Date Text
2009-01-22 10:21:36DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 NFPA-99C
  
 1. SHT A-108 FINISH SCHEDULE INDICATES PAINTED WALLS
 FOR THE TOILET ROOM A-105. PER SECTION 1210.2 WALLS
 WITHIN 2 FEET OF THE WATER CLOSET SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE TO A HEIGHT OF 4 FEET ABOVE
 THE FLOOR. PAINTED SURFACES DOES NOT MEET THE HARD
 REQUIREMENT OF THIS CODE SECTION. PLEASE INDICATE
 METHOD OF COMPLIANCE.
  
 2. SHT A-108 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___LAV:
 A. 11-4.19.2 CLEARANCE HEIGHT
 B. 11-4.19.5 FAUCETS
  
 3. SHT P-1 PLAN KEY NOTES NUMBER 3 & NUMBER 4 INDICATES
 EXISTING 4" SANITARY LINE AND NUMBER 5 INDICATES 3/4"
 WATER LINE CONNECTING TO EXISTING. PLEASE CLARIFY AS
 THIS IS A NEW BUILDING. SECTIONS 106.1.1, 106.1 &
 107.1.
  
 4. SHOW THE LOCATION & INDICATE THE SIZE OF THE WATER
 SERVICE AND SHOW THE REQUIRED RPZV BACKFLOW AT THE
 METER. SECTIONS 603.1 & 608.13.2.
  
 5. SHT P-1 PLAN KEY NOTES NUMBER 8 IS NOT APPROVED.
 LIQUIDS FROM A LEVEL 3 VACUUM SYSTEM, PER 4-5.2.2,
 SHALL BE DIRECTLY CONNECTED TO THE SANITARY DRAINAGE
 SYSTEM THROUGH AN APPROPRIATELY TRAPPED AND VENTED
 DRAIN. SECTION 405.2.1.3.
  
 6. ALL CENTRAL VACUUM (FLUID SUCTION) SYSTEMS. THE
 EXHAUSTS FROM A VACUUM PUMP SERVICE A VACUUM (FLUID
 SUCTION) SYSTEM SHALL DISCHARGE SEPARATELY TO OPEN AIR
 ABOVE THE ROOF. SECTION 713.6.
  
 7. SHT P-2 THE SANITARY & DOMESTIC WATER RISER DIAGRAMS
 SHOW THE SYSTEMS CONNECTING TO EXISTING SYSTEMS. PLEASE
 CLARIFY AS THIS IS A NEW BUILDING. SECTIONS 106.1.1,
 106.1 & 107.1.
  
 8. SHT P-2 TANKLESS WATER HEATER DETAIL. FULL OPEN
 VALVES ARE REQUIRED ON THE WATER SUPPLY PIPE TO EVERY
 WATER HEATER. SECTION 606.1(7). PLEASE INDICATE VALVES
 ON DETAIL.
  
 9. SHT P-2 DOMESTIC WATER RISER DIAGRAM SHOWS A 1/2"
 WATER SUPPLY LINE TO THE VACUUM SYSTEM. THE WATER LINE
 SHALL BE PROVIDED WITH PROTECTION AGAINST BACKFLOW &
 CONTAMINATION OF THE WATER SUPPLY SYSTEM. SECTION
 608.3. PLEASE INDICATE METHOD. PLEASE SUBMIT MANUF.
 SPECIFICATIONS & INSTALLATION INSTRUCTIONS FOR THE
 VACUUM SYSTEM. SECTION 106.1.2 (MORE INFORMATION
 REQUIRED).
  
 10. THE ENERGY CALCULATIONS DO NOT INDICATE WATER
 HEATER - 3 NOR DOES IT INCLUDING THE REQUIRED PIPING
 INSULATION. CHAPTER 13 ENERGY EFFICIENCY
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  