Plan Review Notes
Plan Review Notes For Permit 08110565
Permit Number 08110565
Review Stop E
Sequence Number 2
Notes
Date Text
2009-04-20 12:15:44** DENIED **
  
  
  
 1) NOTE: PLANS STATE METHOD *C* AND THE SUBMITTED FLA
 COM IS METHOD *B*. MAY NOT USE BOTH PER 13-415.2.ABC.1.
 THE EXTERIOR SITE PLANS ALSO CONTAINS SITE LIGHTING
 CIRCUITED TO THIS BUILDING WHICH IS NOT IN THE IDR. THE
 NOTES ON SITE PLANS MENTIONS THE SITE WILL BE ON THE
 BASE PROPERTY SERVICE HOWEVER AS NOTED THE CIRCUITS ARE
 FROM THIS BUILDING. ALL LIGHTING ON THIS SEPARATE LEGAL
 PCN SHALL BE FED FROM THIS BUILDING NOT THE SITE
 BUILDING OR SITE SERVICE. PLEASE COORDINATE ALL PLANS.
 BASED ON THE LEGAL SITE SURVEY THERE ARE SOME LIGHT
 POLES ON THIS PROPERTY NOT CIRCUITED TO THIS BUILDING
 AND A POLE ON THE BASE SITE OF THE SHOPPING CENTER
 WHICH WOULD BE FED FROM THE SHOPPING CENTERS ELECTRICAL
 SERVICE?
 ALL PLANS AND SHEETS NEED TO COORDINATE AND BE UPDATED.
 PLEASE TAKE A LOOK AT THE SITE SURVEY FOR THIS LEGAL
 PROPERTY.
 6 FIXTURES SHOULD BE FED FROM THIS BUILDING AND ONLY
 ONE WOULD BE FED FROM SHOPPING CENTER ELECTRICAL
 SERVICE. THIS IS BASED ON THE LEGAL SITE SURVEY.
  
 13-415.2,13-415.2.ABC.1.1,.1.2 AND.1.3
  
 2) NOTE: ***** NOTE FOR INFORMATIONAL. THE ACCOUNTING
 OFFICE AS SHOWN UNDER SUITE 101A MAY NOT BE A SEPARATE
 LEGAL TENANT. THIS MUST BE THE SAME TENANT AS THE
 DENTAL OFFICE. A TENANT MUST HAVE ACCESS TO ALL OVER
 CURRENT PROTECTION DEVICES AT ALL TIMES. SEPARATE
 TENANTS MAY NOT SHARE ELECTRICAL CIRCUITS ALL COMING
 FROM ONE PANEL LOCATED IN ANOTHER TENANTS SPACE.
 ** THIS WILL BE NOTED ON PLANS AS ALL ONE TENANT.
 THIS NOTE #2 IS NOTED ONLY FOR INFORMATION SO THAT
 DESIGN TEAM AND OWNER HAVE A CLEAR UNDERSTANDING THAT
 101 AND 101A IS ONE TENANT.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717