEEN INDICATED, HOWEVER | | BE ADVISED THAT THE 2003 EDITION OF NFPA 101 SHALL BE | | REFERENCED (THE CORRECT CODE REFERENCES ARE SHOWN ON | | SHEETS CS AND A-101) | | | | | | *NEW COMMENTS: | | | | A. PLAN SHEET LS-2 NOT STAMPED/SEALED AND SIGNED. | | | | B. PLAN SHEET EP1 (WHICH WAS INCLUDED IN THE FIRST | | SUBMITTAL) COULD NOT BE LOCATED WITH THIS SUBMITTAL. BE | | ADVISED THAT THE COVER SHEET (CS) INDICATES THAT THERE | | IS A EP1 SHEET. | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|