2009-04-15 16:44:33BUILDING PLAN REVIEW
 PERMIT: 08110565
 ADD: 2112 N JOG RD
 CONT: POPPER AND ASSOCIATES
 TEL: (561)719-7133
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) COMPLIED.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. PLEASE
 UPDATE COVERSHEET TO INCLUDE THE 2007 SUPPLEMENTS, THE
 PERMIT APPLICATION DATE INDICATES A FIRST TIME
 SUBMITTAL DATE OF NOV. 25, 2008.
  
 2) COMPLIED.
  
 3) SEMI COMPLIED ENERGY CALCULATION METHOD B.
  
 4) COMPLIED.
  
 5) SEMI-COMPLIED. THE ENERGY INPUT DATA REPORT
 INDICATES THE ROOF INSULATION VALUE OF R28.4.THE NOA
 SUBMITTED NOA 08-0221.05 SUB-SYSTEM TYPE A(1) INDICATES
 THE USE OF MULTIPLE LAYERS OF INSULATION CAN BE USED.
 PLEASE PROVIDE A ROOFING SHOP DRAWING FOR THE ROOF
 INSULATION AND HOW THE R VALUE OF 28.4 WILL BE MET?
  
 6) COMPLIED.I
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) COMPLIED.
  
 11) THE RESPONSE FOR THIS COMMENT INDICATES STORM
 SHUTTERS WILL NOT BE REQUIRED, ALL WINDOWS FOR THIS
 BUILDING WILL BE IMPACT RESISTANT. PLEASE REVIEW THE
 PRODUCT APPROVALS THAT WERE REVIEWED BY YOUR OFFICE
 WITH A SHOP DRAWING STAMP AS NON-IMPACT. SHEET
 A-101FLOORPLAN DOES NOT INDICATE ANY STORAGE ROOMS FOR
 THE STORM SHUTTERS. THE DESIGNER HAS ELECTED TO USE
 STORM PANELS BUT NO STORAGE AREA IS LOCATED WITHIN THE
 BUILDING. PLEASE PROVIDE STORAGE ROOM AND THE
 FOLLOWING:
 PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13
 RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES
 WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT
 MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING IS DONE
 SUFFICIENTLY IN ADVANCE OF THE HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE
 ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST
 BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS
 FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 IN LEAU OF LARGE MISSILE IMPACT RATED WINDOWS, STORM
 SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/
 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION.
  
 12) SEMI COMPLIED, A NEW FLAT ROOF PRODUCT APPROVAL HAS
 BEEN SUBMITTED NOA 08-0221.05 SUBSYSTEM TYPE A(1) WITH
 A MAXIMUM DESIGN PRESSURE OF -45. THIS BUILDING DOES
 HAVE A 3'-0" PARAPET ELIMINATING THE REQUIREMENTS FOR
 ZONE 3 FASTENING. THE PERIMETER OF THE BUILDING WILL
 STILL NEED ENHANCED FASTENING FOR ZONE 2 NEEDING TO
 MEET THE REQUIREMENT OF -59.2 PSF.
 THIS NOA LIST LIMITATION# 7 THAT ALLOWS FOR ENHANCED
 FASTENING FOR BOTH THE INSULATION AND BASE SHEET AS
 CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARD 117. CALCULATIONS PREPARED SIGNED AND SEALED
 BY EITHER A FLORIDA REGISTERED ARCHITECT, FLORIDA
 REGISTERED ENGINEER OR REGISTER ROOF CONSALTANT .
 NOTE COMMENT# 5 WILL ALSO NEED TO BE ADDRESSED AS TO
 THICKNESS OF INSULATION TO REACH A R VALUE OF 28.4.
  
 13) COMPLIED.
  
 14) BUILDING PROVISO: KITCHEN W/ HC SINK.:
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION
 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK.
  
 15 A-B) COMPLIED.
  
 15C) SEMI COMPLIED- FLAT ROOF NOA, SEE COMMENTS 5 & 12.
  
 16-20) COMPLIED.
  
 21) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.