2009-04-15 16:44:33 | BUILDING PLAN REVIEW |
| PERMIT: 08110565 |
| ADD: 2112 N JOG RD |
| CONT: POPPER AND ASSOCIATES |
| TEL: (561)719-7133 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 1B) COMPLIED. |
| |
| 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. PLEASE |
| UPDATE COVERSHEET TO INCLUDE THE 2007 SUPPLEMENTS, THE |
| PERMIT APPLICATION DATE INDICATES A FIRST TIME |
| SUBMITTAL DATE OF NOV. 25, 2008. |
| |
| 2) COMPLIED. |
| |
| 3) SEMI COMPLIED ENERGY CALCULATION METHOD B. |
| |
| 4) COMPLIED. |
| |
| 5) SEMI-COMPLIED. THE ENERGY INPUT DATA REPORT |
| INDICATES THE ROOF INSULATION VALUE OF R28.4.THE NOA |
| SUBMITTED NOA 08-0221.05 SUB-SYSTEM TYPE A(1) INDICATES |
| THE USE OF MULTIPLE LAYERS OF INSULATION CAN BE USED. |
| PLEASE PROVIDE A ROOFING SHOP DRAWING FOR THE ROOF |
| INSULATION AND HOW THE R VALUE OF 28.4 WILL BE MET? |
| |
| 6) COMPLIED.I |
| |
| 7) COMPLIED. |
| |
| 8) COMPLIED. |
| |
| 9) COMPLIED. |
| |
| 10) COMPLIED. |
| |
| 11) THE RESPONSE FOR THIS COMMENT INDICATES STORM |
| SHUTTERS WILL NOT BE REQUIRED, ALL WINDOWS FOR THIS |
| BUILDING WILL BE IMPACT RESISTANT. PLEASE REVIEW THE |
| PRODUCT APPROVALS THAT WERE REVIEWED BY YOUR OFFICE |
| WITH A SHOP DRAWING STAMP AS NON-IMPACT. SHEET |
| A-101FLOORPLAN DOES NOT INDICATE ANY STORAGE ROOMS FOR |
| THE STORM SHUTTERS. THE DESIGNER HAS ELECTED TO USE |
| STORM PANELS BUT NO STORAGE AREA IS LOCATED WITHIN THE |
| BUILDING. PLEASE PROVIDE STORAGE ROOM AND THE |
| FOLLOWING: |
| PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR |
| WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13 |
| RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES |
| WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE |
| SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT |
| MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE |
| THAT COMPLETE INSTALLATION OR SECURING IS DONE |
| SUFFICIENTLY IN ADVANCE OF THE HURRICANE? |
| |
| IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE |
| GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE, |
| SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING, |
| CHAPTER 1, |
| ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY |
| OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE |
| BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR |
| ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION |
| OF EXISTING BUILDINGS. |
| |
| IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR |
| MULTI-STORY BUILDINGS, OR MULTIPLE |
| ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST |
| BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS |
| FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY |
| SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION |
| OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE |
| SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH |
| COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND |
| THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS. |
| PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN |
| TWELVE (12) HOURS OR LESS OF THE |
| OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES |
| OF A HURRICANE WATCH. |
| |
| PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD) |
| ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE |
| MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO |
| REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN |
| QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE, |
| DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED |
| UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE |
| MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE |
| BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO |
| SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE. |
| |
| IN LEAU OF LARGE MISSILE IMPACT RATED WINDOWS, STORM |
| SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/ |
| 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT |
| PROTECTION. |
| |
| 12) SEMI COMPLIED, A NEW FLAT ROOF PRODUCT APPROVAL HAS |
| BEEN SUBMITTED NOA 08-0221.05 SUBSYSTEM TYPE A(1) WITH |
| A MAXIMUM DESIGN PRESSURE OF -45. THIS BUILDING DOES |
| HAVE A 3'-0" PARAPET ELIMINATING THE REQUIREMENTS FOR |
| ZONE 3 FASTENING. THE PERIMETER OF THE BUILDING WILL |
| STILL NEED ENHANCED FASTENING FOR ZONE 2 NEEDING TO |
| MEET THE REQUIREMENT OF -59.2 PSF. |
| THIS NOA LIST LIMITATION# 7 THAT ALLOWS FOR ENHANCED |
| FASTENING FOR BOTH THE INSULATION AND BASE SHEET AS |
| CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION |
| STANDARD 117. CALCULATIONS PREPARED SIGNED AND SEALED |
| BY EITHER A FLORIDA REGISTERED ARCHITECT, FLORIDA |
| REGISTERED ENGINEER OR REGISTER ROOF CONSALTANT . |
| NOTE COMMENT# 5 WILL ALSO NEED TO BE ADDRESSED AS TO |
| THICKNESS OF INSULATION TO REACH A R VALUE OF 28.4. |
| |
| 13) COMPLIED. |
| |
| 14) BUILDING PROVISO: KITCHEN W/ HC SINK.: |
| 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| COMPLYING WITH SECTION |
| 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW |
| FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN |
| ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 |
| INCHES (485 MM) UNDERNEATH THE SINK. |
| |
| 15 A-B) COMPLIED. |
| |
| 15C) SEMI COMPLIED- FLAT ROOF NOA, SEE COMMENTS 5 & 12. |
| |
| 16-20) COMPLIED. |
| |
| 21) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |